Generally said: Yes! But the topic is a bit more complicated... when using "optimized block access" you can not used on an "address based" way anymore, so you have to use the symbolic names or drag and drop (like I did in the video with the data that the first PLC sends). You can PUT a whole DB, simply by dragging it and dropping it at the "SD_1" input. ...but as said... the topic of optimized block access is quite complex, maybe I'll make a video on it in the future.
@sashkindg5 жыл бұрын
@@hegamurl7434 I think the topic of optimized block access will be very useful.
@MAli-zh6cr4 жыл бұрын
@@hegamurl7434 In case of whole db with different data types needs to be sent, should I make another db on the other side (plc) with same data types/lengths as well?
@bacem_ch3 жыл бұрын
@@MAli-zh6cr yes
@austins.2752 жыл бұрын
Man I ran out of inputs on a big project and thought "PLC to PLC communication should be easy" 72 hours of pulling my hair and you saved me. Had EVERYTHING right but couldn't get the REQ parameter to work and your video explained it perfects. Thank you!
@hegamurl74342 жыл бұрын
Happy to hear it worked in the end!
@pksharma93294 жыл бұрын
Sir your video always helpful for me....greetings from INDIA as well
@NikPB Жыл бұрын
Thank you very much for so easy explanation of the complicated things!
@framos9991 Жыл бұрын
My favorite teacher /Thank you!
@76POK2 жыл бұрын
Thanks again. I have got so much help from this site!
@crja4114 Жыл бұрын
My good friend you have a new subscriber. Thanks.
@zedjag77014 жыл бұрын
Another great TIA Portal video, thanks a lot.
@santiagomoore3743 жыл бұрын
Sir, I have confusion over profibus, profinet, ethernet?? Please make a video on this topic. At 0:32 we found two ip address 1) is 192.168.1.1 2) 192.168.0.101 What is those two ip?? Please explain or suggest any video
@seanyushi90962 жыл бұрын
The connection id is actually not taken care by TIA. I've tried to have more than 1 PUT instructions and all of the block will always have the identical configuration following the latest changes i made, e.g. ip address of partner, memory address, etc. And this might be my issue, i need to change the connection name.
@sagarparmar89043 жыл бұрын
Sir , your videos are very helpful thanks 🙏
@petervranks27239 ай бұрын
Hello , video is well explained as ever, but still a question : do'n I need to define the S7-connections in the network view are they generated automatically ? What is the SIMATI-ACC option ? Best allways on for easy configuration with unspecified partner ( in my case S7_1500 GET from S7-1200 ?
@KIMZ471123 ай бұрын
Great Video
@mohdshahzad94272 жыл бұрын
How to convert 1 Word into bits via siemens S7 1200 PLC?
@szolek84723 ай бұрын
Hello, Is there any limitations? how many s71200 I can connect by s7 communication?
@dennisrubio2375 Жыл бұрын
why does not PLC 102 isnt on profinet red plz help sr
@melvingomez4264 жыл бұрын
How do you send multiple data..🙏🏽
@محمدالسروري-ه4ه Жыл бұрын
I need to get encoder value from another cpu can I use the GET bock and how???
@hichemchawi44985 жыл бұрын
thanks for your videos, those are very useful to learn about automation
@hansbrannstrom6203 жыл бұрын
Hi Thanks a lot for all nice videos you share with us :-) Is it even possible to test this PUT & GET function with PLC SIM? I does not get it to work....
@Reaper0931 Жыл бұрын
Hey, How can I send more information ? Im a beginner and you say in the end of the video that it is possible, how ?
@mat771112 жыл бұрын
I take it this method doesn’t work with S7-1200 PLCs?
@EshmesVid10 ай бұрын
Uhh it also works on Logo not only S7
@ikkusoft3 жыл бұрын
Can this be simulated in PLC SIM, I tried, I'm not getting value in other PLC.
@whatacode3 жыл бұрын
How Can we send use put for more than 5 plc and send data to one Common plc..... Please respond sir
@kreditslavkov81153 жыл бұрын
Hello, pleace can i have a guestion.... i used a condition as you did at the end of the video for the REQ input. i also put a negativ contact "PUT_DB".DONE instead of freguency. but when i did it for the first time nothing has came into the my next plc. when i deleted it and did it again and upload the plc program again, it works. But when i was working on that again today also same problem and i have to do the same solution. deleted that condition and do it again the same. unfortunetly i cannot used the frueqvency condition, do you know why this negativ contact "PUT_DB".DONE doesnt work for the first time(the datablock put_db is green, but nothing has came into the database on the next plc...)? and is there any solution idea for condition like do it with every cycle of the cpu?
