Sprinklermatic Fire Pump Demonstration

  Рет қаралды 405,233

Sprinklermatic

Sprinklermatic

Күн бұрын

www.Sprinklermatic.net
One of our experienced and NICET Certified field superintendants runs us through the operation, maintenance, start up and shut down procedures of an electric driven fire pump. With our vast experience and knowledge of the fire protection industry we provide a one stop shop for all your fire protection needs.

Пікірлер: 129
@drewm6925
@drewm6925 10 жыл бұрын
I'm a firefighter and your detailed explanation has helped me understand this vital portion of my job. Thank you for your time, your expertise, and for taking the initiative of making it available.
@FurmanLeadership
@FurmanLeadership 8 жыл бұрын
I learned more about fire pumps watching this video than I ever did from reading about them in the fire academy. Great explanation. We actually had a call today where a loss of pressure had caused a big pump like this one to come on at the local state college. Felt good knowing how to get the system property shut down and reset.
@alanharrigan2965
@alanharrigan2965 10 жыл бұрын
Scott Gordon deserves a raise. I've been around plenty of so called Sprinkler technicians that "know" what they are doing. I can only think of one that could hold a conversation with this guy. Great explanation!!
@waynenicholson1172
@waynenicholson1172 8 жыл бұрын
This is by far the most informative and instructive tutorial I have seen in fire protection, keep up the great work....
@themetalhead1463
@themetalhead1463 3 жыл бұрын
I’m a fire extinguisher tech but I sometimes have to help the sprinkler techs and this helped to understand things.
@jamesbradyjr8067
@jamesbradyjr8067 3 жыл бұрын
Definitely explains a lot I haven't put in a fire pump in 12 years and I don't know where I got in my head that the bypass valves had to stay closed the only thing that stays closed is the fire pump test header I felt like such an idiot when I was doing my tampers and flows today,, I'll know better next time. A very good refresher course video.
@Sprinklermatic
@Sprinklermatic 3 жыл бұрын
Thank you for your feedback, James. We are always learning, always growing and appreciate your input!
@justinharrison5159
@justinharrison5159 7 жыл бұрын
Nice to see someone who actually knows what their doing. Good job brother.
@danielblanke9427
@danielblanke9427 5 жыл бұрын
Young fitters should take note - this man's hands are clean because of what he knows. Put your time in and learn this trade and it will take care of you.
@MarzD1
@MarzD1 12 жыл бұрын
I do fire pump testing about every other day in NYC high risers, pal. We do a churn with closed discharge and then we do another churn to get pressure at top of the head to help reset relief valve.
@fitter5426
@fitter5426 6 жыл бұрын
You need fore for closing that valve. Your never supposed to close that valve even when your working in the fire pump cause the discharge check should hold. You should be fired. Uour Lucky you don’t work for me because whoever you work for us just as incompetent as you. Your def not a union guy.
@JAMCJOfficial
@JAMCJOfficial 3 жыл бұрын
Keep on sharing bro. God Bless. Very informative instruction for fire pump. Hope I should learn more procedure specially pump controller how to operate for running the pump.
@elijahwilliams6850
@elijahwilliams6850 10 жыл бұрын
This guy knows his stuff!
@bptbrd66
@bptbrd66 7 жыл бұрын
Just to be accurate the pressure relief valve he refers to is actually called a casing relief valve it is operated by water pressure and is used to keep the fire pump cool when it is running at churn. It simply drains a small amount of water from the discharge side of the pump which brings a small amount of cool water from the supply side which keeps the pump cool, while the casing relief valve is operating feel the water it should be a little warm. Overall Good Presentation All the Best
@josephcivile699
@josephcivile699 8 жыл бұрын
Sprinklermatic is a great company
@Spew1210
@Spew1210 6 жыл бұрын
Great Video, this has helped give me a better understanding a pump system, very thorough and detailed, and an excellent pace that makes this easy to follow
@safety_news
@safety_news 2 жыл бұрын
Great job by Robert.Tamilnadu safety council.Secretary
@Sprinklermatic
@Sprinklermatic 2 жыл бұрын
Thank you for your interest and feedback!
@tcvesely
@tcvesely 10 жыл бұрын
Would like a video on color coding of sprinkler heads..This guy is the Bomb...Great work.
@fitter5426
@fitter5426 9 жыл бұрын
Color coding of sprinkler heads is specifically for us(Sprinklerfitters) to identify the degree of the head 155 is red, 200 is green, 286 is blue, etc. There's also fusible link heads as well. It's supposingly a trade secret of what exactly is inside the head itself. The bubble inside is different size pending the degree of the head and also if it's standard response or quick response heads. Hope that helps.
