How to find a refrigerant leak in an air conditioner?

  Рет қаралды 176,396

Taddy Digest

Taddy Digest

Жыл бұрын

Join this channel to get access to perks:
/ @taddydigest
Wanna Learn more about hvac? Check out my hvac tips for technicians playlist.
• HVAC Tips for Technicians
Diversitech 800-002 Pro-2000 Leak Detector Spray - 1 Quart
amzn.to/3SI2SjI
Fieldpiece DR58 - Heated Diode Refrigerant Leak Detector
amzn.to/3y1KvP0
@DiversiTechCorp

Пікірлер: 228
@terrimcglothin2230
@terrimcglothin2230 6 күн бұрын
If I can't find a residential leak with an electronic & sonic leak detector within 30-40 minutes , I like to add fluorescent dye while I add refrigerant. This provides comfort cooling until we can reschedule the leak inspection, and let the dye have time to show up After 35 yrs in residential, if I can't find the leak in a half hour or so on most units, then I know it is going to be a tricky one. The uv dye really helps to pinpoint the problem. Owner operators.. Remember, dye is a tool to help you. You dont need to make a fortune on the dye. Be fair to your customers. You will earn a fair profit during the repair or replacement of the coil.
@TaddyDigest
@TaddyDigest 6 күн бұрын
Excellent advice 👍
@GApawpawandnana
@GApawpawandnana 2 күн бұрын
I wish I could get y’all’s service in NW Georgia. I was told you can’t fix a leak. You have to have a new unit. I get refrigerant added twice a season or use window units.
@OcRefrigeration
@OcRefrigeration Жыл бұрын
Good video ! But Here’s some tips from a Guy doing it for 42 Years. 1) if System has at least 1lb of liquid refrigerant in it. ( 410a systems ) Just pull the disconnect. Wait 5 min for system to equalize. Equalized pressures on 410a system at 60 degrees outside with liquid in it will be 170Psig. Higher if its hotter out. See pt chart. 170 is plenty to find a leak with a H10-leak detector or any decent leak detector. 2) Most Leaks are in evaps. 75% of the time. Start there first. 3) Rarely have i needed to pressure test over 150 psi to find a Leak with a Ge H10 leak detector.
@stevenross9271
@stevenross9271 11 ай бұрын
I have been doing refrigeration and air conditioning for over 45 years. I am partial to my Inficon select. I spent 30 of those years behind a desk as a service manager. I diagnosed techs problems over the phone. Always look for a leak if the unit is low. To just add gas is not performing your job.
@stevenross9271
@stevenross9271 11 ай бұрын
The G.E. H-10 with a cord is without a doubt the best leak detector you can get your hands on.
@kylehennen
@kylehennen 11 ай бұрын
My man’s got a bow tie on his lip!
@shk2564
@shk2564 Жыл бұрын
“Three dead mice…three dead mice…see how they spin around the blower motor.” 🎶 😂
@dalemihocik4732
@dalemihocik4732 Жыл бұрын
I like how you gave the customer options and didn't judge him on what he chose. I need to find an independent contractor because these company guys are driven to force service contracts and high end equipment down your throat at every given opportunity. Maybe I'll get lucky and find a guy like you.
@TaddyDigest
@TaddyDigest Жыл бұрын
Thank you yeah I just want my customer to be happy. I offer my advice and it's always just what I would do if I had their situation. I agree with you A lot of companies are just driven to make a sale and they don't care about the customer
@ronniehvac653
@ronniehvac653 11 ай бұрын
Hey Dale, I hear ya brother. I work for a company in the Hudson valley in NY. A lot of competition but countless number of times I'm servicing equipment with the competition's sticker on it. I always try to be as transparent as possible. I've learned that once you lose a customers trust, you've lost their business.
@Minimarshi
@Minimarshi 11 ай бұрын
@@TaddyDigest I have the same issue, lost about a pound in a year. Have had 3 companies come out only to not pinpoint the leak, guessing it's probably on the back of the evaporator coil like this one. What did you recommend replacing, the coil or the whole handler?
@dioramaworldcustoms
@dioramaworldcustoms 9 ай бұрын
You are the best teacher on here! I’ve been thinking about going to school for my H-Vac license. Texas is so hot during the summers! I liked & subscribed!
@TaddyDigest
@TaddyDigest 9 ай бұрын
Thank you so much
@srobeck77
@srobeck77 11 ай бұрын
The common census for leak checking is to raise the pressure no higher than the highest rating on the low side. Its to avoid damaging the internals of the system.
