I've been an electrician for years now. The last time I used a Megger was when I was in school. And today I have to test some wires in a building. Your video refreshed my memory. I'm good to go now. Thank you ! 😀
@RCworstwater3 жыл бұрын
Woohoo! Happy we could help :)
@irishguy2000072 жыл бұрын
What about a standard multimeter? It can go up to 10mohms or more.
@akimbojimbo37632 жыл бұрын
@@irishguy200007 a multimeter is acceptable for testing circuit resistance (although a proper micro ohmmeter is preferable). You want high voltages for testing insulation, whereas a multimeter tests at something like 1.5V.
@Loredo_17 ай бұрын
I'm an electrician as well and I always megg wires and motor winding but I use the fluke 1587 fc, which is way better
@robtheisen58445 жыл бұрын
Yet another golden nugget of information to use in my tool kit. Thanks for sharing!
@doc-holiday5 жыл бұрын
I found this most informative. Thank you for sharing.
@sgtrock1 Жыл бұрын
I worked for an electrical testing outfit years ago and we tested everything in a power plant, anything from MCC switchgear, transformers, relays, high voltage busses, etc...One point I recommend in your video is try explaining where do you connect your negative lead and why? Also, explain why you should ground (short out) your positive lead to ground after each test? Megger wiring test plans can vary between many applications so, I would try to explain how a valid megger test only exists when you have an open circuit to the difference in potential between your test cable and ground. Other than that I thought your presentation was really informative.
@satheeshnatrajan31865 жыл бұрын
thank u so much for sharing a good information love from india
@ahmadabomhmod15213 жыл бұрын
Thank you for the video, I have a question that I hope you will answer me, if I want to check the house cables from the board, what should the resistance of the wire be with respect to 500 volts, and how can I know if I have a problem with insulation. Thank you
@mikeadler4342 жыл бұрын
Great video, thank you for taking the time to create it! 👍👍
@RCworstwater2 жыл бұрын
Glad you liked it!
@dannypate242710 ай бұрын
Im not the brightest bulb on the tree..please help me understand this test. Im at the well with all the leads disconnected from the source. Do i put one lead on the ground and the other lead on each wire during the test. Thanks
@pontgta13 жыл бұрын
Thank you ! Very informative.
@samersarah9573 жыл бұрын
What is the numbers should get it when there is some leak? Thanks.
@MJ-iy4fb3 жыл бұрын
good video, one question, how should you select the correct voltage to be used on your meter ? thanks
@gusc67853 жыл бұрын
I good rule of thumb I was told was to double the line voltage .. 120 v send 250 ' 240 volts send 500, 480 send 1000..
@framos9991 Жыл бұрын
Very Useful !
@RCworstwater Жыл бұрын
Glad it was helpful!
@rodgraff1782 Жыл бұрын
Isn’t there going to be a pump ground wire to the casing, which is in contact with the water.?? Why not use that as your grounding reference.
@smellthecoffee53142 жыл бұрын
Excellent video - Thanks
@RCworstwater2 жыл бұрын
Glad it was helpful!
@ianxluza88703 жыл бұрын
Thanks for sharing this great knowledge
@RCworstwater3 жыл бұрын
My pleasure
@bitshtannicajohnson6957 Жыл бұрын
*I was in a Houston restaurant once and the line chef used something like you shown to test the soup in a giant pot, strange huh?*
@benisplayin2 жыл бұрын
Great and informative video. Thank you. I have a hurried wire imbedded in asphalt. How would I be able to determine the specific location of damage to that wires insulation. I have a tracer unit allowing me to determine where a break is but it is less than helpful with damaged insulation. Your input is appreciated.
@luanhoang1419 Жыл бұрын
He said u can spend weeks and still won’t find it bc the damage to insulation can be very minimal to the point where u can’t even see it
@skilltradesmanco.86362 жыл бұрын
Now my question is, how do you test to see if the flow of current is flowing through the wire properly and that the internal conductor itself hasn’t been damaged, Wich from my understanding is that I can test with my Megger at a 1kv and max out at 2.2 gigaohms and there is times I can test and get a slow rise of 100 megaohms to 3 or 400 megaohms
@gusc67853 жыл бұрын
Great video
@RCworstwater3 жыл бұрын
Thanks for the visit
@mikejensen66843 жыл бұрын
So... wouldn’t you want to check insulation resistance between each conductor as well?
