Generac: Smart Management Module Installation, 100 AMP

  Рет қаралды 8,808

Electrician Ron

Electrician Ron

7 ай бұрын

In this video a #generac #generator Smart Management Module load-shedding device is installed. This allows for smaller air-cooled generators to supply loads "only if" the generator is able to start larger electrical loads such as heated Hot Tub. Always contact a Generac Certified contractor for sizing, maintaining, and servicing your Generac standby generator.
Electrical Wiring is NOT a hobby. Call a licensed electrician!
www.generac.com
Classic Electric, LLC is a Generac standby air-cooled generator installer.
Generac Dealer # 1019500
Classic Electric, LLC | Point Pleasant, New Jersey
License & Business # 16557
(732)-770-1437
Ron Pecina Jr. is a licensed electrician in the state of New Jersey. This allows him to apply for electrical permits, work with live conductors, remove meters, and disconnect service from the utility company. New Jersey observes the 2020 NEC and the Uniform Construction Code. The majority of the work seen here on this channel falls under the Rehabilitation Sub Code (Chapter 6 of the U.C.C.). The majority of the work you’ll see on my channel falls under the New Jersey Rehabilitation Subcode. www.nj.gov/dca/divisions/code...
ALL New Jersey licensed electricians MUST complete 34-hours of continuing education units each tricentennial period. This includes a mandatory 10-hour code update course. Any work above 10-volts requires an electrical license in New Jersey.
Ron is an active member of the New Jersey Independent Electrical Contractors Association.
Want to be an electrician? Start here: www.myelectriccareer.com
Become an NJ-IEC member here: www.nj-iec.org
IEC National: www.ieci.org
Customer Guide for Electrical Installation; JCPL: www.firstenergycorp.com/conte...
Customer Guide for Electrical Installation; PSEG: nj.pseg.com/businessandcontra...
WANT TO SEE MORE? FULL 200 AMP SERVICE UPGRADE. WATCH HERE: • FULL 200 AMP SERVICE U...
Ron Pecina Jr’s set up:
Camera: Go Pro 9/ 10 w/ the Media Mod
Microphone: DJI Wireless
Editing software: Apple iMovie
Animation software: Apple Keynote
Background Music & Sound Effects by Soundstripe.com
Like, Share, and Subscribe!