@MundoDaEletrica
@MundoDaEletrica 6 жыл бұрын
Thank you! I'll use this information on our videos!
@RP-nc5ev
@RP-nc5ev 2 жыл бұрын
Great presentation 👏 👌 👍
@Sprinklermatic
@Sprinklermatic 2 жыл бұрын
Thanks for the positive comment!
@mstapell
@mstapell 9 жыл бұрын
Very informative thanks for the effort and the quality
@matthewgregory8218
@matthewgregory8218 7 жыл бұрын
Good instructions on the system how to maintain it as it's not used often unless of a fire.
@fredbarnich8145
@fredbarnich8145 5 жыл бұрын
Video stops at 25:13 and he was still talking, is there a part 2?
@ChuonSophak
@ChuonSophak Жыл бұрын
very clear sir.I am support your video.Thank you.
@Sprinklermatic
@Sprinklermatic Жыл бұрын
Thank you for your comment!
@kgnnetwork8892
@kgnnetwork8892 2 жыл бұрын
Thank you. Alll the best
@chechnya
@chechnya 12 жыл бұрын
Good comment. Fire sprinklers should be mandatory in all structures.
@Matloob303
@Matloob303 8 жыл бұрын
very good brother great and informative video 📹... thnxx
@amandaturner2922
@amandaturner2922 5 жыл бұрын
Thank you for the video! Very informative!
@donsamantissera235
@donsamantissera235 4 жыл бұрын
Thank you for your valuable information,
@cliveramsbotty6077
@cliveramsbotty6077 2 жыл бұрын
very clear and informative, thanks for the effort
@Sprinklermatic
@Sprinklermatic 2 жыл бұрын
Thanks for your interest and feedback.
@МаринМаринов-г7л
@МаринМаринов-г7л 4 жыл бұрын
I, personally, would not route a water pipe into an electrical cabinet. Instead, I would put the pressure sensor outside the cabinet and route it's cable into the cabinet. That looks safer to me in the case when a pipe or a sensor starts leaking.
@electriciandallastx9182
@electriciandallastx9182 8 жыл бұрын
Thanks for the suggestions you have discussed here.
@billmorris6565
@billmorris6565 9 жыл бұрын
good job brother! filmed demos are always fun. lol
@luclapointe6297
@luclapointe6297 3 жыл бұрын
Excellent explanatipn
@FireguyNtx
@FireguyNtx 12 жыл бұрын
Excellent advice. It always scares me to start a pump and let it churn, seems if there's a weak spot, I seem to find it. So you would note on the paperwork that the valve was closed during the test, then reopened and verified at the control panel for proper signal restorals. Have you ever experienced any leaks or problems while running a pump? Also, does the air bleed valve on top of the pump "spit" or "hiss" when running? I find them clogged and rusted all the time. Thanks again for a super job
@MikeBurchett
@MikeBurchett 12 жыл бұрын
Good job man! Nice work!
@markneurohr9663
@markneurohr9663 8 жыл бұрын
Well done. great video!
@willyamaya5908
@willyamaya5908 2 жыл бұрын
Thank you
@markgloverville
@markgloverville 4 жыл бұрын
It's loud but still not as loud as our diesel powered fire pumps at the plant I work at.
@ash1775
@ash1775 3 жыл бұрын
I have one in a small room and I was standing right next to it and it turned on, still can't hear
@franciscoguardado8682
@franciscoguardado8682 4 жыл бұрын
you are the man 👏
@nicoletanis3703
@nicoletanis3703 4 жыл бұрын
Good Job!
@nareshgehlaut
@nareshgehlaut 7 жыл бұрын
This guy is the Bomb...Great work.
@nycflag
@nycflag 7 жыл бұрын
On a tamper switch you will get a Supervisory alarm not a trouble. It is important to know the difference between them both.
@ravikanagasabey285
@ravikanagasabey285 3 жыл бұрын
Correct.
@kylequatier4408
@kylequatier4408 3 жыл бұрын
Supervisory signal. Neither trouble or Supervisory is an alarm
@michelmambueni4289
@michelmambueni4289 3 жыл бұрын
Je trouve cette vidéo très intéressante et instructive.
@Sprinklermatic
@Sprinklermatic 3 жыл бұрын
Merci pour vos commentaires!
@pavel5033
@pavel5033 6 жыл бұрын
Thanks, helped me alot.
