When you do the churn test and you start the pump by dropping pressure through the sensing line, that is automatic start if the pump is on a 10 min. Timmer it will automatically shut off..so you should always time it..if no automatic shut off then you have to manually press the stop button. And it should be noted on the controller or pump inspection tag as to whether it has a 10 minute run timer...remember if you manually start pump via the start switch you have to manually stop..the auto stop usually only works when you automatically start. Also while the pump is running you should check the packing and bearing to ensure they are not getting hot..Ethier by touch or use a infrared heat gun
@ikennaogwogwo4 жыл бұрын
Very nice. Can you share you email to me, I'd like to ask you some questions. Here is mine : ogwogwoikenna@gmail.com Thank you.
@jonijimene4 жыл бұрын
In NYC, fire pumps can ONLY be stopped by manually
@ronfranz75789 ай бұрын
When doing a churn test it is advisable that there are certified oil filled gauges on the sensing lines for both the jockey and fire pumps. These are a better read when dropping pressure than the reading in the controller. Depending also by the AHJ or insurance company some locations what you to close the valve on the discharge side when doing the test because catastrophic failure can happen. The jockey pump on the wall should not be part of a bid anymore because its the cheapest thing that you can install. It was hard to tell inn the video but I never saw a casing relief valve as you showed an air relief. Lastly some pump runs are just a supervisory/trouble. It is always been recommended to tie it in as an alarm. As an example the security guard silenced the trouble on the panel from a smoke detector being out. The pump started inn the pump house on a Friday night and there was smoke coming out of the pump house on a Monday morning. This is why an alarm is suggested.
@jeffhail57785 жыл бұрын
Good training. Thanks.
@locksmithsilva116315 күн бұрын
I’m here at a job checking the pump because the maintenance here says that when pumps on although the water drains the room fills up with water up to 2”. Is there a reason this happens?
@willlock3644 Жыл бұрын
6:30 No. You cannot do drain tests or whatever during the churn test. It’s in the name. Churn test. That pump needs to churn for 10 minutes. Again…churn. The casing relief valve is being exercised during the churn as well.
@gilsgarageofficial4 ай бұрын
In this video, which valve would you close to prevent catastrophic failure during a churn test? I know NFPA 25 requires it but company policy is to close it before conducting test for liability reasons.
@ryanyetman1335 Жыл бұрын
Can I shut the os&y to the header or shut the systems off on the butterfly to not pump the systems up ,
@angelvaltierra63562 ай бұрын
If hooked up to fdc. How do I know if fire pump stopped working.
@willlock3644 Жыл бұрын
I was really hoping that you would explain what the air release valve is four… Downstream of the pump. 🤦🏼♂️
@ikennaogwogwo4 жыл бұрын
Is it normal for water to leak through the suction side of the pump(This is close to the impeller).
@fidelbautista15613 жыл бұрын
if that is on the packing gland, yes its normal
@joseaguilar5845 жыл бұрын
Question: What about the pressure on the field? After the test should we open a drain valve to reduce pressure? Thank you!
@luizbueno42935 жыл бұрын
By the NFPA 20, the system pressure needs to be maintained close to the main fire pump churn discharge pressure to minimize pressure surges in the pipeline. So, you should not reduce the system pressure after the test. I hope it helps you!
@jj13jh Жыл бұрын
Doing a pump run do i shut any valves off will pressure the whole system?
@rittachannelinturkiye_93282 жыл бұрын
good luk my frind
@fredbarnich81454 жыл бұрын
Look like the casing relief valve you are showing look like more like a Air vent? I can be wrong, never mind the main relief valve is under the Air vent
@willlock3644 Жыл бұрын
Also…you cannot leave while the pump is running.
@mustangfox302ho3 жыл бұрын
Joslyn Clark controller, wonder if it's been replaced by now.
@LiamKianAdventures5 жыл бұрын
how do you replace the back up battery?
@sircampbell12493 жыл бұрын
Hard to hear what your saying with pump on ...
@ann0ynim0us4 жыл бұрын
hi there, judging from the video, it looks like there's only a single pumpset for this fire protection service? do you guys practice the 1 duty 1 standby pumpset philosophy or is that not a requirement in NFPA?
@daninraleigh2 жыл бұрын
You must be in a rich country to ask a question like that
@ann0ynim0us2 жыл бұрын
@@daninraleigh naw, I'm in a country with different rules.
@mikefuentes26572 жыл бұрын
If it was the French alps and the systems were turned off yes
@ironmatic1 Жыл бұрын
@@ann0ynim0us Where??? There's a very small jockey pump but that's just to maintain normal pressure.