Hvac brazing

  Рет қаралды 27,189

Love2HVAC with Ty Branaman

Love2HVAC with Ty Branaman

Күн бұрын

Пікірлер: 54
@dogumentary4984
@dogumentary4984 4 жыл бұрын
Now with proper rest and having breakfast in the morning, my mind is able to understand some of the things I miss. You are the best teacher, hope more good things happen to you.
@georgetsetsakos6088
@georgetsetsakos6088 2 жыл бұрын
Heat the pipe first just to melt the brazing rod! Anthem! I love it! Just tried brazing today for the first time and melted a hole in the darn pipe.... hip hip... Can't wait to try again tomorrow with your anthem. Thanks Ty!
@love2hvac
@love2hvac 2 жыл бұрын
Im glad you liked it. Dont worry about how many times you get it wrong, keep working to make it better.
@Garth2011
@Garth2011 Жыл бұрын
The torch tip must be moving at all times...holding it in one spot will damage your tubing.
@mikeiz6944
@mikeiz6944 5 жыл бұрын
Thanks for making these videos Ty, it is greatly appreciated. I hope everything is going well at your new location. Best of luck!
@bbrlocal
@bbrlocal 2 жыл бұрын
you make it looks so easy and seamless love it man
@love2hvac
@love2hvac 2 жыл бұрын
Just takes practice
@RedaReda-uk9lm
@RedaReda-uk9lm 4 жыл бұрын
You are a treasure, hope you are well Sir.
@amersingh2557
@amersingh2557 4 жыл бұрын
Brilliant way of remembering the technique.
@samersarah957
@samersarah957 3 ай бұрын
Hi Ty when replacing compressor with 3/4” and 5/8” with oxygen and acetylene torch what size of tip use and should the pressure be higher than 5 acetylene and 10 or 15 to oxygen? Thank you.🌹
@GotchaplumberGotchahvac
@GotchaplumberGotchahvac 11 ай бұрын
Good looking braze.
@Garth2011
@Garth2011 Жыл бұрын
Lots of HVAC service is performed with an adjustable wrench ! After a few jobs on various HVAC you would think a tech would opt to carry the correct end wrench or fitting wrench and a proper wrench to remove set screws/bolts on fan blades to motor shafts. Too often I see the adjutable wrench rounding off the head of bolts, fittings, etc. What about the next service call and having to put a wrench on them? The worst of them all is those who use "channel lock" pliers to wrench nuts/bolts/fittings.
@samersarah957
@samersarah957 2 жыл бұрын
Thank you Mr.Ty for nice teaching. Is possible to use a propane which is use for heating and cooking or butane gas with oxygen for brazing instead of acetylene gas? Another question when set up the acetylene should be at 5 and oxygen at 10 in the gauge.🌷Thanks.
@love2hvac
@love2hvac 2 жыл бұрын
I oxy propane is possible. Propane generates less than 10% thermal energy. 10 oxygen and 5 acetylene is a good start. Some people like different numbers and it depends on how big the pipe is.
@TomSon-ej3pw
@TomSon-ej3pw 14 күн бұрын
Would it be possible to braze just with the propane without the oxygen?
@al-ameenallu9927
@al-ameenallu9927 2 жыл бұрын
With reference to first brazing example nitrogen was purged through liquid service port and the nitrogen will come out from suction service port isn't it?....so we can proceed with brazing after pumping down refrigerant to condenser....is that safe
@love2hvac
@love2hvac 2 жыл бұрын
Yes. Just remember when you pump down you don't always know the condition of the refregerants or how swell the previous tech dehydrated.
@GotchaplumberGotchahvac
@GotchaplumberGotchahvac 11 ай бұрын
Do u suggest brazing high pressure or low pressure side first, or does it matter?
@love2hvac
@love2hvac 11 ай бұрын
As long as nitrogen is flowing, it does not matter
@eddiegomez3628
@eddiegomez3628 3 жыл бұрын
Do you remove the cores from the valves? Or its not necessary? The way im being taught, in my job, is not necessary.
@love2hvac
