The maximum number of strobes on a single notification appliance circuit shall not exceed 50. CAUTION: These notification appliances are UL Listed as “Regulated”
@jagathchamila29802 жыл бұрын
can we fixing how many maximum smoke detectors to one zone in conventional panel.?
@bdelectricalcircuitdiagram2 жыл бұрын
NFPA 72 standards is 12 No's but you can connect 20 device one zone in conventional panel.
@anilgarg572 жыл бұрын
How does the battery stay charged? There is no charger.
@bdelectricalcircuitdiagram2 жыл бұрын
No need any charge, The controller have inside charger and DC controller. Thanks
@md.biplobhossain2958 Жыл бұрын
❤ good
@bdelectricalcircuitdiagram Жыл бұрын
Thanks
@edwardsampson8453 жыл бұрын
Hello that is cool please can I set a repeater with this panel
@bdelectricalcircuitdiagram3 жыл бұрын
NO, repeater use for addressable panel
@IsmailHossain-jn3vv3 жыл бұрын
Please make protection system video of addressable systems.
@bdelectricalcircuitdiagram3 жыл бұрын
Thanks, I will try to upload.
@FarooqKahn-sr4ns Жыл бұрын
@@bdelectricalcircuitdiagram و.
@tokolitheo53672 жыл бұрын
How much is the training for this course
@bdelectricalcircuitdiagram2 жыл бұрын
Its free
@imrankhan11294 жыл бұрын
Nice 👌 thanks
@josephgrajales22392 жыл бұрын
Can i get the toping points diagram for each terminals sir !?
@bdelectricalcircuitdiagram2 жыл бұрын
Please see me message on Facebook I will help you sir -facebook.com/ecommonroombd
@raeeskhankhan24654 жыл бұрын
How much difference between divices
@bdelectricalcircuitdiagram4 жыл бұрын
Smoke detectors do not have a listed spacing. They have a recommended spacing of 30 feet between detectors. However, smoke detectors can be installed up to 41 feet apart in corridors up to 10 feet wide. The main fact to remember is that all points on the ceiling must be within 21 feet of the detector.
@raeeskhankhan24654 жыл бұрын
Thnks sir
@bdelectricalcircuitdiagram4 жыл бұрын
@@raeeskhankhan2465 Welcome
@raeeskhankhan24654 жыл бұрын
@@bdelectricalcircuitdiagram sir how much of hight of soundr nd mcp top of flor
@bdelectricalcircuitdiagram4 жыл бұрын
@@raeeskhankhan2465 A standard sounder/strobe or individual strobe should be mounted 2.1m above the floor and not closer than 150mm from the finished ceiling.
@hindurashtrrawat4833 жыл бұрын
Thanks
@bdelectricalcircuitdiagram3 жыл бұрын
Welcome
@GMUrduPlus3 жыл бұрын
Good
@bdelectricalcircuitdiagram3 жыл бұрын
Thanks
@imrankhan11294 жыл бұрын
My conventional panel indicators General fault How to reset
@Dime_Bar2 жыл бұрын
Fix the fault then press reset.
@mahamudulhashan86182 жыл бұрын
Tycon conventional panel wearing full review Please