@rwood1995
@rwood1995 9 ай бұрын
That makes it hard to sell them those items though dont it?? 🤑 JK LOL
@g-lato9791
@g-lato9791 Ай бұрын
Does that also apply to the heat pump tho , since it is reversible and they both use the high pressure
@srobeck77
@srobeck77 Ай бұрын
@@g-lato9791 incorrect. This is a lack of understanding right here. In a heat pump, the high side just alternates between the evaporator and condenser but is still same high side pressure reading to go off and you should not exceed that number.
@ParabellumX
@ParabellumX Жыл бұрын
I use Fieldpiece's DR82 Infrared Leak Detector. It's freakin awesome! I do a 3-hits-it's-a-leak check, but I really don't have to; if it goes off, there's a leak (or I accidentally bumped the tip on something). Probably the greatest feature about this particular leak detector is the fact that it gives you three signs to let you know that there is a leak: there's the audible sound, the flashing of the tip, and a vibration throughout the leak detector itself. That's awesome! So it doesn't matter if you're blind, deaf, or dumb, you will find a leak if there is one!
@hectordaniel30
@hectordaniel30 Күн бұрын
I joined. Like your videos very thorough .
@TaddyDigest
@TaddyDigest Күн бұрын
Thank you so much for joining. Here is my email tadfuller1@gmail.com
@AfiOye
@AfiOye Күн бұрын
Great video! I feel like people are scheming us and we live in Florida and our AC unit broke 3 times in the last year and we got it new last year. Weird
@TaddyDigest
@TaddyDigest 18 сағат бұрын
It's hard to find Honest companies.
@seadogharris2102
@seadogharris2102 Жыл бұрын
Great information. Just ordered Webb Coil Cleaner from Lowes.
@robsimmons7650
@robsimmons7650 15 күн бұрын
H10Pro by Bacharach for leak detectors. Always check the service port caps with electronic before getting the gauges out of the truck and before touching the caps.
@maryschultz645
@maryschultz645 29 күн бұрын
thanks for the vid Tad !
@chadriddle3517
@chadriddle3517 10 ай бұрын
Excellent information in this video! Man I appreciate that for people like me that watches KZbin to learn for homeowner use . Subscribed
@TaddyDigest
@TaddyDigest 10 ай бұрын
Glad to hear the information was helpful thank you so much for watching
@dyershvac5884
@dyershvac5884 Жыл бұрын
Great job Tadd!
@TaddyDigest
@TaddyDigest Жыл бұрын
Thank you my friend
@RollingThunder808
@RollingThunder808 9 ай бұрын
CPS leak detector is the best. We had a leak on the R114 plant and it was like chasing a ghost. We put soap on the area and it took about five minutes and the bubbles were so small it looked like shaving cream. That's how small the leak was.
@thomasglessner6067
@thomasglessner6067 5 ай бұрын
Great video. Thank for sharing your knowledge and skills. Im subscribed.
@benb3928
@benb3928 8 ай бұрын
"I will keep you cool if you let me!" ..clever tag line earned my sub.
@TaddyDigest
@TaddyDigest 8 ай бұрын
Thank you brother
@kabsatofficial
@kabsatofficial 6 ай бұрын
500psiig...bro it will not break the system?
@kabsatofficial
@kabsatofficial 6 ай бұрын
Thank you ted
@RocisBigBroSavage
@RocisBigBroSavage 11 ай бұрын
Great quality content. Keep it coming!
@TaddyDigest
@TaddyDigest 11 ай бұрын
More to come!
@jefflemberg645
@jefflemberg645 11 ай бұрын
How many clowns just fill up your freon and try to sell you a new unit when it all leaks out again?
@HippieMosquitoQuatro
@HippieMosquitoQuatro 4 ай бұрын
Yes.
@waynegent2263
@waynegent2263 3 ай бұрын
My boss gets upset at my sales bc their so low. I always find the leak and make sure customers get repairs pricing and unit price depending on warranty. He hates it but keeps up withit
@leestebbins5051
@leestebbins5051 16 күн бұрын
Freon? Old timer.
@AfiOye
@AfiOye Күн бұрын
Yeeeees! That's why I'm watching this video because we got new unit last year, and the man done put freon in it twice and it's still messed up. He didn't even tell us we had a leak.
@calabamian
@calabamian 9 ай бұрын
Is there anyone cool and honest like you in San Diego?
@TaddyDigest
@TaddyDigest 9 ай бұрын
not sure my friend
@godfreyappliance5585
@godfreyappliance5585 9 ай бұрын
I use accu trak ultrasonic. I have used it for a little over 10 years. Works great. It is not a sniffer. Sniffer will go off with anything that burns.