@fitter5423
@fitter5423 5 жыл бұрын
Not a bad video. Def a couple things that were wrong. But all in all not bad. No return bend on the air relief on the lid of the pump head. That’s an nfpa 20 code. Copper drain lines in the packing drip cups are just stupid an a headache waiting to happen cause there going to get clogged. He barely touched on the CRV or circulation relief valve on the fire pump. Other than those couple things it wasn’t a bad video. For being non union his knowledge is semi extensive.
@Calling321
@Calling321 12 жыл бұрын
I know not all buildings have this type of machine, or maybe that I have seen. I would imagine there are different setups for different buildings...so what size building is this system in?
@thangarajm3867
@thangarajm3867 6 жыл бұрын
Nice very use full to all how the fire pumps operares
@JayJay-jz3cp
@JayJay-jz3cp 3 жыл бұрын
Tha k u for sharing ur videos
@michelmambueni4289
@michelmambueni4289 3 жыл бұрын
Il serait très intéressant de faire cette vidéo en français pour nous permettre de comprendre le fond de votre démonstration.
@srinathb8682
@srinathb8682 5 жыл бұрын
Thanks for the informative video
@jcneverquits
@jcneverquits 11 жыл бұрын
Awesome video! Thanks!
@josemoya2815
@josemoya2815 7 жыл бұрын
does the JCO or CMS inspectors in verify that these weekly fire pump checks are happening or being conducted? If so, how does this get documented?
@leny8324
@leny8324 4 жыл бұрын
Thanks Dire Straits, very helpful 🙏
@jlmm3968
@jlmm3968 3 жыл бұрын
Does jockey pump power feed need to be on emergency power
@nps2838
@nps2838 2 жыл бұрын
Thanks for the video. When there's a fire though, will the jockey pump be also running? Since Jockey pump turns on first before the fire water pump reaches its switch on pressure I'm thinking it's running but I am not sure though.
@Sprinklermatic
@Sprinklermatic 2 жыл бұрын
Both the fire pump and the jockey start and stop on pressure settings. If the fire pump is able to maintain a pressure above the jockey pump start the jockey pump will shut off. Thanks for your interest!
@preventum
@preventum 9 жыл бұрын
Great video
@Calling321
@Calling321 12 жыл бұрын
Major flooding is right...as those look like some major pipes...and those pipes look like they major bolts connecting them together.
@ajmdez
@ajmdez 11 жыл бұрын
Excellent.Any chance of doing a rated and peak video?
@charleswilson9952
@charleswilson9952 11 жыл бұрын
If the jockey pumps are properly set per the "intent" of NFPA 20, A.14.2.5.1(4), there should not be a problem as this is what the system would be looking at if there were a fire. Keeping the pressure switch settings narrow, reduces the water flowing on start up. If the jockey start PSI is set at the fire pump churn and Stop 10 - 15 PSI above that, there will be no water flowing when you start the fire pump as along as the supply remains the same, the system will be at churn, not 10 -15 less
@fitter5423
@fitter5423 3 жыл бұрын
What in the world are you talking about. Regardless of what the pressure is set at the circulation relief valve needs to open to let the hot water out and allow cooler water in. The two word enemies of an impeller is heat and cavitation. So what you said don’t make one big of sense. I’m an instructor at the union hall and our coordinator is the UA fire pump instructor. Ifso facto he knows a shit ton more than anyone you know. That’s a fact. He’s gone to trainings for every major pump manufacturer and they all said the same exact thing.
@enriquelaroche5370
@enriquelaroche5370 4 жыл бұрын
I set those up with Detroit diesels for backup grid pressure Major government facility.
@clustonlewis1862
@clustonlewis1862 5 жыл бұрын
good day how do one get full training on fire system with sprinklers online training if possible with certificate at the end
@SCROTUMLORD
@SCROTUMLORD Жыл бұрын
i do 13d... i am wondering how hard it would be to learn all this... its alien to me... ???
@michaeldouglas8866
@michaeldouglas8866 9 жыл бұрын
Great video illustration
@jayuski
@jayuski 11 жыл бұрын
I live in NYC and I'm the super of a small building. I want to get my S-12 and S-13 certificates of Fitness from the FDNY. Do you guys make good money? Can one run a bldg as a ceif engineer with al those certificates?
@arnelada6216
@arnelada6216 4 жыл бұрын
Question: 1. What will happen to your jockey once the electric fire pump kicks in its design cut in pressure? Does it operate together with the electric fire pump or will it stop?
@ravikanagasabey285
@ravikanagasabey285 3 жыл бұрын
When the fire pump starts to run automatcally theJocky pump will not run. Both pump will not run together automatically...
@mni_7
@mni_7 2 жыл бұрын
how much pressure does this pump create
@Sprinklermatic
@Sprinklermatic 2 жыл бұрын
This video was produced back in 2011, so we're unsure of the exact size of the pump. Fire pumps are built and sized job specific. Thanks for commenting and subscribing to our channel!