@luanhoang1419 Жыл бұрын
Not necessarily unless the job spec requires you to. Theoretically If each conductor holds the voltage for x amount of time required in your test then that conductor has no damage to its insulation.
@michealplater90072 жыл бұрын
Is that single insulated cable ?
@mywickedqueen3547 Жыл бұрын
curious if salt water would make a difference over say distilled or ordinary tap water?
@rodgraff1782 Жыл бұрын
Demonized water is a non conductor. Utility companies use it to wash off insulators that are carrying high voltage electricity.
@tabasumcarpentry53362 жыл бұрын
hi sir can an insulation tester detect wires if the wire's insulation is cracked but not touched each other. like some old cables' insulation cracked and the cooper conductor exposed but not touching each other?
@rodgraff1782 Жыл бұрын
Yes. The high test voltage is enough to create an arc between the breaks in the insulation if the breaks are close but not touching. Any moisture would also make a difference.
@mark-gb4zk2 жыл бұрын
If anyone could help, I been looking for anything saying if Megger readings before you run the unit “cold readings is supposed to be more or less than the megger reading after you ran the unit for some time “hot readings”
@rodgraff1782 Жыл бұрын
You should ways Meg motors qt twice their operating voltage, and at operating temperature. Of course disconnect power first. Resistance in wire goes up with an increase in temperature, and down with a decrease in temperature.
@goldfish56063 жыл бұрын
If i were to carry out this INSULATION test on the table where would the test leads be placed then (if we are not placing one test lead in the water) . Do you just put the test leads on both ends of the wire youre testing or do you only use ONE test lead for the wire youre testing . Please advise
@RCworstwater3 жыл бұрын
You cannot do this test without submersing the wire in water; because the water is conductive it will allow electricity to pass through it into any cracks in the insulation. That's why you have one lead on the end of the wire and one in the water.
@goldfish56063 жыл бұрын
@@RCworstwater What if i bought a new cable from the hardware store and its on a table rolled up new. Could i not check and test it to make sure the the insulation is good without unrolling the whole roll of wire. Could i then find the ends of the wire and test with the insulation resistance tester to make sure it does not have any cuts?
@faithmachinerycenter5 жыл бұрын
Great information! Please send us testing an induction motor with a unit of burnt motor and a working or serviceable motor in comparison...thanks and great info.
@irishguy2000072 жыл бұрын
Now that would be a great use for it.
@washerdryeradvicechannel80413 жыл бұрын
Big thumbs up
@knighthonor442 жыл бұрын
So if I put the meter on both ends of the same wire, I should get a low value right. Like zero?
@RCworstwater2 жыл бұрын
Correct
@joeshmoe59354 жыл бұрын
Thanks for sharing, but what if you want to test insulation in wire that is not submersed. I have 3 600 mcm wire in a metal conduit. I want to be 100% sure before energizing that no insulation is nicked or compromised. Would I just attach one lead of megger to the insulation and the other to conductor? I want to rule out any possibility of having parallel arc fault.
@cannaroe12134 жыл бұрын
Then test between the different wires, live, neutral, ground, as you are basically testing 2x insulation at any point there could be a short between two wires. To test the jacket it it's entirety, I guess you are supposed to submerse in water, because you can't get your meter probe to the wire later on - but in your instance you would attach the probe to the metal conduit of course :)
@waynehenson10944 жыл бұрын
Good video.
@RCworstwater4 жыл бұрын
Glad you enjoyed it!
@djelectricals344 жыл бұрын
very nice sir
@NovaHova5402 жыл бұрын
Can these be used with fuel ?
@TheNYgolfer2 жыл бұрын
Conspiracy theories aside, that is basically what brought down TWA flight 800.
@chenxubin2 жыл бұрын
How to megger without water?
@hafoochoo71922 жыл бұрын
thank you !
@RCworstwater2 жыл бұрын
You're welcome!
