Ground Rod Installation Methods

  Рет қаралды 29,203

Electrical Code Coach

Electrical Code Coach

Күн бұрын

We offer the #1 Electrical Exam Prep Program
FREE VERSION
electricalcode...
PRO VERSION
www.electrical...
USB OR DVD PROGRAM FREE SHIPPING!!
electricalcode...
400x Practice Exam PDF Download for only 14.99 electricalcode...
2017 Tabs with FREE SHIPPING
electricalcode...
2020 NEC TABS with FREE Shipping
electricalcode...
2023 NEC TABS with FREE SHIPPING
electricalcode...

Пікірлер: 54
@tray8411
@tray8411 10 ай бұрын
Wish i saw this last week..Burned up a rotor hammer pushing a ground rod thru bedrock...Great vid
@jimbtv
@jimbtv 2 жыл бұрын
You are a lifesaver! I'm in central Tennessee and am hitting ledge at 4 feet. I tried 7 different spots and no joy. Now I know I can excavate a trench and lay my rods horizontal to satisfy code. Thank you!
@luiscolon4961
@luiscolon4961 3 жыл бұрын
I want to thank you for all the information you put out there.I am glad to say I passed my E2 yesterday 🙏🙌🙌thanks to all your content and your energy on wanting to help everyone!!you are the man !!thank you so much!!🙏🙏🙌god bless.
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
That's awesome brother congratulations!!!!!!!
@luiscolon4961
@luiscolon4961 3 жыл бұрын
Hey when do you do your live sessions?I been to two but I’m not sure when you actually do them.
@luiscolon4961
@luiscolon4961 3 жыл бұрын
And thank you 🙏
@seniorcomputer3292
@seniorcomputer3292 3 жыл бұрын
Wonderful information. Thank you for mentioning the 8 feet deep vertical rod.
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
You got it brother! Let's get to it!
@kdogdig
@kdogdig Жыл бұрын
Hey man great video. Right to the point and quick talking! Love it! Other videos talk too slow lol And it’s accurate. I’m a master electrician and these videos are god reference.
@jasonrwilliams2573
@jasonrwilliams2573 Жыл бұрын
Do a video on wiring private fishing dock/ boat lifts. I live in Florida. I'm not finding much info on this on utube. Thanks
@uncledoug9934
@uncledoug9934 2 жыл бұрын
Thank you, thank you, thank you. Nuttin but hard hard shale where I live not too far from the Potomac River. Getting ready to run an underground feeder to my garage. I will definitely run 2 rods in that trench instead of fighting them vertically.
@wildolivetree5089
@wildolivetree5089 Жыл бұрын
Helpful, thank you.
@larrydoss
@larrydoss Жыл бұрын
I came across a "SMOKING" grounding electrode at a house that was connected to the subpanel cabinet in a lug. I know you don't need to install an electrode anywhere other than at the main electrical panel and meter area. What I don't understand is what caused the grounding electrode at the subpanel to spark, pop, and smoke? I simply removed the grounding conductor from the electrode to the lug in the subpanel. When I did that, it immediately stopped smoking. Can you tell me why that happened? i have not, or at least I don't remember, ever seeing that happen in my 42 years of being an Electrician. Thank you for any help to understand what caused that and the theory behind it. Keep up the good work. I love your videos,,,, Let's Get To It!
@ElectricalCodeCoach
@ElectricalCodeCoach Жыл бұрын
Thank you for sharing, It could have been several things, but there's a high probability that the neutral beating that panel was compromised and it was trying to get back to the source through the Earth via the ground rod. They're also could have been a standing fault that was attempting to clear via the ground rod, but there was too much resistance to clear the fault so it was acting as an element.
@lisawing5564
