Hello! With PUT, Data Blocks can be optimized ?
@hegamurl7434
@hegamurl7434 5 жыл бұрын
Generally said: Yes! But the topic is a bit more complicated... when using "optimized block access" you can not used on an "address based" way anymore, so you have to use the symbolic names or drag and drop (like I did in the video with the data that the first PLC sends). You can PUT a whole DB, simply by dragging it and dropping it at the "SD_1" input. ...but as said... the topic of optimized block access is quite complex, maybe I'll make a video on it in the future.
@sashkindg
@sashkindg 5 жыл бұрын
@@hegamurl7434 I think the topic of optimized block access will be very useful.
@MAli-zh6cr
@MAli-zh6cr 4 жыл бұрын
@@hegamurl7434 In case of whole db with different data types needs to be sent, should I make another db on the other side (plc) with same data types/lengths as well?
@bacem_ch
@bacem_ch 3 жыл бұрын
@@MAli-zh6cr yes
@austins.275
@austins.275 2 жыл бұрын
Man I ran out of inputs on a big project and thought "PLC to PLC communication should be easy" 72 hours of pulling my hair and you saved me. Had EVERYTHING right but couldn't get the REQ parameter to work and your video explained it perfects. Thank you!
@hegamurl7434
@hegamurl7434 2 жыл бұрын
Happy to hear it worked in the end!
@pksharma9329
@pksharma9329 4 жыл бұрын
Sir your video always helpful for me....greetings from INDIA as well
@NikPB
@NikPB Жыл бұрын
Thank you very much for so easy explanation of the complicated things!
@framos9991
@framos9991 Жыл бұрын
My favorite teacher /Thank you!
@76POK
@76POK 2 жыл бұрын
Thanks again. I have got so much help from this site!
@crja4114
@crja4114 Жыл бұрын
My good friend you have a new subscriber. Thanks.
@zedjag7701
@zedjag7701 4 жыл бұрын
Another great TIA Portal video, thanks a lot.
@santiagomoore374
@santiagomoore374 3 жыл бұрын
Sir, I have confusion over profibus, profinet, ethernet?? Please make a video on this topic. At 0:32 we found two ip address 1) is 192.168.1.1 2) 192.168.0.101 What is those two ip?? Please explain or suggest any video
@seanyushi9096
@seanyushi9096 2 жыл бұрын
The connection id is actually not taken care by TIA. I've tried to have more than 1 PUT instructions and all of the block will always have the identical configuration following the latest changes i made, e.g. ip address of partner, memory address, etc. And this might be my issue, i need to change the connection name.
@sagarparmar8904
@sagarparmar8904 3 жыл бұрын
Sir , your videos are very helpful thanks 🙏
@petervranks2723
@petervranks2723 9 ай бұрын
Hello , video is well explained as ever, but still a question : do'n I need to define the S7-connections in the network view are they generated automatically ? What is the SIMATI-ACC option ? Best allways on for easy configuration with unspecified partner ( in my case S7_1500 GET from S7-1200 ?
@KIMZ47112
@KIMZ47112 3 ай бұрын
Great Video
@mohdshahzad9427
@mohdshahzad9427 2 жыл бұрын
How to convert 1 Word into bits via siemens S7 1200 PLC?
@szolek8472
@szolek8472 3 ай бұрын
Hello, Is there any limitations? how many s71200 I can connect by s7 communication?
@dennisrubio2375
@dennisrubio2375 Жыл бұрын
why does not PLC 102 isnt on profinet red plz help sr
@melvingomez426
@melvingomez426 4 жыл бұрын
How do you send multiple data..🙏🏽
@محمدالسروري-ه4ه
@محمدالسروري-ه4ه Жыл бұрын
I need to get encoder value from another cpu can I use the GET bock and how???
@hichemchawi4498
@hichemchawi4498 5 жыл бұрын
thanks for your videos, those are very useful to learn about automation
@hansbrannstrom620
@hansbrannstrom620 3 жыл бұрын
Hi Thanks a lot for all nice videos you share with us :-) Is it even possible to test this PUT & GET function with PLC SIM? I does not get it to work....
@Reaper0931
@Reaper0931 Жыл бұрын
Hey, How can I send more information ? Im a beginner and you say in the end of the video that it is possible, how ?
@mat77111
@mat77111 2 жыл бұрын
I take it this method doesn’t work with S7-1200 PLCs?