@renaissanceman5847
@renaissanceman5847 11 ай бұрын
I feel for the home owner... but the best thing to do is have some window units ready... 3 units are more than enough to keep you comfortable enough when SHTF with the main AC. they cost $150 each. Then with an older system, especially one approaching 20 years... just get the full install. else with and older system you may find yourself spending more money over the long term vs a new system plus the inconvenience (they always break on a Friday afternoon ) constantly fixing issues as its dies. At least you can get a warranty on installation and equipment that will cover you for a year or more. I also recommend insisting they inject UV dye into the system upon installation or even service. that way its easier to find the leak should one creep up at any point due to installation errors or aging.
@thecurious6721
@thecurious6721 Жыл бұрын
Thanks for the tip 👍
@TaddyDigest
@TaddyDigest Жыл бұрын
Any time!
@ricardoa4322
@ricardoa4322 9 ай бұрын
I use the yellow jacket infrared leak detector works great
@kevinplante1667
@kevinplante1667 26 күн бұрын
Some of the new evaporator coils will not withstand more than 150 lbs. of pressure without causing a leak, they have warning labels saying as much
@joshuaseaton7002
@joshuaseaton7002 Жыл бұрын
Hey Tad. What's the 1 to 98 countdown when the wind free units shut off after cooling?
@NytefogNJ
@NytefogNJ Жыл бұрын
I use the Testo 316-4 for R410a systems and the Testo 316-3 for R22, but the Inficon Tek Mate is also great option for r-22 systems ( I also have a Inficon tek mate). The Testo 316-4 is probably the most sensitive electronic leak detector I’ve used for r410a.. and I’ve can’t even start to tell you how many electronic leak detectors bought then sold trying to find a good model. Do a Search for NathanHVAC electronic leak detector sensitivity test. He has tested most of the leak detectors I’ve purchased. He has made spreadsheet of the leak detectors and their sensitivity for R22 and R410a refrigerants. I’m trying out Ultrasonic refrigerant leak detector this spring/summer to see if that can help pin point small leak’s faster.
@MrDeviousdom
@MrDeviousdom Жыл бұрын
I've used several ultrasonic leak detectors and found that they were useless when trying to find small leaks. See what the return policy is on the tool just in case. A good way to test it is by using a calibration vial.
@MetalDetectingwithCZkidd
@MetalDetectingwithCZkidd Жыл бұрын
I would not recommend to anyone to go 500psi on a leak test. I, like Oc have been doing it a long time. Never pressure tested that high, even on the commercial side of things. Can get dangerous. Usually there are operating max pressures listed, I would not exceed those. There is a leak detector that works via sound. I had one of those as well, no matter how small the leak, it would sound like a hurricane in your ears. Nice vid.
@MrDeviousdom
@MrDeviousdom Жыл бұрын
500+ psi is where a 410a system is operating during the summer.
@MetalDetectingwithCZkidd
@MetalDetectingwithCZkidd Жыл бұрын
@@MrDeviousdom where? If so, clean the coil. Maybe in AZ. Not in FL.
@MrDeviousdom
@MrDeviousdom Жыл бұрын
@@MetalDetectingwithCZkidd In hot areas. I don't understand the point of your comment.
@epeterson711
@epeterson711 11 ай бұрын
Agreed! I have never heard of anyone EVER going to 500 psi!
@MrDeviousdom
@MrDeviousdom 11 ай бұрын
@@epeterson711 well, I'm in AZ and it does all the time on rooftop units.
@ronniehvac653
@ronniehvac653 11 ай бұрын
Hey, Tad. I use the yellow jacket sniffer. But I also use the Superior Accu Track ultrasonic leak detector. You could have heard those mice fart before they died.
@TaddyDigest
@TaddyDigest 11 ай бұрын
Very cool ronnie
@sonnguyen-ve7gn
@sonnguyen-ve7gn 7 ай бұрын
Great video !
@TaddyDigest
@TaddyDigest 7 ай бұрын
Thanks!
@michaelfesta9289
@michaelfesta9289 10 күн бұрын
Great video very Informative And very easy for Me the weekend warrior to follow
@TaddyDigest
@TaddyDigest 9 күн бұрын
Great to hear!
@craigmarshall40
@craigmarshall40 11 ай бұрын
You have some good prices 😮
@SteveM-426
@SteveM-426 10 ай бұрын
Dye is Best! Hands Down.
