Bruh, 8:00 is the cleanest wirenut "redo" I've ever seen. I've never thought about unwinding the original wires like that. Although I'm a DIY person, not a certified electrician my mom was an electrician for 30 years and taught me a lot. Love your videos, keep 'em coming.
@conniesue89572 ай бұрын
Thank you so very much! My daughter and our roommate are constantly leaving the fan on, and it's driving me insane! Not to mention what it's doing to my electric bill. I know what I am doing next weekend while they are both at work! 😉😅👍❤
@richardcranium58394 жыл бұрын
run the fan exhaust into his room he'll remember to turn it off lol
@ElectricianU4 жыл бұрын
aaaahhhahahaha that's an outstanding suggestion! hahaha
@sylvesterstewart8684 жыл бұрын
@@ElectricianU What are your thoughts on wagos? Really enjoyed your transformer video, thanks.
@JasonW.4 жыл бұрын
@@sylvesterstewart868 I like and use the lever ones. Cost more, but a big time saver and easy to change things later. I've seen too many wire nuts loose.
@sylvesterstewart8684 жыл бұрын
@@JasonW.I Was taught to make a mechanical connection by twisting the wire and the wire nut just insulates the connection. I have some I've used for temporarily connecting this solar panel set up I have. It seems like they could be good for where you might not want to risk breaking old wires by twisting them.
@JasonW.4 жыл бұрын
@@sylvesterstewart868 The loose ones I've seen are where the wires were not twisted, and the wire nut was all that was holding things together. Wire insulation was usually blackened/charred close to the nut.
@saab2fast3 жыл бұрын
😂 The power was still on @ 13:05 for a split second... I appreciate all the info man it’s helping me a lot in my class in Killeen. Thank You
@saycheese18323 жыл бұрын
I noticed that too. 😂
@brucegotohell13233 жыл бұрын
Hi, Even better than a timer, the DewStop moisture sensing switch is fully automatic AND has an adjustable timer (settable between 3 and 15 minutes) function when you need to run it manually. Since the switch is being replaced anyway, this is the best approach. I installed one several years ago and love having it run as long as I'm in the shower and then it will turn off automatically when the humidity is low enough. On a different note, I've implemented the Lutron Caseta system, including the bathroom light switch, anytime I leave the house, all the lights, including the bathroom light, go off. The system is also programmed to turn off all lights (not including the bedrooms) at midnight. All switches are dimmers, so I'm not blinding myself when I need the bathroom late at night. Wish you well with your videos. Bruce
@jec6613 Жыл бұрын
There are a few of them around, I use a similar Leviton product that has an even longer timer range, and will also run periodically - say 5 minutes every hour, great if you're venting a litterbox.
@rostrander724 жыл бұрын
It's my life, it's my house, judge away, fuck off...words to live by 😂😂😂 Also, I love the fact you have the screw holes up and down. Thanks for the upload, keep'em coming.
@JasonW.4 жыл бұрын
I prefer screw holes up/down. They collect dust when sideways and show how little I dust my outlets.
@colinstu4 жыл бұрын
Very interesting to know about the metal tabs used for heat dissipation. I’ve always taken the minimum off, but never realized the purpose behind that. Maybe not quite as important with LED lighting, but great to know.
@colinstu4 жыл бұрын
@@boogermeats those will get warmer the more watts they need to dim down, and the metal acts as a heatsink. Remove some of the metal, the thermal capacity won't be the same and may get too warm while dimming high watt loads. It makes sense to me.
@colinstu4 жыл бұрын
@@boogermeats I would presume the documentation that comes with these lists how much derating happens per piece of metal removed. Would be best to see what the manufacturer says.
@XionAzura13 жыл бұрын
I did this in my house after watching this video (I’m an apprentice electrician in TX). It works great!
@justintimeelectric39564 жыл бұрын
Great video! It is aggravating when those before you don’t leave enough wire. I appreciated the fun fact about copper clad aluminum and about how removing the tabs decreases the rating.