@abedzedan7167
@abedzedan7167 2 жыл бұрын
Does this system have one main pump
@Sprinklermatic
@Sprinklermatic 2 жыл бұрын
This particular installation is just a single fire pump. Multiple fire pump systems will be used in applications such as hi-rise buildings where high pressure is required or in special hazard applications such as aircraft hangar foam systems where a back up pump is needed. Thank you for your interest and for subscribing to our channel!
@whitfieldjoshua8423
@whitfieldjoshua8423 6 ай бұрын
I am a fire technicoan, how fo locate the inspector's test valve in a multi floor building
@Sprinklermatic
@Sprinklermatic 6 ай бұрын
Thank you for subscribing to the Sprinklermatic KZbin Channel. Your question has been forwarded to our service team. Thanks again for your interest!
@MrBonah
@MrBonah 6 жыл бұрын
Does the fire pump always work at max capacity? For example if my pump was 1000 GPM / 10 bars, but only a landing valve was opened which requires ~250 GPM / 4.5 bars. Would the pump work at 1000 GPM / 10 bars and the excess water be thrown out with the Pressure Relief Valve?
@ironmatic1
@ironmatic1 Жыл бұрын
The circulation relief valve only flows enough to keep the pump cool, like 50-100 gpm.
@learnwithshubhra221
@learnwithshubhra221 2 жыл бұрын
Nice👍
@Sprinklermatic
@Sprinklermatic 2 жыл бұрын
Thanks for commenting!
@Txepetxcc
@Txepetxcc 11 жыл бұрын
Hi I've seen you use emergency backup power. I was wondering whether you use a diesel generator or maybe it is bettery pack. Also I've seen in other videos diesel fire pumps, not electric driven pumps. Do you know which system is cheaper? I'd say that an electric pump with an emergency diesel generator would be a little more expensive, but let me know what you know. Thanks!
@garbo8962
@garbo8962 Жыл бұрын
You could never afford the huge # if batteries to provide emergency power for several hours on a 199 HP motor. While at a continuing education class some guy asked the instructor if you could use Solar cells to supply smokers envy power to a fire pump. I struggle told him only if you had guard 24/7 sunshine. In my big city in small to medium buildings that have dual electrical services you do not need an emergency power source .Hospitals & high rise buildings require emergency generator.
@amchac
@amchac 4 жыл бұрын
Very good video. However, the fire pump should be on manual stop and not automatic stop.
@fitter5423
@fitter5423 3 жыл бұрын
If you manually start a fire pump the run timer doesn’t engage. If the run timer is set to any specific time it only engages on an automatic start. For instance when we do 5 year flow testing on prv hose valves we set the time at 1 min to flow the valves with the pump on and when we stop the flow the pump only runs for 1 min and shuts itself off so we don’t have to have someone babysitting the fire pump at all times.
@Irafn1
@Irafn1 11 жыл бұрын
Useful video
@krishnamoorthybaskaran1948
@krishnamoorthybaskaran1948 8 жыл бұрын
EXCELLENT
@ZainalAbidin-po4qq
@ZainalAbidin-po4qq 7 жыл бұрын
krishnamoorthy baskaran
@shakilchowdhury3399
@shakilchowdhury3399 4 жыл бұрын
I am also working fire fighting Qatar NAFFCO
@krishnamoorthybaskaran1948
@krishnamoorthybaskaran1948 7 жыл бұрын
excellent
@aftawabini
@aftawabini 6 жыл бұрын
would the city water reach 300 psi on the pump suction line
@robincollier7976
@robincollier7976 6 жыл бұрын
Ahmad Al-Tawabini no the municipal Supply is much less; here it is more like 60 PSI. The fire department Connection is on the discharge side of the pump; therefore the suction line would not reach any where near 300 PSI.
@aftawabini
@aftawabini 6 жыл бұрын
Thanks Robin, 60 PSI is reasonable. I wondered When I heard 300 psi
@charadremur333
@charadremur333 4 жыл бұрын
@@aftawabini that might be the out side.
@cmarname
@cmarname 5 жыл бұрын
Question: Where is the water going when the pump is running during 10 minutes? I understand that the test header valve is closed, so the water is not escaping there? Is no water flowing?
@engrsubbu25
@engrsubbu25 4 жыл бұрын
There is a Circulation Relief Valve which will make a flow to avoid heating of casing of a Pump.
