How to fix Annoying Squeals in Your MacroAir HVLS Fan
Does your MacroAir HVLS fan emit a high-pitched squeal? Do older people ( 50 and above) not hear it?
Kevin Hoover's experience is that this type of noise is fixable.
He wrote this to help you adjust your MacroAir fan if it has a Yaskawa V1000 variable frequency drive (VFD).
-------------
The squeal comes from the VFD's carrier frequency. The carrier frequency is how often the electricity pulses to the motor. It impacts noise and heat generation.
Fortunately, it's adjustable in most VFDS, especially with the Yaskawa V1000.
Here's how to fix the Yaskawa V1000 MacroAir HVLS fan squeal:
1. Have the VFD powered on, but not running the fan.
2. Press the up button on the VFD until you see "PAR" on the display.
3. Press enter. You'll see a value of "A1-01".
4. Navigate to parameter "C6-02" using the up and enter buttons.
5. Change the right most digit (currently a "4") to a "6" using the up button.
6. Press enter again. The display should now show "06," indicating a 15 kHz carrier frequency.
7. Press enter to save the changes and then escape multiple times to exit the settings menu.
8. Optional) Experiment with values between 6 and 9 to find the quietest setting for your fan.
Understanding the Fix:
Adjusting parameter C6-02 modifies the carrier frequency. A higher frequency creates a truer 3-phase. Consequently, the motor produces less audible noise, but the VFD produces more heat.
We recommend a 15 kHz setting (represented by "06" on the display) to balance noise reduction and efficiency.
MacroAir HVLS Fan Experts:
I have worked with many MacroAir fans over the years. They are good fans. However, there was a need for heavier-duty, direct-drive fans that could withstand crosswinds, which led me to build AmeriWind fans.
If you're experiencing squealing with your MacroAir HVLS fan and have a Yaskawa V1000 VFD, this fix solves the problem.
If you are looking for additional high-quality HVLS fans, give us a call or visit our factory in Oley, PA.
Kevin Hoover, Founder of AmeriWind and AutoVent
610 987 0488
ameriwind.net

Пікірлер
Gearbox seal - HVLS MacroAir® fans - Hub fix and gearbox seal HVLS VFD
3:30
Yaskawa VFD-M "Setup Tutorial"
6:52
plc247 Automation
Рет қаралды 28 М.
Magic? 😨
00:14
Andrey Grechka
Рет қаралды 16 МЛН
If Barbie came to life! 💝
00:37
Meow-some! Reacts
Рет қаралды 72 МЛН
КТО ЛЮБИТ ГРИБЫ?? #shorts
00:24
Паша Осадчий
Рет қаралды 1,4 МЛН
Gli occhiali da sole non mi hanno coperto! 😎
00:13
Senza Limiti
Рет қаралды 18 МЛН
VFD introduction / application / information
18:35
Shadon HKW
Рет қаралды 136 М.
Fan slow to start or won't startup - Easy Fix!
7:53
DIYwithWayne
Рет қаралды 433 М.
Maximizing Livestock Ventilation in the Beam Family's Beef Cattle Barn.
4:31
How to wire up remote/external switches to a VFD
21:30
Cliffs Shed
Рет қаралды 153 М.
Magic? 😨
00:14
Andrey Grechka
Рет қаралды 16 МЛН