How to set a fan cycling control on a refrigeration system

  Рет қаралды 10,925

latent fusion

latent fusion

Күн бұрын

Пікірлер: 29
@williehealer9540
@williehealer9540 2 жыл бұрын
Great info for napa valley 32 F
@andreagate542
@andreagate542 3 жыл бұрын
Thank you for a very well laid out video! My question is how did you decide on the Saturated condenser temperatures of 85 to 105°F For your cut out and cut in the range. Thank you in advance
@patrickg7569
@patrickg7569 5 жыл бұрын
Wouldn’t mind seeing some more of these whiteboard video explanations.
@latentfusion2563
@latentfusion2563 5 жыл бұрын
Thanks patrick any specific topic? I know the quality of the video maybe suspect but I try to get an easy to understand point across. cheers
@saltrue1555
@saltrue1555 4 жыл бұрын
Very instructive thank you very much,God bless
@cosminstanciu6134
@cosminstanciu6134 Жыл бұрын
Thank you for the video
@xraybravo7180
@xraybravo7180 4 жыл бұрын
Where do you get the magic number 85F - 105 F and based on what you determined your differential pressure. I have been struggling with this a lot. Thank you so much for info.
@pedrojardim1163
@pedrojardim1163 2 жыл бұрын
Good staff
@xraybravo7180
@xraybravo7180 4 жыл бұрын
Amazing
@RobRocker09
@RobRocker09 7 ай бұрын
Do you have go back in the late spring and late fall to adjust it
@latentfusion2563
@latentfusion2563 7 ай бұрын
Once the control is set it will maintain the head pressure year round with no need for adjustments.
@MrEltinieblas
@MrEltinieblas 5 жыл бұрын
Great explanation. Are these cut in and cut out settings for medium or low temperature evaporators? Thanks 🙏
@latentfusion2563
@latentfusion2563 5 жыл бұрын
yes, this can be used as the cut in and out on both medium / low temp applications. 👍 just remember to set it up for the refrigerant that your using.
@MrEltinieblas
@MrEltinieblas 5 жыл бұрын
latent fusion thank you so much. I am fairly new to commercial and residential refrigeration. Please keep making more videos.
@user-lh6kg2nw5r
@user-lh6kg2nw5r 5 ай бұрын
is a fan cycle control just for air condition?
@latentfusion2563
@latentfusion2563 5 ай бұрын
It can be for air conditioners but I utilized it more when working on refrigeration equipment during periods of low ambient outdoor temperatures.
@user-lh6kg2nw5r
@user-lh6kg2nw5r 5 ай бұрын
Thank you.does it have anything to with the furnace the fan cycle control?
@user-lh6kg2nw5r
@user-lh6kg2nw5r 5 ай бұрын
And how long can the thermostat be on hold and not on run?
@ace7709
@ace7709 5 жыл бұрын
What happened to the printer set up video? Looks like a lot of your stuff has gone private.
@rs3682
@rs3682 4 жыл бұрын
how about Freon 502 , i want the temp. inside the cold store between -18 -13> is it right to adjust the low pressure 20 psi and diff 12 psi
@latentfusion2563
@latentfusion2563 4 жыл бұрын
Hi RS, So I'm suspecting your using farenheit? Keep in mind most condensing units can only operate within a certain range unless they have been modified. Check the lowest saturated temp with the equipment info. To achieve your temperature settings try 20 psi in and 8 psi diff to start. Monitor the cutout and increase as needed. A liquid to suction heat exchanger may need to be added to the system. Good luck and let me know.
@rs3682
@rs3682 4 жыл бұрын
@@latentfusion2563 thanks ...no data available in the unit....i am in saudi arabia>>>any how i adjust the low pressure 20 psi>>>>> high pressure 300 psi>>>>diff 15 psi>>>>inside cold store thermostat setting -8c >>>ir running normally>>>.is the setting right?
@latentfusion2563
@latentfusion2563 4 жыл бұрын
@@rs3682 just a question, does the room have a thermostat if so then it will be your primary temp control and the low pressure control will be a safety control. If you want the room colder then adjust the thermostat.
@rs3682
@rs3682 4 жыл бұрын