@danceaway2nite
@danceaway2nite 11 ай бұрын
Bow tie.... mustache?!!! 😂 too cute!!! 😊😊
@sbnatomicrecords
@sbnatomicrecords 2 ай бұрын
Great info. Its a shame when you have guys add more freon and try to sell it to the customer knowing there is a leak. Smh
@stansummers6259
@stansummers6259 11 ай бұрын
Great video buddy
@TaddyDigest
@TaddyDigest 11 ай бұрын
Thank you my friend
@dgair5635
@dgair5635 8 ай бұрын
I am just doing some research to learn more. My techs are taking 4 hours to do a leak check after putting dye in the week before :)
@TaddyDigest
@TaddyDigest 8 ай бұрын
You can do it!
@joelbell9082
@joelbell9082 11 ай бұрын
If it's a large leak in an air conditioning system it's usually on the high side of the system To check the condenser hook up your high side and low tide gauges turn off the power remove the condenser fan motor from the top of the unit Turn the unit power back on checking the high side pressure with condenser fan motor not working the high side pressure will increase to a point where you might be able to locate the week much easier Do not exceed momentarily 400 PSI Turn off the power check With an electronic leak detector You can also use an UltraViolet leak detector After injecting and allowing the fluid to circulate throughout the system One other method is using nitrogen to build up the pressure to see if we could find a slow leak using a Ultra Violet leak detector after injected fluid All these methods MUST only be performed by specially trained air conditioning service technicians with years of experience Absolutely no homeowners should ever attempt these leak detection procedures which could cause permanent bodily injury or possible death Leave it to the professionals
@caru3257
@caru3257 Ай бұрын
Three dead mice would be a great name for rock band.
@StevenSchoolAlchemy
@StevenSchoolAlchemy 9 ай бұрын
tell us about the stop leak additives.
@TheStantony
@TheStantony 6 ай бұрын
Hi. What are the resons if frequently happen leakage in condenser coil bends
@alderoth01
@alderoth01 9 ай бұрын
What does it mean when the copper tubing, the one inside by the unit is warm to the touch, even the copper outside?
@flint7777
@flint7777 Жыл бұрын
Good guy
@MonsurBakare
@MonsurBakare 17 күн бұрын
I joined
@StevenSchoolAlchemy
@StevenSchoolAlchemy 9 ай бұрын
look for oil on the tubing
@ericwilliams3407
@ericwilliams3407 6 ай бұрын
Taddy digest have you ever worked on farm equipment ac units I’m a mechanic an have been fighting with one of are equipments ac units I’ve done replaced an fixed where the leak was but it still is leaking down can you help us out
@microgreensgrower3946
@microgreensgrower3946 7 ай бұрын
I'm at 2:20 in the video. Does this hold true for vehicle A/C's? (slow leaks = low pressure side and fast leaks =high pressure side? Thanks for the video!
@TaddyDigest
@TaddyDigest 7 ай бұрын
It really depends on the size of the area that's leaking
@AzizAziz-tp6wd
@AzizAziz-tp6wd 4 күн бұрын
Good price
@bruceelias2732
@bruceelias2732 10 ай бұрын
Thank you sir
@TaddyDigest
@TaddyDigest 10 ай бұрын
You're welcome my friend
@twolfe4295
@twolfe4295 Жыл бұрын
I use the same detector that you have and maybe it would have found the leak if you had used it.
@taylerellis217
@taylerellis217 Жыл бұрын
lol you don't put in 350 or 500psi nitrogen in a residential unit to leak test. Commercial/res tech here over 20 years. you need to read the max test pressure for both the evap coil and the outdoor coil and which ever is lower go with that pressure for test. Many R22 indoor coils are only rated to 150psig max test pressure if you add 350-500psig you are creating new leaks in the evaporator coil!! but idk maybe I screwed this all up and this video is so homeowners take out their A coils in a way they will need to replace them entirely. ooops
@yurikorenev7498
@yurikorenev7498 11 ай бұрын
Correct. I close valve on condenser and put separate line pressure to evap and condenser about 300. after 1 day already see with line is leaking.
@jonswisher8796
@jonswisher8796 11 ай бұрын
Most refrigerant leak detectors are incredibly sensitive. If you add any refrigerant you should always do a leak search. A basic leak search only takes 10-15 minutes to make sure you don’t have a good size leak. You don’t have to reclaim the gas and add nitrogen, the refrigerant is the gas you are looking for, and soap bubbles will also blow bubbles regardless if there is nitrogen, as long as there is pressure, don’t complicate it. You can’t give the customer the choice you are supposed to make as a trained technician when it’s such a simple move and avoids callbacks
@thejimmyrig
@thejimmyrig Жыл бұрын
I have a system from the mid 90s that hasnt run in a few years due to a leak and the refrigerant being super expensive. can a system like that be repaired and retrofitted? or would it be a wash in cost and better to just update?