@vijayakanthm7054 жыл бұрын
Thanks to your good work.I have a question That i didn’t have a physical plc ,so shall configure two plc’s in a single project and test them with each other by single PLCSIM.Don’t bother if it is a genuine question
@tuleanhvt4 жыл бұрын
you can simulate two PLC by PLC SIM
@MrPushpalm3 жыл бұрын
Will s71200 communicate with s71500
@ansonkiek64714 жыл бұрын
If we set unspecified is this must delete the s7 connection ? My partner plc is s400 , I tried use this function communicate but always failed.
@khaledtebai39205 жыл бұрын
This video came just in time! thank you so much! I have a school project, in wich I have to communicate three S7-1200. for now, connecting two PLC's is quit clear, with three , do I just need to add PUT and GET functions in the three of the PLC's if i want to send and read data from all three of them?
@hegamurl74345 жыл бұрын
Yes exactly! Junse repeat for the third PLC
@genantamtam93644 жыл бұрын
@@hegamurl7434 so putGet is only for siemens s7 communication? What if i want ro connect to other systems with my siemens plc? You have a video on that?
@braincrackz5 жыл бұрын
hello there greetings from saudi arabia. god bless you
@stuatkins53 жыл бұрын
hi great video , if i wanted to send a qr code value (say PAC123) from one plc to another is a put instruction the best way?
@ouluberlu73732 жыл бұрын
Hi, I'have got a 1214CPU and using TIA V15. Unfortunatley, S7-communication library is missing. Do you know if I can import it in TIA? If yes, where can I get this library? Or is it a default library? Thanks for your videos !
@rhysdavies89474 жыл бұрын
Awesome video. Thanks!
@danielesauhs50833 жыл бұрын
Hey man! I really like your videos, your explanations are excepcional, thanks for this knowlegment. Just a quick question, I have 2 PLC 1500, both have diferent subred, but one of them have two ethernet ports available, is it possible to link each other trought this free port?
@Gumballation Жыл бұрын
Hi sir! Your tutorial is amazing ❤. I have a question: is it possible to take text input from a human-machine interface and then process it using if/else statements like in programming? For example, the user types "password" and if the password is wrong, you know, like an if/else statement in programming.
@Der_Geraet14 жыл бұрын
Kann man damit auch bspw. M0.0 der einen sps setzt M0.0 der zweiten sps? Sprich kann man einfach nur merker 1 und 0 setzten damit?
@deshabandhunayak3205 жыл бұрын
What is the maximum size of data we can send in PUT command?
@mobros1298 Жыл бұрын
so clear thank you
@ericanderson560 Жыл бұрын
Do you have to be online for this to work? I can't get it to work at all. It tells me the data type is wrong when it is clearly correct, or it tells me the specified value is invalid
@ericanderson560 Жыл бұрын
It says "The data type DInt of the actual parameter does not match the data type Remote of the formal parameter". In this case I dropped it in directly from the tag table of the receiving PLC, which is in my project. They are both Dints
@OnceAgain0704 Жыл бұрын
மிகவும் நன்றி நண்பா
@vinothparker74255 жыл бұрын
Kindly make a video on various communication protocols and what is the difference between each of them sir..
@hegamurl74345 жыл бұрын
Will do at some point!
@genantamtam93643 жыл бұрын
@@hegamurl7434 hi there. You mentioned 14:46 that put/get is not your recommended type of communication but you mentioned "ip protocol"? Which one is that? Isit i-device/control? IO communication by pnpn coupler? Is that the most common?
@alvaropalenciano61474 жыл бұрын
Master!
@hegamurl74344 жыл бұрын
Give yourself some years and experience and you will be the master!
@NotMarkKnopfler4 жыл бұрын
Is this command also available over Profibus (rather than Profinet)? Thanks :-)
@ericanderson5602 жыл бұрын
DO you have to set up a TCON to do a put? If not what's the purpose of setting up the TCON in the prior video?
@hegamurl74342 жыл бұрын
No you dont have to, they are different merhods of communication. The videos are unrelated
@naifsahin2 жыл бұрын
Very useful, thanks.
@HectorRodriguez-si3yr3 жыл бұрын
i love u man, thanks a lot.
@armchairfreedomfighter5 жыл бұрын
Keep'em coming!!
@legendary6864 жыл бұрын
Thanks for the video. I have a question. Can you do this with PLCs from different brands? i.e Sending data from my siemens PLC to an omron in a different project for example?
