@masterchef66947 жыл бұрын
The Engineering Mindset I would like to buy you a coffee....but in my country pay Pal is not available
@kingkongtiger7 жыл бұрын
Thanks for the great video. Please make more videos on HVAC system designs with calculation in different buildings. (May be start with something like single zone design with cooling load & fresh air requirement etc)
@robertingersoll52898 ай бұрын
Good lesson. Small correction - the condensate water term should be negative. energy in = energy out h ent air = Q coil + Q condensate + h lvg air Q coil = Delta air h - Q condensate
@congthinh39797 жыл бұрын
you teached me, HVAC and English. thank you!
@EngineeringMindset7 жыл бұрын
Glad we could help Cong, keep learning!
@tiagoferreira67137 жыл бұрын
Hi! Thank you for your great job! You really understand a lot of things about hvac systems and their components! Please don't stop and continue the great job! Just gonna suggest some themes that I find interesting to understand better so you can maybe had to your list, if you find them interesting: - the various psychometrics evolutions of the air passing through the coils and other components (water cooling and heating coil, dx heating and heating coil, just an electrical resistance, humidification and dehumidification, and maybe others) - how a boiler works and main components (domestic ones (traditional and condensation ones) and industrial ones as you show in one of the videos) - how other type of cooling towers works - the tabs systems (thermo active building systems) Thank you once again and sorry for possible bad english Best regards
@EngineeringMindset7 жыл бұрын
All good points, Tiago. Thanks
@00ABBITT00 Жыл бұрын
A better teacher than the $3200 class my union provides.
@JayMehta607 жыл бұрын
Hi, thanks for the video! How do you select a coil to be used in order to achieve a desired cooling capacity? In other words I would like to understand how must I design the coil geometry to achieve certain cooling capacity, with the water inlet & outlet temps. known, air entering temp known etc.
@EngineeringMindset7 жыл бұрын
Coil geometry and design gets very complex. It takes hours of calculations, you should google the formula Q=U*A*DT as a starting point
@trisafesales93927 жыл бұрын
Hi Paul, superb illustrations and explanations..Just one small doubt Do we have to get RH of 100% for air coming out from the cooling coil in order to achieve the desired cooling effect...
@Hum42922 жыл бұрын
I was also thinking of the same matter. Unless we use to humidify the cool air after evaporator coil, the RH will not rise to 100% RH.
@jeffreyfontenot8803 Жыл бұрын
Yes, you want it to "rain" on the coil, wringing all that water out of the air. That way when you warm 55 F 100% RH air up to 75 F it is at 50% RH.
@babaksp42357 жыл бұрын
Beautiful, excellent
@basilhamdy5426 жыл бұрын
Please can you tell us what is the next step after calculate the cooling coil capacity , how to select the correct coil for your application
@jasonanderson73437 жыл бұрын
Great stuff. Hope to see more about HVAC calculations in the coming videos. Well done
@mohammadalshaikhhasan50912 жыл бұрын
Perfect and useful. I wish new videos about cooling coil water pressure drop and air pressure drop. but for the latent heat cooling load calculation, you assumed hw = hf ( heat of vaporization vs heat of saturated liquid)..why?
@wojtek_sanitarnik7 жыл бұрын
Do you have video about BF & CF fsctors of cooling coil. That would be interesting video. Thanks!
@imiuli13042 жыл бұрын
@ismailmasoodshaikh77572 жыл бұрын
Thanks for this very useful information, can you please let me know the water side pressure drop of cooling coil and the refrigerant required in DX coils for 1 TR of cooling
@mohammadalshaikhhasan50915 жыл бұрын
Thanks for the great video.. so helpful In case we have AHU designed and the evaporator coil sized to specific capacity, can we increase the airflow to achieve higher capacity? A chiller designed to specific capacity and connected to AHU to achieve a certain indoor temperature and air change rate, whats could happen if the AHU coil changed to another one smaller with the same high air flow? The face velocity will be higher? The effects on sensible capacity? The effects on latent capacity? Thanks again
@bhushanpawar88556 жыл бұрын
Sir water inlet temp.to.the cooling coil in ahu is same as chiller set point temperature for calculating kw of cooling coil
@ramamanikantadondapati10436 жыл бұрын
Sir you are saying the relative humidity is 100 persent. But human comfort is 50-55 percent. And also please make an video about relative humidity, specific humidity, dewpoint.
@kylevencer77096 жыл бұрын
hello. how to get the cooling water mass flow rate?
@nse083 жыл бұрын
Hi, I believe that your formula for Q should not include mw*hw, because this latent heat is included in ma*(h2-h1), am I wrong?
@amitstorm5004 жыл бұрын
can you give calculations steps for immersed helical coil in a stationary water tank carrying hot air?
@alimarzooq50515 жыл бұрын
Thanks for this helpful video. I have a question about the air pressure drop, how to calculate it? If you can provide me with some sources it will be better
@jeffreyfontenot8803 Жыл бұрын
What about coil efficiency? Are we assuming 100% efficient heat transfer? What is a typical cooling coil efficiency?
@malikshehryar71457 жыл бұрын
Pual my question is when three way valve is activated then in this situation how much water enters into the cooling coil ? Or water completely bypass the cooling coil and goes back in to return line.
