How to test a RPZ backflow preventer

  Рет қаралды 4,129

Andy Plumbs

Andy Plumbs

Күн бұрын

Пікірлер: 17
@marteacalloway9001
@marteacalloway9001 2 ай бұрын
Thank you so much for your help I received my backflow certification in August and here it is October and I finally got a chance to test my first backflow and your video was perfect. Thank you so very much.
@fredisvelasquez4188
@fredisvelasquez4188 3 ай бұрын
Great brother..
@Jordon.007
@Jordon.007 2 ай бұрын
Can rpz be installed in the basement of a home when a lawn irrigation system is installed? In other words, can it be installed below the height of a lawn irrigation system?
@andy_plumbs
@andy_plumbs 2 ай бұрын
@@Jordon.007 yes!
@Invictusxiv
@Invictusxiv 7 ай бұрын
Something I’ve noticed is nobody talks about the buffer. If you recorded it, how did you? I’m curious about the relevance of it.
@andy_plumbs
@andy_plumbs 7 ай бұрын
The buffer?
@Invictusxiv
@Invictusxiv 7 ай бұрын
@@andy_plumbs Some departments have on their test sheets "buffer PSI" as it's main purpose is to see how much of pressure fluxuation there is, usually it has to be more than 3.0 psi from what I understand. Do you check the buffer on your tests? I have to in mystate/county.
@andy_plumbs
@andy_plumbs 7 ай бұрын
@@Invictusxiv nope, never heard of it.
@joninnet
@joninnet 7 ай бұрын
Reverse the hoses on your rig. The bend on the other end of your high hose will allow you to avoid that half inch water line over the test cock.
@JimmyBackflow
@JimmyBackflow 7 ай бұрын
The differential across the second check valve differs from the differential pressure across the first check valve. Also, to backpressure the second check valve, the high control valve must be opened to introduce high pressure to the backside of the second check valve. Bad installation, no drain for catastrophic discharge. There are many problems with this video.
@andy_plumbs
@andy_plumbs 7 ай бұрын
Are you saying the way I tested it was incorrect? I agree that the RP should be dumping to a drain but I didn’t plumb the building.
@JimmyBackflow
@JimmyBackflow 7 ай бұрын
@@andy_plumbs To measure the differential pressure across the first check valve, connect the high-pressure hose to TC#2 and the low-pressure hose to TC#3, bleed out the air and take the reading. To backpressure the second check valve with the hoses still connected to TC#2 and TC#3, bleed the air out of the vent hose by opening the low control valve and connecting the vent hose to TC#4. Open the high control valve one complete turn and observe the relief valve. If there is no discharge, the second check valve is drip-tight with backpressure. To validate that backpressure was introduced behind the second check valve and not going downstream, close TC#2 and observe the gauge. If holding steady, the backpressure of the second check valve is confirmed, and the backflow preventer test was conducted when in a static state. To trigger the relief valve, open the low control valve one-quarter turn and observe the first drip. To test the DP across the second check valve, close TCs and remove hoses. Next, connect the high-pressure hose to TC#3 and the low-pressure hose to TC#4. Bleed and take the reading. It should be one psid or greater. I refer you to videos on KZbin at jimmybakcflow.com. Also, the AWWA M14 manual has several test procedures, including the one I described. Testing is easy, but not done correctly causes concerns.
@andy_plumbs
@andy_plumbs 7 ай бұрын
@@JimmyBackflow the procedure you’re describing is similar to how DC’s are tested, but I’ve never disconnected my hoses and jumped test cocks on a RP. I’ve always used the ASSE field test procedure book and it doesn’t mention anything of jumping test cocks either.
@JimmyBackflow
@JimmyBackflow 7 ай бұрын
@@andy_plumbs To measure the DP across the RP second check valve, you must measure the pressure at TC#3 and TC#4. You will not see the steps described for measuring the DP across the second check valve because most test procedures and authorities do not require them. The problem occurs when testers fill out the form and put the DP of the first check valve in the second check valve box. This is a big problem in the industry because trainers do not explain how to measure the DP across the second check valve. If you want to measure the DP across the RP second check valve, do it correctly. If not, leave it blank. If you watch my videos, you will have a good understanding on how to test backflow preventers. The procedure is used through the NE States, NY, PA, and NJ and is outlined in the AWWA M14 Cross-connection Control Manual. Also, NEWWA provides a certification program for testing backflow preventers; a written copy of the test procedure is available.
@twtw2247
@twtw2247 2 ай бұрын
You are not reading the asse 5000 book test procedures correctly bleed tc 4 then open close 1,2,3,4 when u backpressure check 2 record it as close tight and sov2 in a no flow condition .asse doesn't require second check differential.you should have moved high to 3 low to4.your reading was incorrect. I teach for 3 asse schools Michigan should have taught u better follow the book
@andy_plumbs
@andy_plumbs 2 ай бұрын
Jumping test cocks is not a part of the RPZ testing procedure.
@twtw2247
@twtw2247 2 ай бұрын
It's bleeding testcocks read your manual you have to eliminate air and debris.I can't believe you were taught this air is compressible water is not.your results will be wrong.
RPZ - Field Test
12:20
Jimmy Backflow
Рет қаралды 71 М.
USC 10th Edition Backflow Test Procedures Demonstration
35:40
Backflow Management Inc
Рет қаралды 44 М.
$1 vs $500,000 Plane Ticket!
12:20
MrBeast
Рет қаралды 122 МЛН
UFC 287 : Перейра VS Адесанья 2
6:02
Setanta Sports UFC
Рет қаралды 486 М.
Complete Installation: Watts 1” RPZ Reduced Pressure Zone Backflow Prevention Device
17:09
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 8 М.
How it Works Backflow Preventer | Plumbing 101
8:09
Roger Wakefield Plumbing Education
Рет қаралды 32 М.
Leonard mixing valve repair
25:31
Andy Plumbs
Рет қаралды 707
Troubleshoot ANY Backflow in 3 Easy Steps
18:22
Disney-McLane & Associates
Рет қаралды 40 М.
DC TEST
3:51
Mark Titus
Рет қаралды 39 М.
Why do we need backflow preventer testing?
3:31
Merit Plumbing
Рет қаралды 10 М.
How to Install and Test a Back Flow  - Irrigation Start Up
5:19
Make It or Break It
Рет қаралды 15 М.
Well tank replacement
31:19
Andy Plumbs
Рет қаралды 1 М.
RP One Hose Test Procedure
14:44
Viking II Backflow Training
Рет қаралды 20 М.
$1 vs $500,000 Plane Ticket!
12:20
MrBeast
Рет қаралды 122 МЛН