Grounding and bonding: Definitions and details

  Рет қаралды 82,681

Eaton

Eaton

2 жыл бұрын

Part 2: Grounding and bonding: Definitions and details Two professional engineers (Dan Carnovale and Tom Domitrovich) with years of power systems experience will clarify this often misunderstood concept while making reference to NEC.
To learn more about grounding and bonding you can find the full video here: • Grounding and bonding
Thank you for watching one of our many educational videos on the topic of power systems. Schedule a visit to one of Eaton's Power Systems Experience Centers in either Pittsburgh or Houston to learn more!
To learn more about Eaton products and our Power Systems Experience Centers: eaton.com/experience
To view more educational videos from Eaton's Power Systems Experience Centers: videos.eaton.com/experience
------------------------------------------------------------------------------------------------------------------------------------------------
Search terms: grounding, bonding, grounding and bonding, grounding vs bonding, generator grounding, transformer grounding, service entrance ground, service entrance grounding, service equipment ground, grounding electrode, grounding conductor, bonding strap, equipment ground, transfer switch ground, ground rod, grounding rod, switch the neutral, neutral switching in transfer switch, four pole transfer switch, 4 pole transfer switch, return current, safety, surge protection, power quality, circulating currents, ground loops, isolated grounds, single point grounding, electrical noise on a power system, utility source ground, building steel, incoming ground, outgoing ground, residential service grounding, grounded neutral conductor, ungrounded conductor, main bonding jumper, transformer grounding configurations, bird on a wire, ground fault current path, electrical shock hazard, touch potential, step potential, grounding grids, grounded to case | What is a ground? What is a bond? How to ground a generator? What is a grounded wire? What is a grounding wire? What is a separately derived system? How to ground a transformer? What is NEC grounding method? Is grounding required by NEC? Do I need a 4 pole transfer switch? What is a high resistance ground? What is an HRG? What does solidly grounded mean? What is the difference between grounding and bonding? #electric #electricity #powersystem #electrical #energy #solar #wind #power

Пікірлер: 72
@Katiebelly123
@Katiebelly123 5 ай бұрын
Wow, this is dense material, but clear. I'd like to take an entire semester of lectures from these engineers. Thanks!
@chriswuzhere91
@chriswuzhere91 Жыл бұрын
I'm going to have to watch this about 50 more times to really understand it LOL
@tedlahm5740
@tedlahm5740 Жыл бұрын
Too much information covered in one video. Needs to be broken down to numerous videos.
@petakyahbuckley6403
@petakyahbuckley6403 Жыл бұрын
Keep up newb
@erilopez7974
@erilopez7974 Жыл бұрын
same here, too much talking less graphics from him.
@G8tr1522
@G8tr1522 Жыл бұрын
it's crucial to understand why you only use ONE main bonding jumper in a system. If you don't understand the implications of why that is, this whole video will probably be confusing. you provide a second main boning jumper ONLY when you have a switched neutral (in your ATS). If it is not a switched neutral, you only have ONE main bonding jumper. If you erroneously add a second main bonding jumper, you would effectively make your equipment grounding conductor the same as your neutral. Meaning that touching an equipment's (conductive) surface could shock you. For example, touching the outside of a metal toaster is usually safe, but in this case, you would become part of the neutral path if you touched the outside. (cue "Dumb ways to die") The reason that happens is because the EGC and entire grounding system is in parallel with the neutral as soon as you add that second MBJ. Thus, the neutral can now 'share' the load's current with the grounding system. Hope this helps.
@IWasNoah
@IWasNoah 9 ай бұрын
@@G8tr1522I thought you should never have a switched neutral though it’s too dangerous
@nhicks8028
@nhicks8028 8 ай бұрын
Thank you for this video . It is the very first time that I have seen anyone explain about bonding a back up generator . I have searched many of times to no avail. I don’t see mention of it in the Generac installation manual either.
@enriquerodriguez2451
@enriquerodriguez2451 2 жыл бұрын
Very useful information thanks
@Spectre.007
@Spectre.007 4 ай бұрын
Very well delivered material. Thanks.