@MikeBramm4 жыл бұрын
When you put the cover plate on, you can see the green LED next to the "ON' label is illuminated (you can see it better at 16:38). Why is it on already? Was the power not turned off, or does this device have a battery-backup to maintain the setting if the power goes out?
@jroy3754 жыл бұрын
Power was definitely on. At 13:03 he hits the switch and the light comes on momentarily.
@BonzaiMotionPictures4 жыл бұрын
I didn't realize those tabs dissipate heat. Thanks for the info. Great video! We put these in all our bathrooms when we wired our house.
@marcberm4 жыл бұрын
Great video as always! I just put in something like this a few months back, except I went with a Leviton IPHS5-1LW since my problem is more people forgetting to turn it ON when getting in the shower. It turns on/off at a button press, for 30 minutes of runtime, then auto off. It will also turn on when above spec humidity and until spec is reached. Humidity sensitivity and runtime are configurable with dials under the cover so there are options and still a neat and simple operation.
@marcberm4 жыл бұрын
I also get great satisfaction from cleaning up a janky junction box when I change or upgrade a switch or receptacle. And yeah... It's nice to just be able to turn the fan on and let it automatically "courtesy vent" after you leave without having to remember to come back and turn it off later. 🤣
@jonathan35183 жыл бұрын
Finally got a good answer in why a timer is code required, at least here. Fire code requires it due to a rash of attic fires from old fans running endlessly
@nick57382 ай бұрын
Excellent! Thanks for grate explanation of operating! 👌🔊🤝
@kristiandawe852 жыл бұрын
he did it all with the power on ☺
@rothandre64973 жыл бұрын
The electrician I worked with told me, just because something can be done (from code) doesn't mean it should be done. Since we worked in a retirement home, switches and outlets were constantly going bad or getting destroyed and would need to be replaced often. As such, we never stripped a mid conductor to create a connecting point. Reason was that exposed hot could accidently get jumped from someone working in the box. It's safer to run a separate pigtail to each switch instead of having that unnecessary exposed conductor.
@johnstancliff73284 жыл бұрын
this was 1 item I added when I bought my house, when upgrading the electrical, I added the 30 minute keywound switch in all the bathrooms.great idea! and now its taken care of....
@tonydyer50732 жыл бұрын
I’ve been watching your videos for awhile now and I have to tell you Dustin that your contents are getting better and better. Good job.
@Mandalawi1987 Жыл бұрын
Loved this video! Dustin my dude, this channel is the reason I'm becoming an electrician. YOU ROCK.
@Edgardocelectric0073 жыл бұрын
I just installed a fan unit with build in moisture sensor in conjunction with timer so unit turns on automatically while taking a shower or in some cases were some bathrooms have washer dryer unit works great
@lightsoutlamp2 жыл бұрын
I have a Panasonic FV-0511VQ1. Have you ever had issues with these timers not work with certain bath fans? I see the bath fan slowly startup and then shut off on its own before the timer expires. Changing the timer to the always on setting does not remedy the situation. Thanks.
@BenRush2 жыл бұрын
I feel like it'd be insanely educational to watch you put in a subpanel, and discuss the code behind all your choices. I recognize you're super busy, but if there's ever an opportunity for you to do that and record it, it'd be the absolute best one on KZbin.
@VanquishAudio Жыл бұрын
So the switches in this bathroom are a vertical unit ie there’s 2 switches with one on top of the other and they flip left and right to turn on and off. I’m sure you’re familiar with this as an electrician.. so what do you recommend I do for that situation? PLEASE! 🙏
@gatsbylight4766 Жыл бұрын
In fairness, there are times.... like when you eat *White Castle* for example... that you do *_need_* to leave that bathroom fan running for *8 to 10 hours* (12 hours if that burger had cheese). Commenting for a friend.
@glennjones5962 жыл бұрын
Even though, I was looking for another timer, I was so entertained, I kept watching. Great job keeping us laughing. I am looking for a timer, that I can plug in my big fan, so it can dry out my shower, then turn off after 1 1/2 hours. I figured, I would plug a timer in the outlet, plug my big fan into the timer, and have a remote control mounted next to my shower. Any thoughts on this? Thanks, Glenn
@RobertLeBlancPhoto3 жыл бұрын
I'll be doing this soon for all three of the bathrooms in my house. I'll be using Wagos. Love em.