@EshmesVid
@EshmesVid 10 ай бұрын
Uhh it also works on Logo not only S7
@ikkusoft
@ikkusoft 3 жыл бұрын
Can this be simulated in PLC SIM, I tried, I'm not getting value in other PLC.
@whatacode
@whatacode 3 жыл бұрын
How Can we send use put for more than 5 plc and send data to one Common plc..... Please respond sir
@kreditslavkov8115
@kreditslavkov8115 3 жыл бұрын
Hello, pleace can i have a guestion.... i used a condition as you did at the end of the video for the REQ input. i also put a negativ contact "PUT_DB".DONE instead of freguency. but when i did it for the first time nothing has came into the my next plc. when i deleted it and did it again and upload the plc program again, it works. But when i was working on that again today also same problem and i have to do the same solution. deleted that condition and do it again the same. unfortunetly i cannot used the frueqvency condition, do you know why this negativ contact "PUT_DB".DONE doesnt work for the first time(the datablock put_db is green, but nothing has came into the database on the next plc...)? and is there any solution idea for condition like do it with every cycle of the cpu?
@vijayakanthm705
@vijayakanthm705 4 жыл бұрын
Thanks to your good work.I have a question That i didn’t have a physical plc ,so shall configure two plc’s in a single project and test them with each other by single PLCSIM.Don’t bother if it is a genuine question
@tuleanhvt
@tuleanhvt 4 жыл бұрын
you can simulate two PLC by PLC SIM
@MrPushpalm
@MrPushpalm 3 жыл бұрын
Will s71200 communicate with s71500
@ansonkiek6471
@ansonkiek6471 4 жыл бұрын
If we set unspecified is this must delete the s7 connection ? My partner plc is s400 , I tried use this function communicate but always failed.
@khaledtebai3920
@khaledtebai3920 5 жыл бұрын
This video came just in time! thank you so much! I have a school project, in wich I have to communicate three S7-1200. for now, connecting two PLC's is quit clear, with three , do I just need to add PUT and GET functions in the three of the PLC's if i want to send and read data from all three of them?
@hegamurl7434
@hegamurl7434 5 жыл бұрын
Yes exactly! Junse repeat for the third PLC
@genantamtam9364
@genantamtam9364 4 жыл бұрын
@@hegamurl7434 so putGet is only for siemens s7 communication? What if i want ro connect to other systems with my siemens plc? You have a video on that?
@braincrackz
@braincrackz 5 жыл бұрын
hello there greetings from saudi arabia. god bless you
@stuatkins5
@stuatkins5 3 жыл бұрын
hi great video , if i wanted to send a qr code value (say PAC123) from one plc to another is a put instruction the best way?
@ouluberlu7373
@ouluberlu7373 2 жыл бұрын
Hi, I'have got a 1214CPU and using TIA V15. Unfortunatley, S7-communication library is missing. Do you know if I can import it in TIA? If yes, where can I get this library? Or is it a default library? Thanks for your videos !
@rhysdavies8947
@rhysdavies8947 4 жыл бұрын
Awesome video. Thanks!
@danielesauhs5083
@danielesauhs5083 3 жыл бұрын
Hey man! I really like your videos, your explanations are excepcional, thanks for this knowlegment. Just a quick question, I have 2 PLC 1500, both have diferent subred, but one of them have two ethernet ports available, is it possible to link each other trought this free port?
@Gumballation
@Gumballation Жыл бұрын
Hi sir! Your tutorial is amazing ❤. I have a question: is it possible to take text input from a human-machine interface and then process it using if/else statements like in programming? For example, the user types "password" and if the password is wrong, you know, like an if/else statement in programming.
@Der_Geraet1
@Der_Geraet1 4 жыл бұрын
Kann man damit auch bspw. M0.0 der einen sps setzt M0.0 der zweiten sps? Sprich kann man einfach nur merker 1 und 0 setzten damit?
@deshabandhunayak320
@deshabandhunayak320 5 жыл бұрын
What is the maximum size of data we can send in PUT command?