@EngineeringMindset7 жыл бұрын
depends on the system, you can check the valve manufacturers documents to see the correlation between position and flow rate
@kuleyedi4 жыл бұрын
Could you also explain heating coil capacity? As far as ı know , at heating capacity we should not add humidity counts to Q and Other hand When we cool room , sometımes ıt concludes excessive humidity problems, how we get rıd of it technically. Thanks for efforts🙏🏻
@rezanoormohammadi69143 жыл бұрын
How can we calculate cooling water mass flow?
@اوسحسن-م7ت Жыл бұрын
hi..i have a question in different subject if you can help in evaporative cooling...is it useful to decrease the temp of water spry or water washer ex: if out air 36c,60%rh..on psy with 90% evaporative efficiency.h ll get a 28c db and 90%rh.. so if i enter a 7c cold water to the washer .will i get a cold air temp....with knowing that in 100%humidity the db is about 27c thanks
@keithwo13 жыл бұрын
good day kind question for this group, i just want to know if there is a formula for cooling capacity which fcu is converted from dx to chilled water or how many percent does of cooling load will be lost if converted?, thank you who ever answers,
@zeegohar83523 жыл бұрын
Does the relative humidity affect the enthalpy? According to the air properties i find 99 kJ/kg for h1. But paul uses 78 kJ/kg. What is the reason for this?
@ZeeshanKhan-fg7ry5 жыл бұрын
Can u tell me about coil in ahu.. Meaning of 4/6 row coil.. When we'd day this ahu is 4 row or any row???
@jayhaantharumugam67036 жыл бұрын
How to calculate the Airout Temperature? How did you arive at 15 Deg C. Please provide calcs?
@lukeallison66186 жыл бұрын
Dont you need the Dt to be able to ascertain the 4.67kg/s? How would you have this info without knowing the delta to begin with?
@EngineeringMindset6 жыл бұрын
you can rearrange or make iterations
@engineersingulf69686 жыл бұрын
here you subtract latent heat why? in the equation above it is adding
@ibrahimosman33937 жыл бұрын
Never stop
@mathewsvarghese61467 жыл бұрын
Can you please upload the duct installation videos based on shop drawings
@levierdragon7 жыл бұрын
You sound Aussie. I assume you're a mech engineer working in HVAC. How's the HVAC job market? I'm planning on heading back to uni to study engineering.
@EngineeringMindset7 жыл бұрын
Hey Roy, I'm not Aussie, but I have a mixed accent that often confuses people. I'm a dual mechanical and electrical engineer, working in building services consultancy. In my opinion HVAC is a great career path. You will likely be a mobile engineer and move around different sites meeting very interesting people, plus a lot of equipment is on the roof so you get great views over cities. It's also a job which will be less affected by the automation revolution, and it's in growing demand. No matter how the financial markets affect the world, there will always be the need for an engineer in a building.
@jfasjfas7 жыл бұрын
esp calculation pls
@Mateoshful7 жыл бұрын
Hello The engineering mindset. I would like to study more about HVAC system. And planning to study abroad. Is there any recommendation which is good university or course? Hope you will reply asap Thank you
@EngineeringMindset7 жыл бұрын
Depends where you would like to study. Try courses approved by CIBSE and ASHRAE, which cover building services.
@ravikumarginne11255 жыл бұрын
i want to calculate my cooling coil capacity for adding condensing unit more.
@partha6367 жыл бұрын
In the cooling load calculation , Q_dot should be negative i.e. -78.5 KW. Why have you taken it positive?
@EngineeringMindset7 жыл бұрын
partha sarathi Das over time engineers find short cuts and this is one of them, in the real world no one asks for a negative 75kW heat exchanger. You're right it is a negative value though.
@mohammedowais47937 жыл бұрын
Hii sir....... Waiting for new videos
@Aznd0077 жыл бұрын
Our Indoor design will be 23*C , RH - below 60 % . in this case the air which coming out from coil air having almost 100% RH !!! Here how will you control this RH Level??
@EngineeringMindset7 жыл бұрын
It's just an example. You can sub cool it and then reheat but a more efficient way is to use a Desiccant Dehumidification unit.
@Aznd0077 жыл бұрын
The Engineering Mindset Thanks for your advice!
@moneeshs81276 жыл бұрын
The air off the coil will be 100% rh , on entering the room i.e air off the grill it will mix with the room condition to make 60%rh i.e 13dec will mix with room condition so it will make 23dec c..since the dbt increase simultaneously the rh tends to reduce
@moneeshs81276 жыл бұрын
The Engineering Mindset for maintaining 50-60 rh any ancillary is not required for comfort application
@chriscoop95 жыл бұрын
0.9m3/kg entering? not 0.887m3/kg? confused....
@dantheman99097 жыл бұрын
How come you have 100% RH when the air has been conditioned through the cooling coil? Keep up the good videos 👍
@LM_25_114 жыл бұрын
At lower temperatures vapour gets saturated even at lower partial pressure. So for a vapour it's easy to attain high relative humidity ,since relative humidity is the ratio of partial pressure of vapour and partial pressure of vapour at saturation.
@butchruelos40706 жыл бұрын
The specific humidity unit in the condensate water mass flow rate calculation is wrong. It should be in kg/kg.
@SubhamCreative.613kviews5 жыл бұрын
ok
@elliotmott18697 жыл бұрын
what if you have a building with hundreds of FCU's in, there must be a quicker way then this