@lisawing5564 2 жыл бұрын
Awesome!
@djnewyork3315
@djnewyork3315 3 жыл бұрын
GOOD STUFF! THANKS.. I just subscribed..
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
Thanks!!!
@bill7949
@bill7949 Жыл бұрын
Does middle Tennessee. Too
@billyedwalltrumpet2632
@billyedwalltrumpet2632 Жыл бұрын
What if I'm hitting bed rock at 15"-24" all over my property? I haven't found a spot that goes past 24" anywhere... Any idea what my options are?
@ElectricalCodeCoach
@ElectricalCodeCoach Жыл бұрын
Definitely work with your local electrical inspector, but you can dig a trench that is 30 in deep or follow any of the other methods lay out there in 250
@davidcooper4385
@davidcooper4385 Жыл бұрын
I believe your ground clamp must be accessible burying it is questionable where is the code section 250 does it say u can bury ground clamps thanks.
@hdtvkeith1604
@hdtvkeith1604 3 жыл бұрын
Nice video, did not know the 2 grounds rods do not have to be directly connected. I had an electrician tell me 2 ground rods were bad. I had driven a second rod years back and disconnected it, I may run new wire back to panel and get it hooked back up.
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
Thank you for the comment brother! If properly installed two ground rods are the correct way
@hdtvkeith1604
@hdtvkeith1604 3 жыл бұрын
​@@ElectricalCodeCoach Thanks, My 2 rods are about 25 feet apart. The original is connected to the plumbing then the panel as 1 direct wire. I was going to connect the other the same way. I also have copper plumbing and made sure I have bonding jumper across the pressure regulator. I assume there is not such thing as too much grounding.
@robertapreston4200
@robertapreston4200 Жыл бұрын
dang!!!!! a twist here and there an life ain't so hard... is it? wowzer🤗🤔😀
@gusgalvanini
@gusgalvanini 2 жыл бұрын
What if I want to install a third ground rod on the other side of my house for a helium miner antenna? Thanks.
@chrisyerp174
@chrisyerp174 7 ай бұрын
What about using sheathed wire and cutting a section out where connecting to the rod does it have to be bare wire
@user-bx7zw2jw2o
@user-bx7zw2jw2o 9 ай бұрын
Inspector is telling me that my gas lines are not grounded,what's the best way to ground them
@ProsperCraft
@ProsperCraft 3 жыл бұрын
Lots of videos on how to install ground rods, but none that say WHERE, does it have to run to the panel, or can a service line from the panel go to the meter and ground there?
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
See if any of these videos answer your questions. If they do not email me electricalcodecoach@gmail.com kzbin.info/aero/PLJokxpBhbuUcyFCKgZTbxx7TQla3Tg3EJ
@Jiminico
@Jiminico 8 ай бұрын
No electrical joint compound on the ground connections??
@JLH0714
@JLH0714 Жыл бұрын
Is there literally nothing talking about how to hammer an 8ft rod into the ground? Are we all assuming the only method is a sledge ?
@chongwang
@chongwang 2 жыл бұрын
if you connect the two rods does it need to be one continuous wire to the panel or can you have two mechanical connections on one rod?
@ElectricalCodeCoach
@ElectricalCodeCoach 2 жыл бұрын
It's going to be an inspector call
@chongwang
@chongwang 2 жыл бұрын
Aww okay. Thanks
@OliveMule
@OliveMule 3 жыл бұрын
Ground rods have to social distance
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
Lmbo that is the funniest thing I've ever heard
@poitka8031
@poitka8031 2 жыл бұрын
hahahaha yeah a jab and booster too!!
@opecons
@opecons 3 жыл бұрын
Hi coach. Can we use insulated grounding electrode conductor? I saw a white wire installed as grounding electrode conductor, is it okay or violation?