@mobros1298
@mobros1298 Жыл бұрын
so clear thank you
@ericanderson560
@ericanderson560 Жыл бұрын
Do you have to be online for this to work? I can't get it to work at all. It tells me the data type is wrong when it is clearly correct, or it tells me the specified value is invalid
@ericanderson560
@ericanderson560 Жыл бұрын
It says "The data type DInt of the actual parameter does not match the data type Remote of the formal parameter". In this case I dropped it in directly from the tag table of the receiving PLC, which is in my project. They are both Dints
@OnceAgain0704
@OnceAgain0704 Жыл бұрын
மிகவும் நன்றி நண்பா
@vinothparker7425
@vinothparker7425 5 жыл бұрын
Kindly make a video on various communication protocols and what is the difference between each of them sir..
@hegamurl7434
@hegamurl7434 5 жыл бұрын
Will do at some point!
@genantamtam9364
@genantamtam9364 3 жыл бұрын
@@hegamurl7434 hi there. You mentioned 14:46 that put/get is not your recommended type of communication but you mentioned "ip protocol"? Which one is that? Isit i-device/control? IO communication by pnpn coupler? Is that the most common?
@alvaropalenciano6147
@alvaropalenciano6147 4 жыл бұрын
Master!
@hegamurl7434
@hegamurl7434 4 жыл бұрын
Give yourself some years and experience and you will be the master!
@NotMarkKnopfler
@NotMarkKnopfler 4 жыл бұрын
Is this command also available over Profibus (rather than Profinet)? Thanks :-)
@ericanderson560
@ericanderson560 2 жыл бұрын
DO you have to set up a TCON to do a put? If not what's the purpose of setting up the TCON in the prior video?
@hegamurl7434
@hegamurl7434 2 жыл бұрын
No you dont have to, they are different merhods of communication. The videos are unrelated
@naifsahin
@naifsahin 2 жыл бұрын
Very useful, thanks.
@HectorRodriguez-si3yr
@HectorRodriguez-si3yr 3 жыл бұрын
i love u man, thanks a lot.
@armchairfreedomfighter
@armchairfreedomfighter 5 жыл бұрын
Keep'em coming!!
@legendary686
@legendary686 4 жыл бұрын
Thanks for the video. I have a question. Can you do this with PLCs from different brands? i.e Sending data from my siemens PLC to an omron in a different project for example?
@RemixProf
@RemixProf 3 жыл бұрын
NOPE. Siemens S7 only.
@Raul-jl1nd
@Raul-jl1nd Жыл бұрын
thanks, grate job
@Olavotemrazaodenovo
@Olavotemrazaodenovo 5 жыл бұрын
Where can I find the frame structure of a command between IHM and PLC by profinet? If I want to snif the protocol to discover how the adress of the word in PLC is coneccted with other adress word in IHM, how can I do it? Congratulations from Brazil. Thank you.
@hegamurl7434
@hegamurl7434 5 жыл бұрын
Don't know what exactly you are looking for... but for analyzing network packages I recommend a free tool called "Wireshark" with which you can analyze network packages
@ziborgbe
@ziborgbe 5 жыл бұрын
search for s7 protocol
@Olavotemrazaodenovo
@Olavotemrazaodenovo 5 жыл бұрын
@@hegamurl7434 I want to analyze it. Thank you for wireshark!
@kadadjamel4545
@kadadjamel4545 2 жыл бұрын
MERCI beaucoup
@GeneralKiller1337
@GeneralKiller1337 4 жыл бұрын
Nice job, Hega! I have one question: can I use this protocol with SINAMICS devices or the S7 protocol is only for the comunication between 2 S7 PLCs?
@mubarishussain3696
@mubarishussain3696 5 жыл бұрын
So you only put instruction to communicate.What about get instruction on receiving PLC.Is not required?
@hegamurl7434
@hegamurl7434 5 жыл бұрын
You only have the instruction on one PLC: If you want to read data from another PLC you use "GET" and if you want to push data into the other PLC you use "PUT". The other PLC does not need any function (although some prerequesites as described in the video)
@alexchiosso221
@alexchiosso221 5 жыл бұрын
Thank you so much!!!
@umairshah9735
@umairshah9735 4 жыл бұрын
Hi dear , Watching your vids . Best one can offer for the betterment of human beings . Thanks alot . Dear i want to send my Level signal from one PLC to other . I am no expert . Kindly, advice me videos in your playlist which can help me . Thanks
@santoshkumarpatro2772
@santoshkumarpatro2772 5 жыл бұрын
Thanks for this video..its helped me
@simonmax3901
@simonmax3901 5 жыл бұрын
That was so informative
@IK-qu9hw
@IK-qu9hw 5 жыл бұрын
Thank you sir.
