I attended a service call due to a battery low (voltage) fault. What is the reason and solution to fix the problem?
Пікірлер: 29
@niloyu1052 жыл бұрын
Watching from Al Khafji Saudi Arabia
@simonegelormino32772 жыл бұрын
Nice work Elmer! I rwally enjoy your videos!Waiting for a video on fault finding for common faults found on Ewis panels, wip phones, break glass, speaker line etc😉
@niloyu1052 жыл бұрын
😂😂😂 masipag Ngayon ang Ads start and end video 20sec. Completed support Filipino Vlogger especially Ads 😂😂😂
@maskarangvlogger7196 Жыл бұрын
Bago nyo pong taga suporta sir.
@o_z_b10 ай бұрын
Thank you so much for this video
@niloyu1052 жыл бұрын
Welcome back hehe! Watching from Al Khafji Saudi Arabia
@fireprotectionguy79432 жыл бұрын
My PC Motherboard was off. Under warranty, so I sent it back to the supplier. I can not wait for the repair so I bought another PC. Thnxs Ingat.
@roderickbalolong67952 ай бұрын
Hi Sir. Elmer, maybe during the design stage the magnetic lock current was not included in the battery calculation.
@fireprotectionguy7943Ай бұрын
True. But magnets must not be included in the normal power supply of the fire system. It should have it's separate power supply. Either with back-up batteries or not.
@niloyu1052 жыл бұрын
Ah! Naka panood din ako Ads 😂😂😂 30sec. Ads completed keep watching and support from Al Khafji Saudi Arabia...
@fireprotectionguy79432 жыл бұрын
Daya...pinagkakakitaan na nila ang video ko.
@niloyu1052 жыл бұрын
@@fireprotectionguy7943 Hehehe! Oks lang yun Sir Elmer alam ko naman po naglilibang ka nalang sa buhay 😂😂😂
@fireprotectionguy79432 жыл бұрын
@@niloyu105 ... tama ka dyan...dadagdag lang sa tax na babayaran ko yan.
@ericchoi16107 ай бұрын
thank you for the video. How did you find a magnet door was the problem? is it common failure or based on your experience? if you didn't know, how would you troubleshoot in general?
@fireprotectionguy79436 ай бұрын
Fire system auto battery test once a day (old system) or once a week (new model). For old system, it's an hour test. Any magnet or external power devices cause the battery to depleted earlier. In this site, it's only the magnet that causing it. From the day I introduced a new power source for the magnet, the problem never re-occur.
@workonmyranger6336 Жыл бұрын
I like your videos
@fireprotectionguy7943 Жыл бұрын
Thank you.
@carlh42792 жыл бұрын
For sure the magnets should have a dedicated power supply.
@stevehunter532 Жыл бұрын
Does the system need to be shut down to replace the batteries? Or can be done while running on mains power?
@fireprotectionguy7943 Жыл бұрын
No need to shutdown. Power should always be ON.
@maskarangvlogger7196 Жыл бұрын
Bagong palit din po ang battery naun eh..slamat po advance
@francisaguinaldo96810 ай бұрын
Hi! How to fix psu fault in zeta primier quatro? Thanks
@fireprotectionguy794310 ай бұрын
I am not familiar with zeta. But the trick is all fire supply fault are the same - Battery Missing, Battery Fault, Blown Fuse, Battey Flat ( just replace it!), Low Battery Voltage, No Power Output or Input, Output voltage is too low ( Normally output is between 26.1 - 27.4 volts DC). Good Luck
@maskarangvlogger7196 Жыл бұрын
Sir,itanong ko Lang po Kung ano dahilan nang battery deplited?simplex po addressable
@fireprotectionguy7943 Жыл бұрын
Flat batteries. Mostly cause of system that is running on batteries most of the time due to power blackout. Once a battery reached it's low voltage threshold - it's hard to charge using the fire alarm system battery charger. Best to charge it using an external charger. Another is, the system is in auto battery test every day. Once a week is okay for 30 mins only based on program setting. If it failed in 30 mins, your system requirement is bigger than the battery can supply. That's the time you sort out which equipment should not be included in the normal battery test and should be separated from the fire system. These are magnet door holders mostly.
@crisdeorbz8986 Жыл бұрын
Good day sir may video po ba kayo procedure replace battery ng consilium fire alarm panel?
@fireprotectionguy7943 Жыл бұрын
Replacing batteries are very basic. When replacing, make sure you have your normal power "ON". Once you removed one terminal, it will fault buzz and just acknowledge it to clear the noise. Just do make sure you got the correct polarity.
@crisdeorbz8986 Жыл бұрын
@@fireprotectionguy7943 ok sir no need to switch off the main power, only disconnect the battery wire
@fireprotectionguy7943 Жыл бұрын
@@crisdeorbz8986 ..correct. Never remove a battery with MAIN POWER OFF cause your battery is the back-up power source.