@firesafe957
@firesafe957 4 жыл бұрын
Hi the water goes through the casing relief valve also this is used in the diesel engine system
@fitter5423
@fitter5423 3 жыл бұрын
When an electric pump starts in churn the casing relief valve is supposed open and flow a full pipe of water to a drain. Once you start to flow water anywhere like for instance doing the performance test the crv should close. And for a diesel when it fire up in churn your should be getting a full pipe of water from the heat exchanger piping to keep the engine and the pump cool. It acts the same as a crv on an electric driven pump.
@jamesbradyjr8067
@jamesbradyjr8067 3 жыл бұрын
I thought it was open stem yoke he said outside stem yoke I'm probably wrong again LOL
@mauriciocastro5080
@mauriciocastro5080 9 жыл бұрын
The camerawork was horrible but the video was very helpful. Thanks
@troysanders7775
@troysanders7775 9 жыл бұрын
Mauricio Castro They tried to get James Cameron to direct the video but he was not available. (^_^)
@Brinestus
@Brinestus 4 жыл бұрын
before i even get a minute into the video, can I comment on the camera skills? They leave MUCH to be desired. in the beginning of the video, when the super stepped off to the left, would have been nice to see what he's pointing at. what he's touching. because I am as green as grass. Just sayin'. other than that, thanks for your time man in making the video.
@retco-.....5476
@retco-.....5476 11 жыл бұрын
thank ....
@loughs321
@loughs321 9 жыл бұрын
wow....the comments and subsequent replies for this video are ridiculous.
@diggsdiggler337
@diggsdiggler337 4 жыл бұрын
HELLO DAN
@PEDERSTEENBERG-nv2id
@PEDERSTEENBERG-nv2id Жыл бұрын
bör vara i varje fastighet världen över
@justinmorton1774
@justinmorton1774 4 ай бұрын
11:02 Book mark
@Sprinklermatic
@Sprinklermatic 4 ай бұрын
Thank you for your feedback and thank you for subscribing to our KZbin Channel!
@justinmorton1774
@justinmorton1774 4 ай бұрын
@@Sprinklermatic I haven’t subscribed though
@asumaef98
@asumaef98 10 жыл бұрын
Bahasane aku ora ngerti
@nadeem.arshadali6267
@nadeem.arshadali6267 8 жыл бұрын
muhammad.nadeem work fair pupe
@mahboobsingh
@mahboobsingh 9 жыл бұрын
many repeats
@garbo8962
@garbo8962 Жыл бұрын
The large hospital/research center/Ambutory care buildings that I retired from had 7 fire Pumps from 75 to 250 HP. I was INE if the electricians who had to run them every week & perform Quarterly PM'S on. Hate how lazy sprinkler guys install angry water pressure gauge sideways. Only takes a minute to install a Nicole & a 90 degree elbow to have them facing straight up making them easier to take readings. How the hell do they get a way with using open motors on all fire pumps instead of the TEFC ( totally enclosed fan cooled ) motors. Have seen every fire pump several times have bad packing then spraying water over open motors and water getting into motors. Hospital fire pumps do not time out after the usual 10 minutes of test run like other buildings. We had a for pump panel like the in your vidio. Had the cheapest piece of shit contactors which you could not remove cover to inspect contacts . We always had to open the drain valve below fire pump water pressure gauge to start pump then record that reading.
@jmcabz48401
@jmcabz48401 6 ай бұрын
Thank you for the Information
@jvmiami714
@jvmiami714 2 жыл бұрын
Awesome video!!
Sprinkler Systems for Firefighters
13:09
Bedford Fire Department
Рет қаралды 144 М.
The Singing Challenge #joker #Harriet Quinn
00:35
佐助与鸣人
Рет қаралды 47 МЛН
Sprinkler Installation Requirements in NFPA 13
1:47:24
Sprinklermatic
Рет қаралды 135 М.
Know More Risk: Wet System -Alarm Check Valve
4:37
FM
Рет қаралды 146 М.
How a fire sprinkler works
7:52
Deconstructed
Рет қаралды 53 М.
Class 10 | Fire Pump Room Layout Design NFPA 20 | Part 1
36:07
Irfan CFPS
Рет қаралды 3,4 М.
Diesel Fire Pump Test
20:19
howImetyourfather
Рет қаралды 28 М.
Weekly diesel fire pump test.
15:20
Joy Cool
Рет қаралды 1,7 М.
Electric Fire Pump Performance Test
11:46
ADLearning Official Channel
Рет қаралды 15 М.
System Reset: Model F Dry Valve - Dry Pipe Fire Sprinkler System
15:05
Viking Sprinkler
Рет қаралды 30 М.
5 year fire sprinkler inspection
20:02
Joy Cool
Рет қаралды 12 М.