@Robert-3691
@Robert-3691 4 ай бұрын
This is outstanding material. I recently enjoyed a similar book, and it was truly impressive. "The Art of Meaningful Relationships in the 21st Century" by Leo Flint
@MrMaxyield
@MrMaxyield 10 ай бұрын
Great job Tom...!!! 👏
@adelcamac8681
@adelcamac8681 9 ай бұрын
This is Beautiful! Thanks 👍
@tomrandall4871
@tomrandall4871 2 ай бұрын
Excellent refresher for us old salts!
@maxujess25
@maxujess25 8 ай бұрын
This is an awesome video
@MissionFitnessCTC
@MissionFitnessCTC 6 ай бұрын
Great video.
@jonacholo8908
@jonacholo8908 Жыл бұрын
Great Video. Maybe you can add next time an example at fault condition why the code probihit something it would be a perfect explanation😊
@anthonypicozzi7360
@anthonypicozzi7360 2 жыл бұрын
Really good video
@TGUlricksen
@TGUlricksen 10 ай бұрын
Excellent!
@davem5392
@davem5392 Жыл бұрын
great video I think very to the point instructions! Wondering if you can help me with a separately derived system question, I'm struggling with. 480v pad mount transformer 3 wires and ground ran to plant disconnect Plant disconnect to busway 3 conductors and case grounding to MCC MCC breaker 2 wire plus gnd wire feeds transformer primary 480v secondary single phase 240/120 panel. Question? is the ground wire from the MCC the only wire needed to ground this separately derived system or do you need some other electrode at transformer?
@erikolsen3611
@erikolsen3611 2 жыл бұрын
Great video, thank you so much. I think one point worth adding in regards to the EGC within a system. If my understanding is correct, it is connected to metal parts and enclosures that have potential to become energized in order to "trip" the over current protection device in the case of a fault.
@G8tr1522
@G8tr1522 Жыл бұрын
he covered that when he discussed equipment bonding jumpers. And yes, exteriors of equipment must have equipment bonding jumpers if the equipment is powered by a grounded system. Question: do you remove equipment bonding jumpers if the equipment has no neutral (eg, a motor), and the equipment is powered by a non-grounded system??
@jswallow4168
@jswallow4168 5 ай бұрын
@@G8tr1522not sure but I’d enjoy you elaborating on an answer
@mohammad45h
@mohammad45h 2 жыл бұрын
سلام سپاس تشکر درود و..هزاران 👍...جناب مهندس باشکوه ممنون همواره تندرست و شاد باشین
@agliettoingenieria
@agliettoingenieria 2 жыл бұрын
Excelent!!!!
@ondadevapor
@ondadevapor 2 ай бұрын
i feel like Neo when he learns kung fu for a few seconds
@Deathproof-Zero1
@Deathproof-Zero1 7 ай бұрын
Wait a second. At 6:23, what is the purpose of putting a transfer switch for the neutral between the service and the generator if they are also both directly connected to the grounding system?
@gravecrawlerr
@gravecrawlerr 11 ай бұрын
3:03 I'm trying to qualify to be a home inspector. We typically only work with single phase electricity. Are you saying that you only see the ungrounded conductors in three phase? I'm confused
@swriley444
@swriley444 Жыл бұрын
Question: do you have to run a neutral cable from the transformer to the first disconnecting component even if you don’t plan on using single phase loads? Could you just ground X0 (neutral) at the transformer and just run the 3 ungrounded cables to service?
@G8tr1522
@G8tr1522 Жыл бұрын
that's a really good question
@jonacholo8908
@jonacholo8908 Жыл бұрын
I think you need the neutral or grounded conductor for protection purposes. Example is the equipment grounding. We know that current will find a way to back to its source. If you have faults like ungrounded conductor to your equipment enclosure, it will be back to source means it will circulate the your protection will trip
@regorksr.6892
@regorksr.6892 9 ай бұрын
Wouldn’t be ideal, i would run the neutral *conductor* if i had it even though i didnt need it. They make delta-delta transformers for this reason.
@jonerasmus9399
@jonerasmus9399 Жыл бұрын
Awesome video. So let's say I have an inverter (solar system) connected on the opposite side of the transfer switch similar to your diagram (just without a generator) . Is it recommended that I rather choose a 4 pole transfer switch instead of a 3 pole transfer switch? Secondly if my main incoming supply originally has n and earth bonded as your example above do I need to bond earth and neutral in my generator/ or inverter ?