latent fusion u r right...yes i have,,,,,another question if u pls, what standard or normal pressure for freon 502 means what suction and discharge rate?thanks again
@latentfusion2563
@latentfusion2563 4 жыл бұрын
@@rs3682 suction pressure is determined by what saturated temp you are trying to achieve. Refer to a pressure temp chart. You can also download the danfoss phone app. Head pressure is determined by the ambient temp around the condenser. As a general rule the condenser will add 25f to 30f to the ambient. So if it is a 70f day the condensing unit will be condensing at 100f. On a pressure temp chart for r502 it should be around 215 psi. Download the app and have a play. Hope this helps. The pressures and temperatures will very day to day as conditions change.
@alphatechrefrigeration3983
@alphatechrefrigeration3983 5 жыл бұрын
Typically we are taught to set the differential between 30 and 50 psi. I've been in the field since 1995 and as of yet no one that I've spoken with has ever suggested a 66 PSI differential setting nor have I ever felt the need to set it that high. So if you don't mind providing a little feedback where did you come up with the 66 PSI differential setting?
@latentfusion2563
@latentfusion2563 5 жыл бұрын
Thank you for your question. I have based my numbers on the saturated condensing temperature of the refrigerant that i am using. Since all refrigerants have a different pressure/temperature relationship I didnt want to recommend a rule of thumb like 30 - 50 psi. Standard condensing units have a T.D. across the condensing coil of 30f So at an ambient of 55f we will be condensing at 85f. At 75f ambient we will be condensing at 105f. All condensing units have a recommended refrigerant temperature range in order to achieve the greatest net refrigeration effect. Some new equipment have lowered this range by increasing the size of the condenser slightly. My example in the video was for r404a, blended refrigerant. If I was to use other refrigerants they would work out as follows. R134a in @135psi out@ 79psi diff of 56psi R22 in @ 209psi out@ 155psi diff of 54psi. R12 in @ 129psi out@ 91psi diff of 34psi. So to re-cap the difference between my settings and yours is about 2f in saturated condensing temperature. Although my pressures seem higher than the R.O.T. that you have been taught it means next to nothing when it comes to the effective operation of the equipment. I have spent a lot of time in canada so I have always preferred getting a bit more run time out of my fan.
@alphatechrefrigeration3983
@alphatechrefrigeration3983 5 жыл бұрын
@@latentfusion2563 thank you!
@sbitschy
@sbitschy 4 жыл бұрын
Wow. You were prepared to answer that question, lol. Good answer
How a vacuum effects moisture in a refrigeration system.
2:24
latent fusion
Рет қаралды 7 М.
Refrigerant Low Pressure Control setting
10:09
latent fusion
Рет қаралды 68 М.
Unveiling my winning secret to defeating Maxim!😎| Free Fire Official
00:14
Garena Free Fire Global
Рет қаралды 16 МЛН
HVAC 107 Scenario: Low Ambient
11:40
Love2HVAC with Ty Branaman
Рет қаралды 11 М.
Refrigeration: Low Pressure Control As Temp Control
25:22
Christopher Molnar
Рет қаралды 92 М.
How to DESIGN and ANALYSE a refrigeration system
18:27
The Engineering Mindset
Рет қаралды 196 М.
Using a low pressure control to control box temp
8:16
HVACR VIDEOS
Рет қаралды 51 М.
Fan Cycling Switch
7:39
HVAC TECH LIFE
Рет қаралды 11 М.
Walk-in Freezer Warm With Fan Cycle Switch Adjustment Failing Motor
10:59
System short cycling on Saturday evening
7:33
HVAC GUY
Рет қаралды 39 М.
3D How Refrigeration and Air Conditioning Works P1 - Components
9:47
Online HVAC Training - HVAC Training  Solutions -
7:44
Ron Walker
Рет қаралды 228 М.
Unveiling my winning secret to defeating Maxim!😎| Free Fire Official
00:14
Garena Free Fire Global
Рет қаралды 16 МЛН