@TaddyDigest
@TaddyDigest Жыл бұрын
I would probably upgrade
@JC-sc9rx
@JC-sc9rx 22 күн бұрын
Tad is solid
@mustangmike6421
@mustangmike6421 4 ай бұрын
Can u do a video on superheat and subcooling, i know everyone tells people to only check subcooling, which if the system is installed properly the txv will hold the superheat to what it is suppose to be, but alot of the time it's not and superheat is usually way low.
@TaddyDigest
@TaddyDigest 4 ай бұрын
Type in the search bar super heat and sub cooling taddy digest. I did a video
@user-ni2gf8gb9x
@user-ni2gf8gb9x 4 ай бұрын
I have had hit or miss with Electronics. It often goes off (all brands) if its near water in the pan , My Inficon goes off in light wind, My field piece just goes off because field piece. lol I almost always have better luck with Nitro and visual with soap bubbles.
@9to5techs
@9to5techs 3 ай бұрын
is goodman heat pump GSZB404210A good for 2014 mobile home? in amarillo texas , r19 walls, r25 roof, r 30 floor, singal pan widows, 1216 sqft home. not air tight it has leaks. temps below 20 is like 8 days during heating seanson. i set termostat to 74 f and am using electric furnace 10 kwh for 108 hours a month. my electric rate is 0.097 kwh. the highest bill to have was 250 but that is from whole home usage. the goodman heat pump says it uses 2.9 kwh at 10 f with a COP of 2.08 and a 2.7 kwh with COP of 1.34 at -5 f. the price for the 5 ton a-coil and 3.5 heat pump is $4,876. i can get 30% off that price on rebate then it whould be $3,413.235 also, why whould tech go with mortex 5 ton a-coil and 3.5 heat pump. thanks for help.
@guadalupemartinez-mj5ie
@guadalupemartinez-mj5ie 14 күн бұрын
Technician said had freon leak! On evaporator! $. Ouch! He put leak seal! Looked like a syringe. What are you thought on leak seal. After a month, failed to cool again!
@TaddyDigest
@TaddyDigest 14 күн бұрын
Find the leak and fix it
@craigmarshall40
@craigmarshall40 11 ай бұрын
H10 with the long probe
@williamlangley2044
@williamlangley2044 Жыл бұрын
I use dish soap water paint brushes and spray bottle, the leak detector gives me a general idea of the leak is.
@SovereignTroll
@SovereignTroll Жыл бұрын
I was told dish liquids (Dawn, Joy, etc) have lye in them and are corrosive to copper. Use an approved something if you don't want to pay for Big Blue etc.. Also chlorine sterilizer in condensate drains can attack furnace parts, use vinegar. Yet in reach-ins salad dressings and tomato products seem to eat coils. Who is right?
@user-cb4qd5fc1x
@user-cb4qd5fc1x 3 ай бұрын
😮 damn mans a pro
@zairuscanales
@zairuscanales Жыл бұрын
Hi! Thank you for this very informative video. I’m your new subscriber. Can I ask you a question regarding our AC unit? We just bought a house and unfortunately the AC is not cooling the room. The AC Unit is manufactured in 2006 (very old). And it’s definitely leaking refrigerant. The technician that checked the unit suggested to add refrigerant and check for leaks 1 or 2 weeks after. Is that okay? Or should I insist to find the leak first? I would really appreciate your advise. Thank you on everything that you do!
@TaddyDigest
@TaddyDigest Жыл бұрын
I would go ahead and let him add refrigerant because you need to know exactly how low it is Sometimes, it's hard to find the leak unless the refrigerant is significantly low, so it's good to know how low the refrigerant is before you schedule a leak check
@victork3397
@victork3397 Жыл бұрын
My company likes to use fluorescent trace dye for leak searches. And those require a return visit for Leah search after the dye has been circulating for a few weeks. Maybe that’s what the tech was referring to?
@chada472
@chada472 11 ай бұрын
If its a heat pump you have high pressure on the indoor coil when its heating right?
@TaddyDigest
@TaddyDigest 11 ай бұрын
yes
@jerrysinclair423
@jerrysinclair423 2 ай бұрын
I’ve been using the same leak detector. Had to replace the battery and sensor. Other than that, it’s been a great detector! I’ve also use a H10. A little expensive but what isnt these days?!
@maryschultz645
@maryschultz645 29 күн бұрын
just got a quote for r22 refrigerant at 3 lbs it was over $900 that sounds pretty steep
@TaddyDigest
@TaddyDigest 28 күн бұрын
Dang that is so expensive
@maryschultz645
@maryschultz645 28 күн бұрын
glad i held off especially when theirs apparently a severe leak
@lonestaryall2501
@lonestaryall2501 11 ай бұрын
Mice?? Yuck!! Great job on this system by you!!