@G8tr1522
@G8tr1522 Жыл бұрын
you provide the second main boning jumper ONLY when you have a switched neutral (in your ATS). If it is not a switched neutral, you only have ONE main bonding jumper. For example, if the TS/ATS had no switched neutral, and you erroneously added a second main bonding jumper, you would effectively make your equipment grounding conductor the same as your neutral. Meaning that touching an equipment's (conductive) surface could shock you. For example, touching the outside of a metal toaster is usually safe, but in this case, you would become part of the neutral path if you touched the outside. (cue "Dumb ways to die") To answer your first question, a switched neutral is sort of more advantageous, because your ground fault current path will be shorter when using the secondary power source. This is especially true for large facilities like hospitals and warehouses, but for small structures like a house or a medium sized commercial building (like a restaurant), there isn't much of an advantage. Put simply, if you're putting your solar system on a house, i wouldn't worry about spending the extra money on a TS that has a means to switch neutrals.
@jonerasmus9399
@jonerasmus9399 Жыл бұрын
@i need more sleep I'm humbled by your superior knowledge . Thank you for the time to explain topics not covered in enough depth at college level .
@G8tr1522
@G8tr1522 Жыл бұрын
@@jonerasmus9399 lol, damn, I'm just in an apprenticeship program. About to take my j-man's tho. Helps that i was an EE dropout too. glad i could help!
@altuber99_athlete
@altuber99_athlete 2 жыл бұрын
6:53 Is it valid to keep the ground rod (grounding electrode) at the generator connected to the other ground wires?
@G8tr1522
@G8tr1522 Жыл бұрын
yes, you should always bond together the entire ground system. If you didnt, and if your generator had a ground fault, it could potentially find a current path through the rest of your grounding system thus creating a hazard.
@Gallardo6669
@Gallardo6669 9 ай бұрын
Not enough explained why, what happened. No example with functional consequences
@mrnade333
@mrnade333 2 жыл бұрын
WOW! Thanks! Can we change grounding to earthing!?
@altuber99_athlete
@altuber99_athlete 2 жыл бұрын
The term “ground” is used in the US, the term “earth” is used in the UK.
@eds6569
@eds6569 Жыл бұрын
I think (in the US) it would make things less confusing if "Earth" were used at least when referring to something which has direct contact with the earth.
@G8tr1522
@G8tr1522 Жыл бұрын
At the very least, the NEC is FINALLY calling the "grounded conductor" a neutral.
@D.Hozzie
@D.Hozzie Жыл бұрын
Hello Tom….. So if I am setting a panel right next to a 13,200-480V transformer, the XO is tied in with all the grounding conductors…..is the panel N and G “ bonded” there too?
@G8tr1522
@G8tr1522 Жыл бұрын
NO. you should remove the bonding jumper in either the panel or the transformer, whichever you prefer. You should always have ONE main bonding jumper. the only instance you will EVER have two of them is if you have an ATS/TS with a switched neutral.
@D.Hozzie
@D.Hozzie Жыл бұрын
@@G8tr1522 Thank you. Now go get some sleep😉
@jahboy699
@jahboy699 Жыл бұрын
nice
@abdullahalahmadi695
@abdullahalahmadi695 Жыл бұрын
If ground and neutral are bonded at main panel, why aren't all grounded device chassis energized?
@G8tr1522
@G8tr1522 Жыл бұрын
because you only did it in one place. If you failed to provide a MBJ, then there will be no possible way to clear a ground fault with a breaker. Because there is no path back to the source. What you are describing in your question will happen if you erroneously install TWO main bonding jumpers.
@jonacholo8908
@jonacholo8908 Жыл бұрын
Always remember that ECG should not carry a current at normal condition and should only at fault condition.
@WindsurferHD
@WindsurferHD 2 ай бұрын
The drawing at 7:43 is wrong. You bond both the GEC and neutral X/O at the transformer and you install the line side bonding jumper there. When you leave that transformer you keep the neutral and equipment grounds separate in the panel it feeds. You can bond the equipment frame to the equipment ground and your neutral is always placed on isolators at all points from that panel the transformer feeds all the way to the utilization equipment.
@Nahum17good
@Nahum17good 4 ай бұрын
How can I get a shirt like that?