@RemixProf3 жыл бұрын
NOPE. Siemens S7 only.
@Raul-jl1nd Жыл бұрын
thanks, grate job
@Olavotemrazaodenovo5 жыл бұрын
Where can I find the frame structure of a command between IHM and PLC by profinet? If I want to snif the protocol to discover how the adress of the word in PLC is coneccted with other adress word in IHM, how can I do it? Congratulations from Brazil. Thank you.
@hegamurl74345 жыл бұрын
Don't know what exactly you are looking for... but for analyzing network packages I recommend a free tool called "Wireshark" with which you can analyze network packages
@ziborgbe5 жыл бұрын
search for s7 protocol
@Olavotemrazaodenovo5 жыл бұрын
@@hegamurl7434 I want to analyze it. Thank you for wireshark!
@kadadjamel45452 жыл бұрын
MERCI beaucoup
@GeneralKiller13374 жыл бұрын
Nice job, Hega! I have one question: can I use this protocol with SINAMICS devices or the S7 protocol is only for the comunication between 2 S7 PLCs?
@mubarishussain36965 жыл бұрын
So you only put instruction to communicate.What about get instruction on receiving PLC.Is not required?
@hegamurl74345 жыл бұрын
You only have the instruction on one PLC: If you want to read data from another PLC you use "GET" and if you want to push data into the other PLC you use "PUT". The other PLC does not need any function (although some prerequesites as described in the video)
@alexchiosso2215 жыл бұрын
Thank you so much!!!
@umairshah97354 жыл бұрын
Hi dear , Watching your vids . Best one can offer for the betterment of human beings . Thanks alot . Dear i want to send my Level signal from one PLC to other . I am no expert . Kindly, advice me videos in your playlist which can help me . Thanks
@santoshkumarpatro27725 жыл бұрын
Thanks for this video..its helped me
@simonmax39015 жыл бұрын
That was so informative
@IK-qu9hw5 жыл бұрын
Thank you sir.
@mehmettevfikcete33975 жыл бұрын
Hegamurl hi, Is there a limit on this process. I mean, can i send for example 200 byte datas with 300 ms rate ? And could you share a lesson about putting or getting data from different brand plc's to siemens plc please.(not s7 connection) Thank u so much again. God sent you to us. :)
@mehmettevfikcete33975 жыл бұрын
Note: our network bandwith is very nice. There is no bottleneck on this topic.
@hegamurl74345 жыл бұрын
Very good question! I have never tested the maximum, but also have never reached it. I'll simply test it out (and also read the documentation) on it, when I have the time. As far as I know the PUT/GET here is only between SIMATIC components. For other devices I always recommend a TCP connection (my next videos will be about that)
@lassejespersen98804 жыл бұрын
With the 1500 system you Can PUT 400 bytes and GET 400 bytes
@akshayjadhav61454 жыл бұрын
Hello, thanks for such great videos. Could you have a video on Ethernet diagnostics to find communication error in your network and display on HMI. That would be very helpful And thank once again
@saeed2tube5 жыл бұрын
Hi I have question maybe irrelative. How we can mirror hmi to monitor without pc and use finger touch of monitor? And if you can please make video about data logging server. thankful
@hegamurl74345 жыл бұрын
Hi! I am not sure if I fully understand your question, but if you want to use your PC as HMI you will need WinCC Professional Runtime on your PC, which will simply run a program that emulates an HMI on your PC. Added Data Logging to my list!
@saeed2tube5 жыл бұрын
Thank for your answer. But i want connect monitor directly to hmi.
@GeorgeMan_19815 жыл бұрын
Use sm@rt client ..
@vishalpatil67405 жыл бұрын
Thanks bro.... 👍
@kanishgakathiravan35744 жыл бұрын
Thanks
@dee-hl2tp4 жыл бұрын
Hi, another great video thank you. Just one question, In the PU_DB ADDR_1 parameter, (P#M0.0 INT 1) is M0.0 not just 1 BIT? If so how can you store an INT value in it?
@beautyofislam3234 жыл бұрын
Thanks sir
@jamesedrielleaurellana Жыл бұрын
😍😍😍
@mrloh7197 Жыл бұрын
Is it possible to use Put and Get instruction with the CPUs with different TIA Portal Version? One using V15.1 and another using V16.0.
@GeorgeMan_19815 жыл бұрын
Just subscribe ..
@zhengkunyan80014 жыл бұрын
Good
@BG-gr1uu2 жыл бұрын
Please improve voice quality,
@Automation283 жыл бұрын
thanks for your videos, those are very useful to learn about automation