@Mixiter554 жыл бұрын
If you loose power does the switch default back to on? Kick the breaker off wait and min and kick it back on. Wondering if you will have to re-program after.
@DrN0073 ай бұрын
In regards to copper cladding you mentioned, a wire could even be hollow w/o loss of conductivity due to AC skin effect.
@MikeA-lo9xu Жыл бұрын
Random question I have 3 different porch lights in 3 different places around the perimeter of the house is it possble to connect all 3 porch lights to 1 timer or does each 1 need a seperate timer switch??
@ichoo5048 Жыл бұрын
I have a bathroom fan controlled by 2 x 3 way switches. One in the bathroom and the other on the lower floor to use the same fan as an exhaust for kitchen fumes. (Open concept floor). How do I install a timer in the bathroom? Cannot find a 3 way timer switch.
@AlexMartinez-dc4pe4 жыл бұрын
Great video like always. I just went with motion sensors, so I don't have to even touch them.
@ElectricianU4 жыл бұрын
I've done that in the past too, but sometimes you have some extra stink and need to keep that thing on for a long time lol - I guess a lot of motion sensors let you program time delays though too. Solid option, you're right
@andypop1232 жыл бұрын
Is there a bathroom timer like this with a remote switch? Re 1 central fan pulling from 2 locations. Ty
@willy2mil11 ай бұрын
Can you still turn the vents when the light switch it’s Off or when the dimmer it’s at low or half way? My Fan doesn’t come on until my light switch dimmer is at high or at On position.
@gitsoakville2 жыл бұрын
Good to know this model of timer exists that doesn't require a neutral wire. Thanks.
@daddio14912 жыл бұрын
I have the same issues with my daughters. I like this idea but will this timer work with a fan with a single bulb heat lamp combo?
@swamp3r3 жыл бұрын
The model in your vid is MA-T51-WH (60 minutes). Your description is linking to the Lutron MA-T530GHW-WH (30 minutes). Thx for the install tips!
@pepsifan85043 жыл бұрын
When was your house built our house was built in 1996 and they never connected ground wires to the light switches
@thebnbaldwin2 жыл бұрын
I've got a Klein tracer that works well but, the thing is too thick to insert it into an outlet. What's up with that?
@maple_syrup_boy_11754 жыл бұрын
Why do U have 20 amp breaker but you have 14 2 wire I thought you use 15 amp break for 14 gauge
@battlegalaxy32464 жыл бұрын
I think that was stock footage meant to highlight shutting off the breaker first. But, you’re right about the 20amp/12ga relationship.
@victorbirukov32434 жыл бұрын
@@boogermeats Good point! Was wondering the same thing. I think Battle is right about the footage highlighting the shutoff.
@tjguidry49893 жыл бұрын
Yes if you watch at 13:00 you realize the power is actually still on.
@samwee62 жыл бұрын
Is this good to auto off for a room Air Condition unit?
@thebnbaldwin2 жыл бұрын
What's the deal with the intermittent timed exhaust fans I'm seeing in some new houses?
@VanquishAudio Жыл бұрын
This is exactly my problem. 👏👏👏👏
@explorster2 жыл бұрын
Good job Brad 👏 👍 👌
@JasonW.4 жыл бұрын
I see your drywall guys also love giving texture to the wires.
@JeDeanT3 жыл бұрын
LEARNED A LOT MAN GREAT INSTRUCTION FOR A HOME OWNER
@matthewoles79714 жыл бұрын
@8:05 that was butter Marine!
@illestofdemall134 жыл бұрын
I have seen old neutral pigtails from the 1950s where they left one leg long, skinned a section and twisted it with the other neutrals. Then they soldered it and covered with friction tape.
@kevinpoore56264 жыл бұрын
That sounds old school and ugly and most likely there is no Earth conductor involved LOL :-) :-) don't stick a fork in it or you will be done
@illestofdemall134 жыл бұрын
@@kevinpoore5626 Sometimes there is a thin ground wire to the back of the box.