@love2hvac 3 жыл бұрын
For brazing I remove the cores every time. It does not take but a few seconds. They are very small and sensitive to heat. It is also very difficult to flow nitrogen with them in place. That said, Never argue with your lead. Eventually you will be in your own truck.
@eddiegomez3628
@eddiegomez3628 3 жыл бұрын
@@love2hvac That last part is true..hehe. But you're right. Thank you.
@samersarah957
@samersarah957 3 жыл бұрын
Do you prefer oxy-a cytalen or acetylene torch in brazing? Thanks.
@love2hvac
@love2hvac 3 жыл бұрын
I do prefer oxy acetylene , air accetlyne second
@jericosha2842
@jericosha2842 4 жыл бұрын
Ty, your videos have been an incredible aid as a new tech. Thanks so much.
@RedaReda-uk9lm
@RedaReda-uk9lm 4 жыл бұрын
Hello Sir, Brilliant videos
@cleansebob1
@cleansebob1 5 жыл бұрын
How do you flow nitrogen through a non-bleed TXV? I've had problems with this in the past. No matter how small I make my flow rate, it still wants to blow the solder out of the joint.
@love2hvac
@love2hvac 5 жыл бұрын
Great question Bob, If it is a threaded Threaded TXV, I just leave the TXV out until all the brazing is done. Leaving it attached as if it was a fixed till I complete the brazing. If it is a pre-brazed TXV inside the coil, then I will add a service port outside the evaporator on the liquid and the suction line and push nitrogen threw both lines outside with a tee.
@cleansebob1
@cleansebob1 5 жыл бұрын
@@love2hvac Thanks for the quick reply!!! Nitrogen will then flow from the injection point outside to the newly added service port. But it seems to me that it won't get to where it's needed - the actual braze point for the TXV which is downstream from the newly added service port. Am I overthinking it? By the way, yours are by far the best HVAC training videos I've seen so far. I've forwarded them to a couple of my apprentices.
@love2hvac
@love2hvac 5 жыл бұрын
@@cleansebob1 yes your right. It is not nearly as good as it flowing past the braze. The main purpose is to keep the oxygen out to prevent oxidation. So while it is not as good it still limits oxygen. Thanks for the complement, I'm still learning every day. I Iove this trade.
@patrickpk6299
@patrickpk6299 5 жыл бұрын
Hi Nice videos! What type of brazing rod do you recommend?
@love2hvac
@love2hvac 5 жыл бұрын
For copper to copper I recomend 15%. It will be a stronger braze that will hold up to vibrations and much less likely to be a call back later on.
@Elisummit845
@Elisummit845 5 жыл бұрын
Great stuff. Can I place a request? Can you do a class on none condensable refrigerant in a unit? What the symptom's would be and how to be sure not to mistake it for another issue. Thank you so much
@love2hvac
@love2hvac 5 жыл бұрын
I will try to get to it. Still setting up the lab at the new school. Non condensibles will have the same symptoms as a restriction. With proper airflow you will see a High superheat and high subcooling. I have a paper somewhere in a box I made for that. I will try to find it this weekend. I recomend using the same solve for both. Recover all the refregerant. Open the metering device and check the screen and look for contamination. Purge some nitrogen threw the line to see if there is any restrictions. Cut out the old drier. Braze in the new dryer while flowing nitrogen. Pressure test with trace amount of refrigerant and a sniffer refrigerant leck detector. Pull a vacuum to 259 microns not to rise above 500 after 20 min or manufacture recomendations. Recharge with new refrigerant.
@Elisummit845
@Elisummit845 5 жыл бұрын
@@love2hvac Thank you. We are rooting for you here in New York to succeed at your new home 😊. Btw you inspire me to teach my coworkers and I make them all watch your videos. Thanks for everything