Пікірлер: 37
@mars617
@mars617 Ай бұрын
I have a 20KW Cummins genny and a Generac SMM on my electric hot water tank. Have had several outages and it it set to wait 5 min. So far 2 years later works well. Excellent video as usual
@Framdark
@Framdark 7 ай бұрын
I really appreciate the work you put into your videos have a great Christmas Ron!
@Nahum17good
@Nahum17good 7 ай бұрын
I always enjoy watching your videos. They’re very inspiring. Have a Merry Christmas Ron.
@electricalron
@electricalron 7 ай бұрын
Thanks! You too!
@JMDangler
@JMDangler 7 ай бұрын
Haha @10:37 been there before. The I wish I had more hands moment. SOAB is the technical term for it. Great video, keep trucking Ron 🎉
@mattschoular8844
@mattschoular8844 7 ай бұрын
Another nice job. Merry Christmas Ron
@MC-ig8cm
@MC-ig8cm 7 ай бұрын
Merry Christmas I enjoy your videos! Thank you
@BigD63
@BigD63 6 ай бұрын
Ron, once again great video. Merry Christmas to you and yours. Happy new year. Best regards from Chicago
@mackfisher4487
@mackfisher4487 7 ай бұрын
Ron Merry Christmas Thank you for all the great videos, and continuing regardless of some of us not being kind in our comments. Ego jumps out in many of them, I suspect that people forget the golden rule.
@ChristopherKotch
@ChristopherKotch 7 ай бұрын
Merry Christmas and a Happy to New Year to you and yours also...((Its nice to see people still saying that....and not just Happy Holidays!!!))
@scottdenham848
@scottdenham848 7 ай бұрын
Great videos Ron, working with frequency makes sense because the hertz goes down with increasing load (reducing speed below 3600 RPM.) An innovative way to do it. Merry Christmas.
@kesleicarvalho4062
@kesleicarvalho4062 7 ай бұрын
Nice job, Ron. Congratulation
@PaulDziomba
@PaulDziomba 7 ай бұрын
Merry Christmas and a Happy New Year to you and all your subscribers as well!
@electricalron
@electricalron 7 ай бұрын
Coming from a Flyers fan that's awfully nice of you! Haha!
@katyair1
@katyair1 7 ай бұрын
I hope you had a good Christmas and happy New Year🎊
@Bob.W.
@Bob.W. 7 ай бұрын
Dig the pull chain headgear. Thx. Have a Merry Christmas.
@davidbush2414
@davidbush2414 6 ай бұрын
I like the video. You’ve got some great content. New subscriber 👍🏻
@electricalron
@electricalron 6 ай бұрын
Thank you, David!
@chuckquinn8026
@chuckquinn8026 7 ай бұрын
Sweet! Merry Christmas to you and your family Ron! Fur babies too ❤️. 🎅🎅🎅
@jw228w
@jw228w 4 ай бұрын
thanks for the video.in a residential home does each large load require its own relayer can one relay handle more than one load with different priority settings?thanks John
@gosolxsolar
@gosolxsolar 6 ай бұрын
Hmm. Nice video. Just trying to understand. You said the red marked conductors were for loads and black for line. But you have the red ones going to the circuit breaker which i would call line terminals since power comes from those. I would call the hot tub conductors load, but you have those marked black. What am i missing? Also, is it really just 1 circuit per smm?
@donmclean1220
@donmclean1220 5 ай бұрын
Plumbers would call the nut on the flex a “compression nut” I think.
@sixfour7
@sixfour7 6 ай бұрын
Did you consider AC Soft Starter?
@electricalron
@electricalron 6 ай бұрын
No.
@wirenut9062
@wirenut9062 2 ай бұрын
Offset and bonded locknut...no ?
@dogboy19d31
@dogboy19d31 6 ай бұрын
So no control wiring needed to the transfer switch?
@electricalron
@electricalron 6 ай бұрын
Nope!
@scotts4125
@scotts4125 7 ай бұрын
Generac had defective 60amp load sheds. If the PCB is green it's one of the problematic ones. The load shed stays open as a row of caps or resistors (I forgot which) burns out. The revised replacement boards are blue. In my case one of my A/C's stopped working. I had power from the breaker but no power at the A/H. It had me stumped until I remembered the load sheds. On utility power your device will not work if the board is fried. I bypassed the contactor and everything worked again. I later found out you can just disconnect the wire going to the board and the contactor will close. It works the opposite of an A/C contactor. It's normally closed pulled in is open. The replacement blue board fixed it.
@electricalron
@electricalron 7 ай бұрын
why would you need load sheds on the air handler? Its the condensing units that consume power during start up, not a blower motor on the furnace/ air handler.
@scotts4125
@scotts4125 7 ай бұрын
@@electricalron That's a great question and I thought the same thing. The generator company did the install. I never checked power to the condenser. My Tstat was out. That's how I noticed there wasn't power. I assumed it was the float switch. It wasn't that. I'm a DIYer so it took me a couple hours to figure out it was the load shed. I couldn't understand how I had power at the breaker and nothing at the A/H. At one point I wondered if a critter ate both lines in the attic but didn't short the wires out. lol I was grasping! They probably hooked it up wrong. I also have a second unit but that load shed is a PSP which from everything I have read is a much better unit.
@electricalron
@electricalron 7 ай бұрын
what size generator? @@scotts4125
@scotts4125
@scotts4125 7 ай бұрын
@@electricalron 22kw House is 3200 sq ft.
@price9195
@price9195 7 ай бұрын
Kohler uses time delay contactor on the "y" thermostat wired in series back to the compressor. Keeps the compressor off until the time delay contactor comes on in the transfer switch. Nice way and the wire is low voltage side of the equipment. Thanks for all the great videos Ron!
@Californians_go_home
@Californians_go_home 7 ай бұрын
Anytime I see the word SMART in a system of technology, I assume the government or tech has the ability to lock you out of it.
@electricalron
@electricalron 7 ай бұрын
Unless you have your own power plant, the govt has been able to do that since the advent of electricity.
@Californians_go_home
@Californians_go_home 7 ай бұрын
Wait until they only give us an ‘allowance’ per month. The county next to me has already banned natural gas installation for new builds, and no wood heat. Seems pretty easy to flip a switch on us now so we can comply. If we want food. It’s also why I keep an older car that doesn’t connect to WiFi . Love the channel Ron!
100 AMP TO 200 AMP PANEL UPGRADE | Sunny Side Linden, NJ.
20:26
Electrician Ron
Рет қаралды 52 М.
WHAT’S THAT?
00:27
Natan por Aí
Рет қаралды 13 МЛН
Зачем он туда залез?
00:25
Vlad Samokatchik
Рет қаралды 3,3 МЛН
마시멜로우로 체감되는 요즘 물가
00:20
진영민yeongmin
Рет қаралды 33 МЛН
Whole-Home Generators: Peace of Mind or Financial Liability?
13:04
Electric Pro Academy
Рет қаралды 71 М.
Problems with our Generac generator install
12:57
Maynard Family Homestead
Рет қаралды 172 М.
Generac Generator Installation Part 1  | Clark, NJ
22:26
Electrician Ron
Рет қаралды 64 М.
Thinking of purchasing a generac whole home generator?
12:34
Just Can’t Sit Still
Рет қаралды 655 М.
200 AMP ELECTRIC SERVICE RISER REPLACEMENT #electrical #electrician
31:01
How much fuel does a 24kw Generac standby generator use?
6:15
Maynard Family Homestead
Рет қаралды 40 М.
How To Perform Annual Schedule A Maintenance Generac 20kw Automatic Whole House Standby Generator
10:56
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 36 М.
Keep Your Family Warm During A Power Outage By Installing This $5 Part
11:47
The DIY HVAC Guy
Рет қаралды 1,6 МЛН
iShowSpeed Does a Backflip into the WATER🤯⚡️
0:15
Reidar
Рет қаралды 29 МЛН
Cleaning gadgets #food #funny #comedy
0:19
IK REACTS
Рет қаралды 15 МЛН
LA  CINTA NUESTRA HISTORIA
0:59
Santi
Рет қаралды 16 МЛН
My Hero Brother‼️ How to Survive Swimming Pool😎 Like a Boss💕❤️😘 | JJaiPan #Shorts
0:49