I have Belimo nrf24a-sz Used on the cooling line. Always variable when temperature rises, sometimes 100% and sometimes 0%. Note that he must be a conqueror
@Belimo_Global7 ай бұрын
We are glad you found this video helpful. Are there any other questions we can help you with?
@Maverick7343 ай бұрын
Do you need to set the damper shaft in the open position before powering up? As the actuator will automatically spring return..what if you have the damper shaft/blades on the closed position? Cheers
@Belimo_Global3 ай бұрын
You always want to perform the pre-tensioning with the damper closed and set the actuator in the closed position without the actuator being powered. Once that is set, you should power it up, and the actuator will go to its commanded position.
@AlexSanchez-hs5yx3 жыл бұрын
Hi we have same actuator and it makes a very loud winding noise when we turn off or turn on the AC. Is this normal?
@Joe_Mission2 жыл бұрын
some noise maybe, very loud noise I would not think is normal
@lonsdaleslipons95702 жыл бұрын
@@Joe_Mission it will make a winding noise. Loud would maybe indicate lose parts inside actuator or possibly the kit the actuator is controlling has loose or faulty parts.
@JaykeSapalaran-iq3qs Жыл бұрын
Great video tutorial ❤ thank you for sharing your knowledge and experience 🇵🇭🫡
@sumankabi9496 Жыл бұрын
Does it works with 24DC volt or 0 to 10 DC v ?
@Belimo_Global Жыл бұрын
This video is showing 24 DC voltage. You can contact technical support for detailed instructions on a 0 to 10 DC v actuator.