How electrical distribution systems TN TT IT protect against indirect contacts. Grounding systems.

  Рет қаралды 85,434

SCIENTIA

SCIENTIA

Күн бұрын

Пікірлер: 41
@asiaintermat
@asiaintermat 6 ай бұрын
Very useful!!! My country changed few years ago country code to Europion code . And also Protection Code changed to same as European Code
@andersonpinesso2812
@andersonpinesso2812 6 ай бұрын
Thank you very much for perfect explanation...very good job
@Ignisan_66
@Ignisan_66 6 ай бұрын
In the country I live in we use TN-C-S for most applications, TN-S and IT in a few niche applications.
@abdullahalahmadi695
@abdullahalahmadi695 Жыл бұрын
Thank you very much. I have TN C-S system in my building, and a 3-phase lift motor with control panle in the sixth floor is connected properly to the system as you described and there is encased electrode that is conected to the building structure and to foundation sticking out in the elevator room can I used as earthing for further protection and ground the control panle and the elevator motor to it.
@mjamshidi1993
@mjamshidi1993 3 жыл бұрын
It was very useful video
@danalex2991
@danalex2991 3 жыл бұрын
Good comprehensive video
@NihilisticAngel
@NihilisticAngel 2 жыл бұрын
are there any reading materials that you recommend? I would like to read up more on this topic.
@spelunkerd
@spelunkerd Жыл бұрын
In a TT system I believe the whole house RCD is upstream of the breakers. As discussed below, for safety there is never any breaker or switch to interrupt neutral lines. Also I believe the TCN-S system is so labeled simply because the feeder wires to the home combine N and PE together, not because there is a mix of downstream components that are fed with either separate or combined neutral. As a rule of thumb the bonding of neutral and PE (in TCN-S) happens at only one point between the service input and the main house beaker, and there are never any devices on the other side of that bond. You might consider doing this again, it is a useful resource. You might also bridge into how a broken neutral can change the neutral and ground voltage level throughout the home, causing some devices to experience higher than average voltage drop because of imbalanced consumption between the two lines of a split phase 120V TCN-S system.
@Zuwwar
@Zuwwar 11 ай бұрын
Why it is not recommended to distribute neutral in IT earthing system?
@coldscug
@coldscug 10 ай бұрын
I think there is no harm using the Neutral as long as its not referenced to the ground. The whole idea is to separate the installation from any potential difference to the ground.
@إبراهيمالشلبي-ب1ف
@إبراهيمالشلبي-ب1ف 2 жыл бұрын
In the IT system fault why the touch voltage is not as the same voltage of the supply?.
@okaro6595
@okaro6595 2 жыл бұрын
Because of the high impedance of the earth connection. Also even the open circuit voltage is just 133 V because one has no neutral.
@zazugee
@zazugee 2 жыл бұрын
it's a floating ground
@sotadjiqtasotadjiev9390
@sotadjiqtasotadjiev9390 3 ай бұрын
👌
@Imtiyaz5power
@Imtiyaz5power 2 жыл бұрын
Awesome 🔥
@mohamedabass9795
@mohamedabass9795 2 жыл бұрын
Excellent
@ZopcsakFeri
@ZopcsakFeri 3 жыл бұрын
"My name is Robert" - says the robot :D I see what you did there...
@SCIENTIAPLUS
@SCIENTIAPLUS 3 жыл бұрын
???
@ZopcsakFeri
@ZopcsakFeri 3 жыл бұрын
@@SCIENTIAPLUS "Robot" / "Robert" - you know :D great video though! I usually never believe what robots say, but in this video it was valuable information and easy to follow. Have you considered to use real human voice though? It would make your videos more popular (because many people hate computer-generated narration).
@SCIENTIAPLUS
@SCIENTIAPLUS 3 жыл бұрын
@@ZopcsakFeri Hello Ferenc, what do you propose?
@ZopcsakFeri
@ZopcsakFeri 3 жыл бұрын