@sevanson1
@sevanson1 5 жыл бұрын
Nice series. But, what happened to rag cooling the joints at the air handler? Annealing?
@love2hvac
@love2hvac 5 жыл бұрын
I should have had another rag inside behind the panel. It is a good idea to move the wet rag over the joint as soon as its complete to allow for annealing. Annealing for copper is keeps it soft where as annealing for steel makes it harder and more brittle.
@sevanson1
@sevanson1 5 жыл бұрын
@@love2hvac ;-). thanks for the series!
@joecool4836
@joecool4836 3 жыл бұрын
@@love2hvac I think you mean quench. Quenching copper anneals it making it soft. Quenching steel will make it brittle. Annealing is a term used for process of softening metals. Thanks for the video. Nice.
@Michael-pz1hc
@Michael-pz1hc 4 жыл бұрын
Good day, You are the best instructor online. Do you have any video about the TXV external equalizer, what/how does what is does, why is better than internal Eq...Thank you!
@love2hvac
@love2hvac 3 жыл бұрын
I prefer external equalizer, it gets a more accurate superheat reading since it is getting it pressure at the end of the evaporator. Internal gets the pressure right after the txv, and does not account for pressure drop of the tubing in the evaporator.
@Michael-pz1hc
@Michael-pz1hc 3 жыл бұрын
@@love2hvac Thank you!
@Bryan-mg4gf
@Bryan-mg4gf 4 жыл бұрын
Can you do a video of brazing a Brass distributor to a TXV? Just want to see how you’d go about it
@gabaknegocios
@gabaknegocios 3 жыл бұрын
is any PEX systems for HVAC systems? (like in pluming with sharkbite)
@Garth2011
@Garth2011 Жыл бұрын
I hope not !
@Harr1s0n_Berger0n
@Harr1s0n_Berger0n 4 жыл бұрын
What torque wrench would you use for that piston?
@Resist_JWO_1984
@Resist_JWO_1984 5 жыл бұрын
Thank you for uploading this video. Is the nitrogen flowing toward the coupling?
@fabianpesantez7305
@fabianpesantez7305 Жыл бұрын
what type of solder do you use friend thanks
@love2hvac
@love2hvac Жыл бұрын
Depends on the application. Most of the time for Cooper to copper I use 15%silfoss
@fabianpesantez7305
@fabianpesantez7305 Жыл бұрын
thank you so much
@mariobrot6305
@mariobrot6305 4 жыл бұрын
like it
@leonardlewis5586
@leonardlewis5586 Жыл бұрын
Darn I forgot about that o ring😳
@rodgraff1782
@rodgraff1782 Жыл бұрын
When you flip that rod around and it burns a nice brand on your hand, you will start wearing welding gloves. Other than that, and the singing, good video. PS. You should set a better safety example for your apprentices, by wearing the proper personal protection equipment.
@love2hvac
@love2hvac Жыл бұрын
Safety note, don't get into the trades, it's too dangerous.
How to braze copper? @Uniweldproducts
23:15
Taddy Digest
Рет қаралды 15 М.
Brazing Techniques
15:48
HVAC School
Рет қаралды 66 М.
HELP!!!
00:46
Natan por Aí
Рет қаралды 16 МЛН
MY HEIGHT vs MrBEAST CREW 🙈📏
00:22
Celine Dept
Рет қаралды 93 МЛН
HVAC 044 o-rings, caps and locking caps
7:44
Love2HVAC with Ty Branaman
Рет қаралды 11 М.
HVAC 087 A. Connections part 1 Brazing,  introductory only
16:27
Love2HVAC with Ty Branaman
Рет қаралды 4,8 М.
Oxy-Acetylene Brazing 3D
15:47
HVAC School
Рет қаралды 156 М.
Brazing Training for HVAC Technician
35:45
HVACTIME
Рет қаралды 79 М.
HVAC Installation: Braze like a pro!
6:26
World of HVAC
Рет қаралды 1,1 М.
Never Need A Coupling Again!  How to Swage Copper Pipe!
18:14
PlumbingsCool
Рет қаралды 69 М.
HVAC Silver Soldering vs Brazing vs Brazing While Flowing Nitrogen!
18:42
AC Service Tech LLC
Рет қаралды 41 М.
Oxy Acetylene Brazing Tips and Tricks For HVAC Techs
9:30
HVAC in SC
Рет қаралды 112 М.
How to Braze Air Conditioning Copper
11:23
HVAC School
Рет қаралды 404 М.