Help Dr Solar resolve the Pylontech LV Hub comm issues.

  Рет қаралды 17,646

Dr Solar @AWPS Renewable Energy, LTD

Dr Solar @AWPS Renewable Energy, LTD

Күн бұрын

I am stuck at the LV Hub, can you help?

Пікірлер: 51
@joeyranieses3489
@joeyranieses3489 2 жыл бұрын
I apologize to you on my side of misunderstanding. I read manual of up5000 and it does support daisy chaining. I think this is going to be like these in ADD dip switches assuming u(UP)=0 and d(DOWN)=1 :master A & B dip switches must be uudu and master C(last chain) uuuu. If still failing, reduce baud rate therefore, master A & B dip switches must be uudd and master C(last chain) uuud.
@drsolar
@drsolar 2 жыл бұрын
Nothing to apologize for. You were very helpful.
@nestyplus
@nestyplus 2 жыл бұрын
CAN interface is terminated by 120ohm between the hi and lo terminal. That is from CAN node to another CAN node. You can not connect CAN to RS485. Those two are serial ports but they have different communication protocols.
@drsolar
@drsolar 2 жыл бұрын
I will try your suggestions. CAN to CAN. Thank you for the suggestion
@ChasethesniperGod
@ChasethesniperGod Жыл бұрын
How did you solve the problem?
@Tom-lv1xx
@Tom-lv1xx 2 жыл бұрын
RS485 is simply not can, it will not work. So try connect from MC(Master C) A/Can to MB A/Can and MB B/RS485 to MA B/RS485. I did not hear about this wiring scheme anywhere by now, so would try the normal connection scheme. Please connect all A/Can from MA, MB, MC to the Hub and set MA Dip switch 2 on, MB Dip switch 3 on, MC Dip switches 2 and 3 on. Watch out on the numbering, if th switches are soldered in ther wrong way 1 is 4, 4 is 1, 2 is 3 and 3 is 2 respectively.
@dougveganparadisebuilder5808
@dougveganparadisebuilder5808 2 жыл бұрын
I hope this works for you Dr. Solar but I am sure that you will share the solution and give credit where credit is due.
@drsolar
@drsolar 2 жыл бұрын
The wiring and current dip switch setting work without the hub. Master A can turn all the batteries on and off. It just does not work with the Hub.
@commodoreaustralia7141
@commodoreaustralia7141 2 жыл бұрын
Hey mate, not sure if you're still having trouble.. we had a similar issue & found that on the master battery on bank 1 which connects to the LV Hub - remove wires from pins 1, 2 & 3 on this RJ45 cable. This solved our very similar issue where one out of 2 banks were being detected only - before we resolved the cable issue... Also we found the dip switches on the LV hub should all be down except for the last one on the right hand side should be up. Cheers mate
@drsolar
@drsolar 2 жыл бұрын
Good morning from Lagos. Thank you for watching and commenting. I like the community that we belong to. We try to help one another. Our initial cables had pin 1 2 and 3 removed and it did not work. We went to regular rj45 cables and we had communications between the battery banks. Then we used the the same cables between the Hub and master 1. We had to restart the batteries a few times before we got the two lights on the LV Hub to come on. We should visit the comment about the dip switch. We are getting some flickering from the BMS display on the inverter. Thank you so much for your help.
@BrianChama-ii5vc
@BrianChama-ii5vc 4 ай бұрын
Hi sir , the ALM Light is on and then switching off
@drsolar
@drsolar 4 ай бұрын
Thank you for watching and commenting. Please explain.
@MrBafaro69
@MrBafaro69 2 жыл бұрын
hi, do your master batteries have different ADD addresses? then the CAN ports of the master batteries must go to the LV-HUB. LV-HUB PIN 6 must be ON.
@drsolar
@drsolar 2 жыл бұрын
Thank you for the suggestion. We got it resolved. Welcome to the channel
@jonerasmus9399
@jonerasmus9399 Жыл бұрын
Could you explain how to set dip switches when adding new batteries?
@drsolar
@drsolar Жыл бұрын
On the Up5000 it is not necessary.
@joeyranieses3489
@joeyranieses3489 2 жыл бұрын
Additional comment ,you cannot daisy chain CAN bus from masters C to B to A to Hub as there were no terminating resistors in its both ends.
@drsolar
@drsolar 2 жыл бұрын
Pylontech does not mention resistors in the manual.
@dougveganparadisebuilder5808
@dougveganparadisebuilder5808 2 жыл бұрын
I hope you can find the solution Dr. Solar. Please share any solutions or suggestions with him, people who are in the know-how.
@drsolar
@drsolar 2 жыл бұрын
I will once I get a resolution
@joeyranieses3489
@joeyranieses3489 2 жыл бұрын
I see your problem now after several replays in your videos. Master A dip switch address assignment must be set to 0100 and its CAN cable should be plugged to port 1 of the hub. Master B dip switch address assignment must be set to 0010 and its CAN cable should be plugged to port 2 of the hub. Master C dip switch address assignment must be set to 0110 and its CAN cable should be plugged to port 3 of the hub. Do you have a complete schematic for your project and share it in video. I saw your struggles and been watching your videos anonymously for more than a year.