@TheReal19534 жыл бұрын
OK, but typically in a well case, the water level could be 20ft or more from the top. I think it's important to emphasize you need to drop some sort of test wire down there to hit water and then hook up one of the megga leads to that?
@rodgraff1782 Жыл бұрын
Just use the pump ground wire as your reference. It’s attached to the casing, which is in contact with the water.
@luanhoang1419 Жыл бұрын
There’s no resistance in water whether you’re at the top of 100ft or at the bottom unless it’s really really dirty and filled with junk like wood
@jeremiahtallant4 жыл бұрын
You can do this in open air!!!! For every single wire you want to megger. Get a spool and connect 2 leads and megger.... that meter gives you the number of resistance. Wow....
@RCworstwater4 жыл бұрын
We are measuring the integrity of the plastic insulation. Hooking one lead up to either end of the wire would tell you the resistance of the wire, not the insulation.
@Wolf.88 Жыл бұрын
Thanks
@lupojacobo98924 жыл бұрын
Thanks for sharing
@RCworstwater4 жыл бұрын
Thanks for watching!
@samuelpowell874 жыл бұрын
Awesome
@j.r50545 жыл бұрын
I have a problem with my water well cause its keep tripping the breakers i have change the pressure switch and the control box its wokst until the pressure drops to 30 psi when it tries to raise the pressure tripping the breakers again
@RCworstwater5 жыл бұрын
Jairo: Please give us a call and we will help you troubleshoot: 855.329.4519
@milton33793 жыл бұрын
so no resistance means the wire is cut, resistance means the wire is ok? is 1000 volts ,who resist this voltage the wire or the insulation. sorry for a dumb question.
@kaybhee63 жыл бұрын
why u got water down there...
@RCworstwater3 жыл бұрын
That's where we like to keep it. Just kidding, that's our pump testing pit.
@DJayAce44 жыл бұрын
Why would you read less resistance/ohms when the wire is damaged but hire resistance at 660 when it's perfect wire? Or am I just thinking about it in the wrong way. Are you sending 660 volts through the wire or something and if it's perfect wire it'll read 660 obviously, if it's bad wire the voltage won't make it's way through it and will read 0, is that what's going on? Also if you have one meter lead in the water and one touching the good wire and it reads 660, how does that lead that is touching the wire know that it's 660? The other lead is in the water so how does it know... Also let's say you have a panel and the main is tripping maybe every 3 or 4 hours. The customer calls you to the house but it doesn't trip right away. You want to do an insulation resistance test like you are doing now. How would you achieve this in the panel? You would go hot to neutral correct? Instead of hot to water like you are doing here.
@DJayAce44 жыл бұрын
@Castlebury21 reading 0 indicates there is no resistance and the wire is bad? How does this make sense. If there is no resistance, wouldn't it be a good wire? A bad/damaged wire would have a lot of resistance on it I'd assume
@randysterling47004 жыл бұрын
@@DJayAce4 take a electronics course you dick pickle
@RCworstwater4 жыл бұрын
We are measuring the continuity between the water and the bare copper wire Jason, so no resistance means there is a crack in the wire insulation that would result in a ground fault if it were installed in a well.
@illestofdemall133 жыл бұрын
@@DJayAce4You aren't really understanding what he is doing and why. In the test he is doing, he got 0 resistance between the copper conductor and the water thus proving that the insulation is compromised. Electricity is making a direct path from the water to the copper and vice versa through the damaged insulation. He isn't measuring the resistance of the 2 ends of one conductor. That would be done with an Ohmmeter and the resistance in a good conductor would not be 0 Ohms necessarily, but the lower the better. Depending on the gauge of the wire and how long it is will change that reading.
@rodgraff1782 Жыл бұрын
I thought you were going to test the pump insulation and splices.
@agora78783 жыл бұрын
Muy mala la traducción. No se entiende. Por favor mejoren la traducción o si es posible pongan el audio en español pero con la traducción mejorada.
@joeneal213 жыл бұрын
I kissed where you put the other lead I just d at the red lead was the other end in the water?
@jaimemeza9134 Жыл бұрын
What did he saaaay?!😮
@billkarpsr.82494 жыл бұрын
C
@TheFalconJetDriver Жыл бұрын
The proper word is submerged not submersed the way you are applying the word.