@mehmettevfikcete3397
@mehmettevfikcete3397 5 жыл бұрын
Hegamurl hi, Is there a limit on this process. I mean, can i send for example 200 byte datas with 300 ms rate ? And could you share a lesson about putting or getting data from different brand plc's to siemens plc please.(not s7 connection) Thank u so much again. God sent you to us. :)
@mehmettevfikcete3397
@mehmettevfikcete3397 5 жыл бұрын
Note: our network bandwith is very nice. There is no bottleneck on this topic.
@hegamurl7434
@hegamurl7434 5 жыл бұрын
Very good question! I have never tested the maximum, but also have never reached it. I'll simply test it out (and also read the documentation) on it, when I have the time. As far as I know the PUT/GET here is only between SIMATIC components. For other devices I always recommend a TCP connection (my next videos will be about that)
@lassejespersen9880
@lassejespersen9880 4 жыл бұрын
With the 1500 system you Can PUT 400 bytes and GET 400 bytes
@akshayjadhav6145
@akshayjadhav6145 4 жыл бұрын
Hello, thanks for such great videos. Could you have a video on Ethernet diagnostics to find communication error in your network and display on HMI. That would be very helpful And thank once again
@saeed2tube
@saeed2tube 5 жыл бұрын
Hi I have question maybe irrelative. How we can mirror hmi to monitor without pc and use finger touch of monitor? And if you can please make video about data logging server. thankful
@hegamurl7434
@hegamurl7434 5 жыл бұрын
Hi! I am not sure if I fully understand your question, but if you want to use your PC as HMI you will need WinCC Professional Runtime on your PC, which will simply run a program that emulates an HMI on your PC. Added Data Logging to my list!
@saeed2tube
@saeed2tube 5 жыл бұрын
Thank for your answer. But i want connect monitor directly to hmi.
@GeorgeMan_1981
@GeorgeMan_1981 5 жыл бұрын
Use sm@rt client ..
@vishalpatil6740
@vishalpatil6740 5 жыл бұрын
Thanks bro.... 👍
@kanishgakathiravan3574
@kanishgakathiravan3574 4 жыл бұрын
Thanks
@dee-hl2tp
@dee-hl2tp 4 жыл бұрын
Hi, another great video thank you. Just one question, In the PU_DB ADDR_1 parameter, (P#M0.0 INT 1) is M0.0 not just 1 BIT? If so how can you store an INT value in it?
@beautyofislam323
@beautyofislam323 4 жыл бұрын
Thanks sir
@jamesedrielleaurellana
@jamesedrielleaurellana Жыл бұрын
😍😍😍
@mrloh7197
@mrloh7197 Жыл бұрын
Is it possible to use Put and Get instruction with the CPUs with different TIA Portal Version? One using V15.1 and another using V16.0.
@GeorgeMan_1981
@GeorgeMan_1981 5 жыл бұрын
Just subscribe ..
@zhengkunyan8001
@zhengkunyan8001 4 жыл бұрын
Good
@BG-gr1uu
@BG-gr1uu 2 жыл бұрын
Please improve voice quality,
@Automation28
@Automation28 3 жыл бұрын
thanks for your videos, those are very useful to learn about automation
TIA Portal: GET Command / PLC-PLC Communication
11:49
Hegamurl
Рет қаралды 45 М.
1% vs 100% #beatbox #tiktok
01:10
BeatboxJCOP
Рет қаралды 67 МЛН
小丑女COCO的审判。#天使 #小丑 #超人不会飞
00:53
超人不会飞
Рет қаралды 16 МЛН
Cat mode and a glass of water #family #humor #fun
00:22
Kotiki_Z
Рет қаралды 42 МЛН
TIA Portal: IO-Devices / PLC-PLC Communication
15:47
Hegamurl
Рет қаралды 116 М.
PUT GET Function S7 1200
13:05
PHUK HOANG
Рет қаралды 16 М.
TIA Portal: Functions (and how to reuse them)
21:32
Hegamurl
Рет қаралды 85 М.
GET-PUT Communication: S7-1200 - S7-300/400
10:40
Igor Alterman
Рет қаралды 40 М.
1% vs 100% #beatbox #tiktok
01:10
BeatboxJCOP
Рет қаралды 67 МЛН