@drsolar
@drsolar 2 жыл бұрын
Good morning. Thank you for watching and commenting. For the US3000 and 2000 that is what the manual suggests. The Up5000 is different. The set up we used is what is in the manual. I will try your suggestion. At this point I will try anything.
@drsolar
@drsolar 2 жыл бұрын
Thank you so much. A whole year. Wow
@solargarant373
@solargarant373 2 жыл бұрын
Hi, can you explain how it is solved? We have a similair failure with 18pieces US 5000. Hope to hear from you.
@drsolar
@drsolar 2 жыл бұрын
Can you explain what the problem is? Message me on whatsapp
@solargarant373
@solargarant373 2 жыл бұрын
@@drsolar our Bms hub shows red failure led. Same problem as in video. What is your whatsapp?
@drsolar
@drsolar 2 жыл бұрын
@@solargarant373 kzbin.info/www/bejne/fpWuiKOwqMRrmsk our big problem was the cable
@solargarant373
@solargarant373 2 жыл бұрын
@@drsolar Hi thank you do much. Our problem was the same. We added some standard utp cables and there it was. Even it worked with 3 sets to the hub directly as described in the manual.
@tirivaenim
@tirivaenim 2 жыл бұрын
Hey Dr. Solar… I know you’ve been busy at the moment with the hotel project, but just wanted to check-in with you with regards to any issues with the Pylontech batteries? By the way, why didn’t you opt for the US5000, which have a longer warranty.
@drsolar
@drsolar 2 жыл бұрын
Good morning. I have not had issues with them. Yes we got the extra 3 years
@aliyumuhammad6193
@aliyumuhammad6193 2 жыл бұрын
on the switches according to battery arrangement
@drsolar
@drsolar 2 жыл бұрын
We have been following the manual and we are stumped. The only switch it says to touch is on the first master
@e.gn.g1183
@e.gn.g1183 2 жыл бұрын
Bonjour, avez vous trouver le probleme j'ai le MEME probleme sur les US3000C MERCIIIII
@drsolar
@drsolar 2 жыл бұрын
Le 3000C ne marche pas si vous n'avez des communication entre les deux. Inverter et bougie
@ОлександрДергачов-ы3з
@ОлександрДергачов-ы3з Жыл бұрын
Добрий день. З'єднання батареї PYLONTECH US5000 з інвертором deye по протоколу can або brs485? Якщо по can, то батарея постійно перезарускається, якщо brs485 індикація постійно горить. Можливо підключати 2 кабелями і по can і по brs485? Дякую.
@drsolar
@drsolar Жыл бұрын
You can]t do two protocols. It is one or the other. How old is your Deye inverter?The cable for the UP5000 C is different. Pay attention to your cable
@offgridwanabe
@offgridwanabe 2 жыл бұрын
If it was me I would unplug it all and start with one battery then add the rest one at a time to see if they were accepted eventually you will find the battery which is configured wrong.
@drsolar
@drsolar 2 жыл бұрын
Did that many times. The A master battery can turn all the batteries on and off
@adou7716
@adou7716 Жыл бұрын
Please can you help me ? I have exactly the same problèm. I can Connect the master to the lv hub. What was youre problem ? Thanks you
@drsolar
@drsolar Жыл бұрын
Please explain what you are lookin for help on
@chandarasemi6227
@chandarasemi6227 2 жыл бұрын
Please follow manual step by step
@drsolar
@drsolar 2 жыл бұрын
Thank you very much. We resolved it. Thanks for watching and commenting. Don't forget to subscribe.
@e.gn.g1183
@e.gn.g1183 2 жыл бұрын
@@drsolar quel était le probleme ?
@drsolar
@drsolar 2 жыл бұрын
@@e.gn.g1183 Salut. Dit moi votre problem. Type de Inverter, si vous avez de communication entre pylontech et l Inverter.
@catalincomsa7832
@catalincomsa7832 9 ай бұрын
@drsolar
@drsolar 9 ай бұрын
Thank you?
Pylontech 125 kwh battery bank is up and working. how did we do it
6:40
Dr Solar @AWPS Renewable Energy, LTD
Рет қаралды 15 М.
Clarification of the DIP Switch Settings on EG4 LiFePOWER4
6:32
Lance Knoechel
Рет қаралды 12 М.
Players vs Corner Flags 🤯
00:28
LE FOOT EN VIDÉO
Рет қаралды 61 МЛН
Which One Is The Best - From Small To Giant #katebrush #shorts
00:17
Brawl Stars Edit😈📕
00:15
Kan Andrey
Рет қаралды 53 МЛН
- "SolaX Inverters And Batteries: 3 Years Later, Is It Worth It?
10:06
Dr Solar @AWPS Renewable Energy, LTD
Рет қаралды 245
Pylontech Battery Firmware Upgrade How To US2000C / US3000C
21:34
Pylontech US2000C internal fuse repair (Solar Lithium LiFePO4)
11:44
Solar Sizing Secrets: Why One Size Doesn't Fit All When It Comes To Solar Systems
8:21
Dr Solar @AWPS Renewable Energy, LTD
Рет қаралды 895
What's Your Protection Game? Check Out Our Solution. @SolaxPowerGlobal
5:16
Dr Solar @AWPS Renewable Energy, LTD
Рет қаралды 549
Deye 8 kw hybrid Inverter. Updating the firmware
9:36
Dr Solar @AWPS Renewable Energy, LTD
Рет қаралды 28 М.
2 Nouvelle Batterie Us2000C Mai 2022
15:01
regiSolaire
Рет қаралды 19 М.
Adding a new Pylontech US5000 battery to my home energy storage.
11:49
Nicholas Howell
Рет қаралды 46 М.
Players vs Corner Flags 🤯
00:28
LE FOOT EN VIDÉO
Рет қаралды 61 МЛН