@DoughboyGod
@DoughboyGod Ай бұрын
💯💯💯💯💯💯💯
@tazmania17171717
@tazmania17171717 Жыл бұрын
At 3:23 wouldn't that be a supply-side bonding jumper and NOT an equipment grounding conductor?
@regorksr.6892
@regorksr.6892 9 ай бұрын
Yes, this video is kinda disappointing. Funny how eaton employees do not understand an electrical system basics.
@JoJo-gy9sw
@JoJo-gy9sw 2 ай бұрын
I'm more confused now than before I saw this video.
@mirandapowers5594
@mirandapowers5594 2 ай бұрын
😂😂😂
@Mr.GuGuGaCucaSnooch
@Mr.GuGuGaCucaSnooch 26 күн бұрын
Literally just a video of a guy reading from a dictionary. No context or clear examples aside from a schematic.
@G8tr1522
@G8tr1522 Жыл бұрын
kinda upsetting to see how many amateurs in the comments don't understand grounding. I can understand why. It's not an intuitive concept when you are taught that electricity is analogous to water flowing through a pipe.
@jonacholo8908
@jonacholo8908 Жыл бұрын
Because water wipe has no protection. Main purpose is to supply water by on and off
@tommymairo8964
@tommymairo8964 4 ай бұрын
While, why you need to ground the secondary winding at the beginning? Most modern residential electrical transformer are wrapped in ground metal cases, and the wires associated with the secondary winding travels underground to the residential building. So the whole electric system linked to the secondary winding is in a huge faraday cage where the lightning is impossible to strike on. So if the system is ungrounded at all, it's almost impossible to electric shock someone unless he touches hot and neutral concurrently. Won't it be more safer comparing to getting shocked by simply touching the hot wire?
@LesterBarrett
@LesterBarrett 11 ай бұрын
This video is barely ok if one already understands pretty much everything about grounding.
@regorksr.6892
@regorksr.6892 9 ай бұрын
I wouldn’t even say its that ok. Could be very misleading to those learning.
@user-wo7gx6nb5f
@user-wo7gx6nb5f 9 күн бұрын
trump usa
@chathurangalakshitha7777
@chathurangalakshitha7777 4 ай бұрын
Plz dont use a book to explain. We come here just bcz after done enough with the book definitions
@wm79198
@wm79198 2 жыл бұрын
Just here to see if you can help track my order, SAT1225245. I placed it last October, and it has been delayed 4 times. No one at your factory will give me or my Rexel rep a real answer as to the validity of the ship date. Any help would be appreciated. Thanks
@G8tr1522
@G8tr1522 Жыл бұрын
lol, jesus, good luck.
Grounding and bonding
29:15
Eaton
Рет қаралды 35 М.
What is Ground? Earth Ground/Earthing
9:27
RimstarOrg
Рет қаралды 3,2 МЛН
Luck Decides My Future Again 🍀🍀🍀 #katebrush #shorts
00:19
Kate Brush
Рет қаралды 8 МЛН
🌊Насколько Глубокий Океан ? #shorts
00:42
Survival skills: A great idea with duct tape #survival #lifehacks #camping
00:27
Grounding, System and Equipment [250.4, 2020 NEC]
33:35
MikeHoltNEC
Рет қаралды 100 М.
Difference between grounding, earthing and bonding with examples
5:39
The Engineering Power
Рет қаралды 11 М.
Why Do We Bond at the Service Panel and Not a Subpanel?
19:46
Electrician U
Рет қаралды 1,1 МЛН
Why Neutrals & Grounds are Connected in a Main Panel
20:13
Benjamin Sahlstrom
Рет қаралды 1,5 МЛН
Table 250.66 How to Size GEC's Grounding Electrode Conductors
14:57
Electrical Code Coach
Рет қаралды 7 М.
What is Electrical Bonding? Bonding VS Earthing!⚡
6:05
Axis Electricals
Рет қаралды 14 М.
The Most Confusing Part of the Power Grid
22:07
Practical Engineering
Рет қаралды 1,1 МЛН
Where Does Grounded Electricity Actually Go?
19:36
Practical Engineering
Рет қаралды 5 МЛН
Electrical Grounding Explained | Basic Concepts
6:45
RealPars
Рет қаралды 907 М.
YOTAPHONE 2 - СПУСТЯ 10 ЛЕТ
15:13
ЗЕ МАККЕРС
Рет қаралды 120 М.