@stephwaylonwells3218
@stephwaylonwells3218 Жыл бұрын
👍
@rawimpact
@rawimpact 10 ай бұрын
I just jb welded a leak
@tomasavilla1175
@tomasavilla1175 11 ай бұрын
My unit froze up the lines are copper so I turned the unit off so it can thaw from the big ice block so would that problem be from having a leak in the system? Thanks in advance
@TaddyDigest
@TaddyDigest 11 ай бұрын
Could be from leaking refrigerant. Could be from a dirty filter. Could be from low air flow. Just use a process of elimination to figure out.
@alfonsobenitez8574
@alfonsobenitez8574 10 ай бұрын
Best gor the customer to get a completely change out.
@tonyrandall6261
@tonyrandall6261 Жыл бұрын
Homeowner must have picked the platinum package, all that he took loose
@KTK_Rockstar
@KTK_Rockstar 10 ай бұрын
At what point do you recommend replacing the condenser and evap coil vs just the evap?
@wow1022
@wow1022 3 ай бұрын
the 3 blind mice met their doom 😂
@robertsneed7689
@robertsneed7689 11 ай бұрын
Can I use shampoo as well? Thanks for sharing.
@TaddyDigest
@TaddyDigest 11 ай бұрын
I'm not sure
@VooDooWarrior01
@VooDooWarrior01 10 ай бұрын
Guys here tried to charge me over $1500 just to put $75 leak sealant in, so I got my 608 very and work on my system myself.
@user-tt3dv6sw2f
@user-tt3dv6sw2f 11 ай бұрын
Can an overcharging the system cause the TXV to get stuck closed?
@TaddyDigest
@TaddyDigest 11 ай бұрын
Overcharging will definitely to stay closed
@user-tt3dv6sw2f
@user-tt3dv6sw2f 11 ай бұрын
@@TaddyDigest Thanks for that, the tech told me that the TXV is bad and he need to install a new coil, the system is 3-year-old. I took an image of his 4 port manifold + Micron gauge where it showed the following, on the left side, a pressure of 96.3 Psig below it is 39.1 SH, and below it is 29.5 VSAT. On the right side it shows pressure of 278.8 Psig, 16.8 SC, and below it 90.7 LSAT. I would very much appreciate your thoughts on this
@TaddyDigest
@TaddyDigest 11 ай бұрын
Yeah it looks Like there is too much liquid in The condenser And not Enough Liquid In the evaporator so definitely could be the filter dryer for the t x v
@jorgee910
@jorgee910 Жыл бұрын
D-tek 3
@user-ni2gf8gb9x
@user-ni2gf8gb9x 4 ай бұрын
Hay Taddy, Got an unrelated Question, sorry to post on your video. I went to a Goodman PKG HP the other day with Compressor not starting. I could hear it trying like a dead CAP. Checked the CAP (70x5 duel) it was 4.7 on fan and 311 on Herm!! 311/5 wow. Cap was 1.5 yrs old. I replaced it and system began to run. Was pulling 15.5 amps at start then 10 minutes in I noticed it had risen to 18 then ten minutes latter it was near 20. The RLA is 26. I traced the wires and found nothing mis wired to the cap so I called it the Compressor and recommended the Comp. I did not find any strange readings when I did OHM the comp tho before I restarted with the new CAP. Have you seen this before? It is a new one on me.
@TaddyDigest
@TaddyDigest 4 ай бұрын
Is it a 2 stage compressor was it going into high stage? And that's why it pulled more amps Or is it just single speed
@user-ni2gf8gb9x
@user-ni2gf8gb9x 4 ай бұрын
@@TaddyDigest Single speed
@anthonybernier9952
@anthonybernier9952 2 ай бұрын
The capacitor can read higher but if you look at your meter its nano farads so its actually lower.
@anthonybernier9952
@anthonybernier9952 2 ай бұрын
kzbin.info/www/bejne/mYu4oXZ7l66Fpdksi=v8283FCc_UPzLQoh
@miguelarevalo6400
@miguelarevalo6400 Ай бұрын
H10 pro by Bacharach
@KTK_Rockstar
@KTK_Rockstar 10 ай бұрын
Just curious what your thoughts are on UV dye and leak checking that way
@Gabe-bz9nk
@Gabe-bz9nk Жыл бұрын
The only thing that you forgot to do is that when ever you do any sort of testing over 100 lbs of nitrogen you tell EVERYONE AROUND that place that you are performing a high pressure test and that it would be better if they stayed away from the copper pipe. God forbid if it had a bad joint and it exploded it could hurt someone
@MrDeviousdom
@MrDeviousdom Жыл бұрын
🤣
@donaldallen743
@donaldallen743 Жыл бұрын
@MrDeviousdom please explain. I had a bad leak years ago, but luckily it was in the crawlspace. It couldn't keep the nitrogen in at 350 psi. It would've scared a customer but it did not came apart
@MrDeviousdom
@MrDeviousdom Жыл бұрын
What pressure do you think that the refrigerant piping normally has in it? Is it over 100 PSI? That's why I'm laughing
@5822huron
@5822huron Жыл бұрын
Not true. Smh
@MrDeviousdom
@MrDeviousdom Жыл бұрын
@@5822huron Tell us what's not true.