@kevinpoore56264 жыл бұрын
Yeah if that's what you want to call that but sometimes very rare and if it is there it's so short it does no good lol :-) :-)
@illestofdemall134 жыл бұрын
@@kevinpoore5626 It can possibly clear a ground fault if the hot wire in the metal box happens to become exposed and touches the box. Better than nothing at all if the box is metal.
@ElectricianU4 жыл бұрын
me too lol
@rmok27743 жыл бұрын
In residential, how many 14/2 can fit through a 3/4” hole in joist? I understand the hole is not allow to > than 1/3 of the size of the joist and stay 2” away from the sides. Please help
@bgarrison672 жыл бұрын
Hole has to be 1 1/4" from the edge. We run no more than 3 14-2 through a 7/8"s hole if the circuit is on an arc fault breaker and up to 5 14-2 on a standard breaker.
@kevinswan83904 жыл бұрын
Great video.. I was just telling the wife to start turning off the fan!!
@ElectricianU4 жыл бұрын
Mine always left the garage lights on because the washer/dryer were in there. Annoyed the shit out of me, so I put an occupancy sensor in there...problem solved.
@calmeilles4 жыл бұрын
We don't find separate fan switches very often over this side of the Atlantic, usually only very old or very poorly retro-fitted installations. More common is having the fan on the light-switch with a delay timer cut-off. Switch the light on, the fan comes on. Switch the light off and the fan stays on for anything from 5 up to 30 minutes afterwards. The good parts are that the fans always come on when the bathroom is in use (unless you do your business in the dark) and there's no permanently on option. The bad part is that this does no good if the kid also leaves the light on all the time!
@devinclose16004 жыл бұрын
Ayyyy! Appreciate you making this Dustin! You're the best
@Manny17NJ4 жыл бұрын
Are you experiencing access issues on your website? Cannot log in to the practice exam I bought late December. Also, I am unable to reach out to you through your regular contact methods for assistance.
@dandacosta89252 жыл бұрын
Hey great video but get yourself a voltclaw to push those wires back into the box. Also to get the plate lined up and level stick it on backwards and put a level on it. Finally turn off the power unless you like buying $30 timers that blow up when you push them in.(I usually tape up the timer it it has exposed screws)
@juanlara41274 жыл бұрын
Good job Dustin I liked this and I think you’ve improved since the boot review
@calvert48 Жыл бұрын
Great tutorial!
@rickturner81893 жыл бұрын
Do you know of a timer switch that gives you the option of constant power (no timer) as well as timed? My wife likes to run the fan as a white noise sound while going to sleep and needs to run for a long period of time.
@bgarrison672 жыл бұрын
You can use it manually as well as timed
@camerondierking76443 жыл бұрын
So, since you mention DIY, I do electrical work professionally, but in RVs. I am wanting to become a certified/licensed electrician. The catch, I’ve recently gone into business for/with myself, and don’t have time for an apprenticeship. Do you know any way to get certified/licensed without an apprenticeship? I will only be doing electrical work the pertains to RVs, such as hooking up 50 amp service plugs at peoples homes for their RV.
@CalgaryBen4 жыл бұрын
Even better than a timer is a humidity sensor switch. Leviton makes one (PN IPHS5-742-0LW) which works well. Simplifies use by removing an actual duration selection (thereby removing the decision from my kids), but allows manual turning on with a single button, or automatic turning on of fan when humidity rises (no longer need to yell at my kids to turn on the fan when they take a shower!). I've replaced all my digital timer switches with the humidity sensing switch, which should just be a code requirement because of its benefits.
@calebmorand46044 жыл бұрын
I have a question. Are 10ka 120 or 240 volt circuit breakers ok in residential installations? Thank you.
@calebmorand46044 жыл бұрын
@@boogermeats ok thank you.
@mistersir70553 жыл бұрын
Thanks for the vid. Like the comment about the tabs you broke off. Would've liked a mention about what happens, what do it mean... great vid over all 👍 👍 thank you.