​@@SCIENTIAPLUS Well, there are multiple ways, and they are not even as difficult, since I suppose for the synthetically generated voice, you already have a script. So one possible solution could be to read it in your own voice, that would make it sound more natural. Another way could be - in case you don't feel the confidence to do this - would be to ask one of your friends with a nice English pronunciation to read it out for you - you record it, and use it as the narration. In both cases the results are usually more popular than the computer-generated versions. Of course they require mort effort, but people seem to like them more than synthetic voices. :) But this is just a mere suggestion - your video is still a very good one with useful information - I urge you not to feel offended by my ideas here. just in case you want to give your videos more "personality", then this could be an effective way to do.
@SCIENTIAPLUS
@SCIENTIAPLUS 3 жыл бұрын
@@ZopcsakFeri Hello Ferenc, I am not offended, just the opposite. I really appreciate any comments to improve. Thanks a lot
@abdulbaqihaitham7704
@abdulbaqihaitham7704 3 жыл бұрын
Very thanks
@SCIENTIAPLUS
@SCIENTIAPLUS 3 жыл бұрын
Hello Abdulbaqi, thanks to you for seeing the video!!!
@vlog-tube6890
@vlog-tube6890 2 жыл бұрын
Thanks
@BjornV78
@BjornV78 2 жыл бұрын
Good video, but the animated person is distracting and doesn't add a extra value to the video.
@florincheche163
@florincheche163 Жыл бұрын
👍
@ahmedrefaat2874
@ahmedrefaat2874 3 жыл бұрын
at TNC CONNECTION , YOU put on the diagram a Circuit beaker on the PEN which goes to the load , which is wrong, as it is prohibited to break the PEN , Because this will isolate the earth to the loads, which is dangerous !!!!
@SCIENTIAPLUS
@SCIENTIAPLUS 3 жыл бұрын
Hello Ahmed, you are right! copy paste error. I will correct it. Thanks a lot for the comment!!!
@okaro6595
@okaro6595 2 жыл бұрын
Breaking the PEN energizes all grounded equipment cases. No fault in the equipment is needed. That is highly dangerous.
@robertokrauze397
@robertokrauze397 Жыл бұрын
That is the reason why I always read the comments bellow to the video. Good Job.
@JonasKianzad-zn4oi
@JonasKianzad-zn4oi Жыл бұрын
Why do you spend time animating this person standing there, which are just flexing. Instead of animating this electrical system much better?
@zaitonyahya4768
@zaitonyahya4768 Жыл бұрын
Ump&kwsp
@ShomiTheGreat
@ShomiTheGreat 6 ай бұрын
It hurts listening to the AI voice. Anything's better than AI.
@ThanhNguyen-wh9ih
@ThanhNguyen-wh9ih 3 жыл бұрын
the sound is not good I am quite disappointed
@sergioraffo6795
@sergioraffo6795 5 ай бұрын
Sarebbe bello sentirlo in italiano
@freedomofopinion6135
@freedomofopinion6135 2 жыл бұрын
We wish explain videos Arabic
@SCIENTIAPLUS
@SCIENTIAPLUS 2 жыл бұрын
Hello, thanks for your comment, unfortunately I don't know Arabic, although I would like to learn it.
Grounding and bonding: Definitions and details
12:42
Eaton
Рет қаралды 101 М.
Don’t Choose The Wrong Box 😱
00:41
Topper Guild
Рет қаралды 62 МЛН
黑天使只对C罗有感觉#short #angel #clown
00:39
Super Beauty team
Рет қаралды 36 МЛН
My scorpion was taken away from me 😢
00:55
TyphoonFast 5
Рет қаралды 2,7 МЛН
Overcurrent, Overload, Short Circuit, and Ground Fault
6:54
Dave Gordon
Рет қаралды 938 М.
TT SYSTEMS - WHY MUST THEY BE RCD PROTECTED
17:09
LEARN ELECTRICS
Рет қаралды 38 М.
Nettsystemer - IT, TT eller TN?
10:41
BKK
Рет қаралды 6 М.
Using a TT earth where a TN earth already exists
23:49
John Ward (jwflame)
Рет қаралды 76 М.
Why there is no Neutral in Transmission Lines?  Explained | TheElectricalGuy
8:46
Gaurav J - TheElectricalGuy
Рет қаралды 280 М.
TN-C-S Danger - Broken PEN Conductor (Combined Earth & Neutral)
9:50
John Ward (jwflame)
Рет қаралды 166 М.
Loop Impedance
15:56
John Ward (jwflame)
Рет қаралды 293 М.
Types of earthing systems explained  | TN S, TN C, TN C S, TT  &  I T |
8:54
Don’t Choose The Wrong Box 😱
00:41
Topper Guild
Рет қаралды 62 МЛН