How to do cable sizing for MCC panel

  Рет қаралды 14,968

electrical mastar

electrical mastar

Күн бұрын

Пікірлер: 29
@johnnyambi550
@johnnyambi550 Жыл бұрын
EYE OPENER PLEASE CONTINUE WITH THE GOOD CAUSE
@pavanmahajan8703
@pavanmahajan8703 3 жыл бұрын
Thank you for this. Very good informative video!!
@dkverma67
@dkverma67 2 жыл бұрын
Your video is very good and informative
@morraa13
@morraa13 2 жыл бұрын
For more clarity 4 runs per ph. that's means 4 x (4C x 240 SQMM) + G. Thanks for your effort.
@sattibabu229
@sattibabu229 2 жыл бұрын
Thank you so much for your information.Can you explain differences to wcl and armoured cables ? How to select water cooled leads ?
@gautamlnt
@gautamlnt 3 жыл бұрын
The short circuit current will get devided into 4 cable runs, so your system short circuit current per cable will be 30/4 kA and your calculated cable short circuit capacity is 34K.
@devendra09singh
@devendra09singh 2 жыл бұрын
Please tell me what power factor shall be consider for DOL motor, VFD drive motor and for feeder.
@fisonraj8073
@fisonraj8073 3 жыл бұрын
great.thank you sir
@pramodgavit7666
@pramodgavit7666 3 жыл бұрын
Nice vdo sir can you do it same for Size of earth wire ,electrode for building and house...calculation
@devendra09singh
@devendra09singh 2 жыл бұрын
Please tell me the effect of ambient temperature, short circuit current, soil resistivity in cable sizing.
@pankajsonu3768
@pankajsonu3768 2 жыл бұрын
Dear sir How you find the value of sin value in voltage drop formula
@rudsonpietersz4946
@rudsonpietersz4946 6 ай бұрын
whats stands FLI for.?
@dkverma67
@dkverma67 2 жыл бұрын
Please specify: 1. Why No Voltage drop has been considered due to motor load starting current? 2. Why transfer full load was not considered ? After period of time more load may be put upto transfer full load. 3. Power factor shall be less than 0.9 as depends on nature of load. Regards
@manishmonci5730
@manishmonci5730 3 жыл бұрын
Hello, Please tell why ahve you taken Full Load Current =774 A, when rated CB Full Load Current Value was 721A and previous Ampacity Calculation Full Load Current for 4 runs was 876 A. Please tell if its an error. Sir, please show another video of breaker Sizing calculation with a heavy motor with all the calculations for Cable Sizing, Breaker sizing etc for a simple HT /LT Motor with an SLD.
@pankajkumar-tv9qq
@pankajkumar-tv9qq Жыл бұрын
Please explain cable schedule
@soumyajitbaur9153
@soumyajitbaur9153 3 жыл бұрын
sir what is dyn?
@mwncc6528
@mwncc6528 2 ай бұрын
Sir sorry, I have question in cable sizing. What is the meaning of no of runs? Example: 5R/3.5C/240sqm/XLPE and 1R/3.5C/25sqm/XLPE Thank you Sir
@dhirendrapratap4056
@dhirendrapratap4056 3 жыл бұрын
Sir, we devide derating factor to the base current or multiply , some confusion becuse in some KZbin video they divide but you multiply , Kindly clear it
@AfrozAlam975
@AfrozAlam975 3 жыл бұрын
Bcoz already cable size is fixed so we can't increase the cable size we can increase the run of cable
@dkverma67
@dkverma67 2 жыл бұрын
The values should be increasing in order . If multiply it should be more than 1'some number
@siyadsirajudeen657
@siyadsirajudeen657 3 жыл бұрын
Thanks
@electricalmastar
@electricalmastar 3 жыл бұрын
Thanks dear
@sudhansusamal8886
@sudhansusamal8886 Жыл бұрын
Hindi main ...new videos karie..sir
@SONUKUMAR-23
@SONUKUMAR-23 2 жыл бұрын
Plz hindi
@manoranjan4598
@manoranjan4598 3 жыл бұрын
Hindi
@electricalmastar
@electricalmastar 3 жыл бұрын
Ok bro i will make hindi version very soon
@mohammadshabeer8749
@mohammadshabeer8749 3 жыл бұрын
How full load current becomes 774A instead of 729A in voltage drop formula?
@electricalmastar
@electricalmastar 3 жыл бұрын
Yes you are correct for voltage drop calculation only consider full load current 729A
Transformer sizing for MCC or Switchgear
9:00
electrical mastar
Рет қаралды 9 М.
Medium Voltage Switchgear Fundamentals: The Mini Course
36:46
EEB: Electrical Engineer BootCamp
Рет қаралды 48 М.
Hilarious FAKE TONGUE Prank by WEDNESDAY😏🖤
0:39
La La Life Shorts
Рет қаралды 44 МЛН
Andro, ELMAN, TONI, MONA - Зари (Official Audio)
2:53
RAAVA MUSIC
Рет қаралды 8 МЛН
BREAKER AND CABLE SIZES FOR ELECTRICAL CIRCUITS.
11:39
LEARN ELECTRICS
Рет қаралды 182 М.
Busbar sizing
9:27
stephen brooks
Рет қаралды 137 М.
Cable sizing calculation|How to select cable size|Electrical Technology and Industrial Practice
22:27
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 166 М.
Easy Guide to Cable Sizing and Cable Calculations
22:01
Sparky Help
Рет қаралды 114 М.
Designing of MCC Panel
16:37
Star Automation
Рет қаралды 34 М.
VCB closing circuit scheme full explanation
17:56
electrical mastar
Рет қаралды 73 М.
Cable Tray Size Calculations | Cable Tray Selection | Electrical Designing
6:26