@johnjmacejak
@johnjmacejak 10 ай бұрын
Send the mice patrol to sniff out leaks …
@jesusnavarrete9213
@jesusnavarrete9213 Ай бұрын
Can I put pressure in my condenser
@TaddyDigest
@TaddyDigest Ай бұрын
What do you mean
@christianlara9918
@christianlara9918 Жыл бұрын
I have used multiple bacharach h10s and various other refrigerant leak detectors. I have NEVER found a leak with any of them. I always find them with bubbles, sound, and oil spots. What leak detector do you use?
@chrismyers5758
@chrismyers5758 Жыл бұрын
I have never found a leak with bubbles only leak detectors
@MrDeviousdom
@MrDeviousdom Жыл бұрын
That makes absolutely no sense as the h10 picks up leaks that are so small they don't even create bubbles. You might want to revisit your technique and or have the equipment checked. The H10 includes a calibration vial of R11. Make sure it's calibrated properly.
@donaldallen743
@donaldallen743 Жыл бұрын
I've found some leaks with the NAVAC.
@OcRefrigeration
@OcRefrigeration Жыл бұрын
@ Christian lara Ive been doing Leak detection with a Ge H-10G Leak detector for 42 Years & it WILL Get you Right to a leak EVERYTIME. THE Problem is With YOUR Leak detector or YOUR Technique Period ! Basics of Leak detection with a Ge/Bacarach H10G Leak detector. 1) Plug detector in. 2) turn on. 3) set switch to Medium. Turn dial left until no clicks are heard during warm up. 4) Let detector warm up for 5 Minutes on the clock. Then adjust dial till clicks are heard every 1 second. 5) bring probe tip across top of Sample bottle & hold for 1 second. Leak detector should scream loudly. If not. Set Switch to SMALL. Adjust dial to clicks ever 1 second. Try again. Wave probe tip over sample bottle / reference leak detector test bottle included in every ge H10 leak detector. It should scream loudly & Red led should be flashing madly. IF Not Leak detector NEEDS Adjusted / Sent in for Service. If Leak detector works / Tests out good Here is Basic technique of Leak detection - 1) System Must Have 25 Psi of Refrigerant in it Min. Then - 2) Add 150 psi of Dry Nitrogen to System being checked. 3) Test that both Sides of the System have a Min Pressure of 100 -150 Psig in the System. 4) Allways check that Leak detector works before starting leak detection procedure with test vial or at refrigerant tank briefly. Once detector is known functional then & only then can leak detection start. 5) Start with Ge H10 Leak detector in Medium position , set click rate of 1 click per second & Bring leak detector Near Evaporator or Condenser. To check for leaks. 6) the H10 is designed to be moved across an area at a Rate of 1” per second. 7) DO NOT LET IT SUCK UP WATER / Keep it away from water. It is a Pump that WILL SUCK up water and it will instantly Junk out the Leak detector. 8) if you get the probe tip wet - Change the white probe tip filter with the filters provided. 9) Remove plastic probe tip & dry out with paper towel or rag. 10) Replace Red Floating ball 🏀 that is in Probe Plastic tip. ( it shows you that Pump is sucking air ) 11) install New dry white Filter into probe tip. 12) install Rubber tip on probe & start again. 13) Warm up Detector, set to medium, Keep probe tip moving at a rate of 1” per second & try to keep it away from water & soap bubbles. Keep approx 1-2” away from wet surfaces. This should get u started.
@maryschultz645
@maryschultz645 29 күн бұрын
joined
@TaddyDigest
@TaddyDigest 28 күн бұрын
Hey, mary, I do not see where you joined
@tomoliver8498
@tomoliver8498 Жыл бұрын
You should be able to wet your bare hand and feel for the leak better
@OcRefrigeration
@OcRefrigeration Жыл бұрын
Yea, spray some soap bubbles on it. You can feel bubbles with your fingers really easily & it makes bubbles when you pass over the leak with your fingers.