@Cablesmith4 жыл бұрын
Very interesting, so so much different than what I’m used to ! Nice work bro
@rossroyce22584 жыл бұрын
where did you get that shelving cube from start of video?
@judeshellito22693 жыл бұрын
I installed this very switch and it just flashed. Instructions noted the load is either to small or to big. Is there another timer switch that might work.
@hyagosilveira9872 жыл бұрын
What’s the difference between these timer switches vs the Intermatic timer switches? Can they both be used for pools ?
@mikell30874 жыл бұрын
"Turn the power back on" me like the power was on the whole time lol
@josesanchez-cr3jm4 жыл бұрын
🤣🤣
@marksmith65324 жыл бұрын
Exactly!! You can turn it off ?? Lol
@BeerkegGarage4 жыл бұрын
Thank you for the upload
@ElectricianU4 жыл бұрын
I did it for you my dude
@jonathancampos7424 жыл бұрын
Do you have a video on how to get started as a electrician? This is something I want to get into but I just don’t know where to go
@sethmorton63724 жыл бұрын
Look through his channel, generally for most places you must be licensed to do commercial and industrial, but you may work under someone for residential, call around to your local chain and individual residential electrician services and ask if they could use help and are willing to train. It’s usually that easy and since it’s a construction job for the most part unless you do service calls, you may not even need to do an application. Good luck.
@ElectricianU4 жыл бұрын
I do, check out my other channel Journey 2 Master - there's a ton of perspective type videos that I top about topics like that
@joesaladino5284 жыл бұрын
I’m new too, I went the trade school route and just finished last month. I just started calling a bunch of companies in my area after I graduated and I start next week
@markchidester62394 жыл бұрын
15 min is fine to destink the room! Interesting about the heat sink on the switch. Speaking of heat, I just learned that there is code for thermal expansion of pvc conduit and an expansion coupling to handle this. Made me think of the wire in the conduit. I'm running 1 1/2 PVC 90 feet to a subpannel. Using 2-2-2-4 aluminum wire. The PVC will expand and contract about 3" in a 100degree temp change. What about the wire? Can't find anything on this, but it will expand with the temperature changes. Would it be a good idea to put a pull box in the middle and loop the wire in a circle to make room for the expansion and contraction? Also, a video on different types of wire would be cool. I learned a lot looking for what type of wire to use for this.
@Melmin447 Жыл бұрын
Great video! I have two questions out of curiosity: 1. Can you give me a ballpark estimate what an electrician would charge to do something like this? 2. What does it mean that the wattage rating will go down if you need to clip those tabs off...is that a safety concern? Thanks!
@Geosstatus4 жыл бұрын
Love these vids. Thanks!
@jimholloway17854 жыл бұрын
I am new to your channel and I am learning as much as I can on switches and such and learning from others(like yourself), I was curious why you use regular twist connectors and not Wago connectors?
@katoertli39643 жыл бұрын
I feel this in my soul, thank you for the solution
@colinstu4 жыл бұрын
Or change out the fan with one of those humidity-sensing ones. Ours was super old and noisy and barely moved air anyways. Replaced with a model that was quieter, higher CFM, Auto on with humidity (showering) and can manually trigger it on for 15 min with flicking it on-off-on quickly. Also was FORCED to do this since the switch controls the bathroom wall light as well, no extra switch leg in the box for just the fan. Yay old homes.
@Ozzie4Para3 жыл бұрын
"Judge away, fuck off". Too funny.... lol
@OthmanAlikhan3 жыл бұрын
Thanks for the video, very helpful =)
@TheWellnessLawyer3 жыл бұрын
How can you tell incoming from out going to the load?
@jimmyofbethesda3 жыл бұрын
Great video. Not only educational but also fun to watch. One question: is there supposed to be a neutral line? Or is that optional?
@ElectricianU3 жыл бұрын
Thanks for watching! Depends on if the equipment requires a neutral. (More often than not it does require one.)
@DanMashuda4 жыл бұрын
Awesome video!