@claysmith428
@claysmith428 3 жыл бұрын
What is the best (least expensive) way to test for 25 ohm ?
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
The best would be using a meter, you can buy used ones online. Thanks for the comment!
@anthonyb5291
@anthonyb5291 3 жыл бұрын
Question: When installing a 8ft ground rod horizontally 30inches deep. Do you need to install (2) ground rods 6ft apart? So your trench total would need to be 22ft? Question 2: Say your hitting rock and you don’t have the space to lay a 8ft ground rod or 2. Is there a NEC approved plate you can buy that you can burry in the ground? If so how deep?
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
Great question!! you still will need the second ground rod or other approved supplement. Even with the "plate" electrode they are required to be supplemented!! Thanks!!!!
@codykurtz4144
@codykurtz4144 2 жыл бұрын
They do make ground plates and ground rings and I think they have to be 30” deep as well
@victoryfirst2878
@victoryfirst2878 2 жыл бұрын
Dose the code allow for an all copper grounding rod that is eight feet long instead of a heavy copper plating rod ??? A two hundred amp service needs what size copper wire connection size too ??? Thanks
@ElectricalCodeCoach
@ElectricalCodeCoach 2 жыл бұрын
The ground rod is required to be 8 ft in length It is allowed to be one of the compositions listed in 250 As far as size it depends what type of electrode you are terminating to. And if you're terminating to other electrodes.
@victoryfirst2878
@victoryfirst2878 2 жыл бұрын
@@ElectricalCodeCoach So all copper ground rod will work ???
@victoryfirst2878
@victoryfirst2878 2 жыл бұрын
Thank you for letting me know Sir. Peace VF
@thomasmarable6818
@thomasmarable6818 2 жыл бұрын
@@victoryfirst2878 let me know if you find one please.
@Inkling777
@Inkling777 2 жыл бұрын
Does the ground rod have to be a rod? I've got some #6 copper wire I could strip and bury in a trench. That'd spare me the $20 x 2 cost of copper-plated rods plus the cost of the connectors. There'd also be no risk of corrosion in the connectors.
@michaelsandoval5466
@michaelsandoval5466 2 жыл бұрын
Hello Coach, In a methane zone level 3 where can I set my ground rods? How far from the building? How deep?
@ElectricalCodeCoach
@ElectricalCodeCoach 2 жыл бұрын
Thats a great question for your inspector, Lets get to it!
@ismaeldominguez1649
@ismaeldominguez1649 3 жыл бұрын
Hi bro what size of ground rod can I use for 200A service panel ?
@ElectricalCodeCoach
@ElectricalCodeCoach 3 жыл бұрын
Minimum of an 8-foot ground rod
When NOT to drive a Ground Rod at a Detached Building
4:59
Electrical Code Coach
Рет қаралды 9 М.
Grounding and Bonding an Electrical Panel
13:24
Appalachian DIY
Рет қаралды 313 М.
Секрет фокусника! #shorts
00:15
Роман Magic
Рет қаралды 61 МЛН
WILL IT BURST?
00:31
Natan por Aí
Рет қаралды 40 МЛН
这三姐弟太会藏了!#小丑#天使#路飞#家庭#搞笑
00:24
家庭搞笑日记
Рет қаралды 118 МЛН
The Easiest Way To Drive Grounding Rods
6:45
Practical Home Projects
Рет қаралды 182 М.
Grounding and Bonding
8:01
schulerruler
Рет қаралды 669 М.
Ground Rod Resistance
2:47
Northwest Lineman College's Lineman Channel
Рет қаралды 154 М.
Fastest And Easiest Way To Drive Grounding Rods
4:52
Everyday Home Repairs
Рет қаралды 65 М.
Ground Rods at Detached Garages and Out Buildings??When  you dont. Part 1
5:07
Electrical Code Coach
Рет қаралды 15 М.
Do We Need Separate Ground Rods for Each Sub Panel?
4:02
Electrician U
Рет қаралды 78 М.
Why do we drive Ground Rods at Detached Garages?
5:07
Electrical Code Coach
Рет қаралды 34 М.
Секрет фокусника! #shorts
00:15
Роман Magic
Рет қаралды 61 МЛН