@patrickvillegas3885
@patrickvillegas3885 15 күн бұрын
Ultrasonic is a lot easier,
@Chunkylifehealthyfuture
@Chunkylifehealthyfuture 10 ай бұрын
I have that noise coming out of my central vent when the AC is off. Does anyone know what's wrong with my AC? It works fine. Just that sound is lingering after it's off.
@hhn2002
@hhn2002 9 ай бұрын
I’m not professional but just a guess it maybe the high and low side pressures equalizing which would be a normal thing.
@MrDeviousdom
@MrDeviousdom Жыл бұрын
H10, The only leak detector worth a damn.
@TaddyDigest
@TaddyDigest Жыл бұрын
Okay I will check that 1 out
@OcRefrigeration
@OcRefrigeration Жыл бұрын
I second that. H-10 Ftw. Only leak detector worth its weight in gold.
@chrisparkinson9237
@chrisparkinson9237 Жыл бұрын
I have the Accutrak vpe-1000 and Fieldpiece DR82 can't fault the pair of them, finding leaks that others can't in minutes.
@mrpatter19888
@mrpatter19888 11 ай бұрын
All you people thinking 500 psi destroyed that coil on a heatpump? No way, someone runs heat on a warming day what do you think it’s seeing?
@scottygenao2051
@scottygenao2051 10 ай бұрын
You only put the max on what the system tells you #tag . Especially if you putting nitro on the low side if low side says max250psi you put 250psi
@gabooda2380
@gabooda2380 9 ай бұрын
there is no way to only put nitrogen in the low side unless you would disconnect the coil. But yeah, the coil clearly states design pressure and R22 is very low pressure. I thought last one I saw was 150 on the R22 coil and 450 on 410a coil.
@virgilsmith5792
@virgilsmith5792 16 күн бұрын
an automotive stethoscope would easily let you hear exactly where it was coming from.
@JC-sc9rx
@JC-sc9rx 22 күн бұрын
one might even say that you have found 3 blind mice. Haha hahaha ahahahahahahhahahahahhahahahahahahahaha
@TaddyDigest
@TaddyDigest 22 күн бұрын
😄 🤣 😂
@slickpulla865
@slickpulla865 22 күн бұрын
Joined
@TaddyDigest
@TaddyDigest 22 күн бұрын
Excellent thank you for Joining and being a member Here is my email tadfuller1@gmail.com
@MartinLDeLoach903
@MartinLDeLoach903 Жыл бұрын
You don't have to buy that expensive bubbles, dawn soap and warm water in a spray bottle does Exactly the same trick
@MartinLDeLoach903
@MartinLDeLoach903 Жыл бұрын
Very little dawn soap..
@Lew114
@Lew114 11 ай бұрын
My takeaway is to let the technician do a leak check even if it costs more up front. I’ll bet it saves money more often than not.
@TaddyDigest
@TaddyDigest 11 ай бұрын
Absolutely
@s0uth5tar
@s0uth5tar 9 ай бұрын
How much does a nitrogen test cost?
@s0uth5tar
@s0uth5tar 9 ай бұрын
Because I think I need that test done at my house
Leak Search Tips From Bert
17:50
HVAC School
Рет қаралды 65 М.
Goodman Heat Pump Low On Refrigerant!  Adding Leak Stop And Charging With R-410a!
12:43
Normal vs Smokers !! 😱😱😱
00:12
Tibo InShape
Рет қаралды 117 МЛН
狼来了的故事你们听过吗?#天使 #小丑 #超人不会飞
00:42
超人不会飞
Рет қаралды 53 МЛН
🍟Best French Fries Homemade #cooking #shorts
00:42
BANKII
Рет қаралды 13 МЛН
когда достали одноклассники!
00:49
БРУНО
Рет қаралды 2,4 МЛН
Top 5 Things AC Companies Don't Want You To Know How To Do!
12:40
How To Home
Рет қаралды 2 МЛН
STOP Buying This HVAC Brand
9:38
The DIY HVAC Guy
Рет қаралды 196 М.
how to service your HVAC drain lines
3:51
Remodeling Wizards of Maryland
Рет қаралды 18 М.
How to replace the AC units leaking condenser coil?
34:42
Taddy Digest
Рет қаралды 5 М.
How to use Easy Seal Ultimate Leak Sealant/UV Dye? @1NuCalgon
14:09
How To Add Refrigerant To Air Conditioner
22:08
Word of Advice TV
Рет қаралды 1,6 МЛН
3 Things HVAC Contractors Don't Want You To Know About.
13:17
The DIY HVAC Guy
Рет қаралды 2 МЛН
Low Refrigerant? Freon Leak? Check This First!