@ElectricianU4 жыл бұрын
Thank you!
@19993gt3 жыл бұрын
Looks like this is my next home project
@felix45253 жыл бұрын
If power is off at the braker, why is the ON led flashing?
@antoniosilva83313 жыл бұрын
I love it. Thanks.
@jeremie25994 жыл бұрын
Hey Justine would you. Explain. tell us if someone wants to be an electrician what is the first step. Or just say an electrician helper. Do you want a diploma? We need a video for that subject pls big man thank very much
@stephenmayock37763 жыл бұрын
My bathroom fan is on two three-way switches five feet from each other. WTF were they thinking. There are also two doors to the room. How do I wire a timer switch to this mess.
@thedge74 жыл бұрын
Can I add a timer if there are 3 switches controlling one fan?
@coreysalo18094 жыл бұрын
Did you figure that circuit for a constant load?
@RichadTheLionHeat3 жыл бұрын
Right on! It’s your home. No one has any right to ridicule you on this website👍🏻😉.
@isabelstaples1983 жыл бұрын
Thank you, my exact setup to replace.
@Lone-Wolf874 жыл бұрын
"A clean freak" 😂😂😂😂😂😂😂😂😂😂😂😂😂😂😂
@garbo89623 жыл бұрын
Don't be a dope like me. When I had my bathroom remodeled I went to a.large supply house who told.me on the phone that they stock 2 different batroom fans with moisture senser to turn fan on. When I got there of course they were.out if stock and carpenter was sheet rocking ceiling & walls next morning so I had to purchase a regular ceiling fan but with a night & regular light. Turned power.off the next night and wired in a 10 20 30 &.60 second timer. Turned power back on and fan did not work. Of course as a sparky with over 40 years in the trade I don' t need to tead instructions. Pulled timer.out of wall to check that I had power. Da never moved very little slide switch to on position. Thanks for another informative vid.
@enigmamatrix3 жыл бұрын
What's he mean at 3:15 that DIY people shouldn't be doing electrical work? Does he mean electrical work isn't for DIY, or does he mean people shouldn't DIY if they aren't comfortable doing it, or does he mean something about NEC and permits, or... ?
@lou20323 жыл бұрын
i use a humidity sensor combined with timer totally auto but its $65 cdn ..:(
@RMHxgames3 жыл бұрын
"no bare copper passing the back of the device." I can hear the old mans voice now lmao
@MasterTheNEC4 жыл бұрын
Um...Copper Clad Aluminum isn't "dipped" in copper...LOL... it's metallurgically bonded from AA8000 Aluminium and a copper veneer. In fact, that bond has to take place prior to being drawn into appropriate conductor sizing. Now, back in the time you are speaking the issue was AA 1350 Alumimum and it was more an issue with the terminations rather than the AA 1350 Aluminum. It was all about the terminations and the expansion and contraction differences of the terminals and the aluminum, less ductile AA 1350. Just for some additional information of course. Now turn off the exhaust fans JOSH.
@pepsifan85043 жыл бұрын
Plus the switches that were added after our house was built were all grounded
@ZionicImpulse4 жыл бұрын
Do you know what a window cut is? U dont need a knife and it actually can make hooking up boxes alot faster cause it allows you to premake double gang outlets
@michaelcooper78113 жыл бұрын
Best music ever
@HI-rb9bl3 жыл бұрын
You need a twirliey screw driver dude!👌🤑
@wilhelmtaylor98633 жыл бұрын
An average bathroom fan runs at ~20W, or .02 kW. In Colorado we pay $0.13 per kW-hr so it costs $0.0026 per hour. Say you let the fan just run an hour each day and eventually get around to turning it off - just like most of us do. That's less than $1 per year. Can you guess how long it takes to offset the cost of this $30 switch? And a lot of people will pay a contractor to do this. What's your hourly rate? Add that to the $30. Now you probably have more than 1 bathroom so multiply that $30 by that number. This switch is as useless as an electric pencil sharpener.
@glenjamindle4 жыл бұрын
I was diggin the porn music while you were rewiring that box.