Learn Everything About Heat Pump Defrost

  Рет қаралды 72,522

HVAC School

HVAC School

Күн бұрын

Пікірлер: 76
@ivanvelasquez8558
@ivanvelasquez8558 Жыл бұрын
Good explanation good work as always
@Howie875
@Howie875 Жыл бұрын
As an experienced HVAC tech, I would like to say this video is very well done. Just have a couple of things to add. I believe using sensors or thermostats to terminate a defrost cycle before its timed period is up is called defrost termination, because I know that is the term used on commercial freezers. Also, since the evaporator and condenser are constantly switched in a heat pump the better way to describe them would be indoor and outdoor coil. Also, the for the new techs out there, the first time that the unit goes into defrost after running in cooling all summer, the auxiliary heat strips that come on during a defrost cycle that temper the cold air will most probably has a small amount of dust on them that will burn off and the customer may smell it. Then when the outdoor coil comes out of defrost and the outdoor fan comes on it many times will blow out a big cloud of steam that the customer thinks is smoke. Just keep that in mind.
@rj.parker
@rj.parker Жыл бұрын
Nice universal board. Now they need one for two stage systems. My rules of thumb for York heat pumps with demand defrost: * Defrost is limited to an ambient range between 50f and -25f. Liquid line sensor temperature must be below 40f. * Demand Defrost board uses a variable Ambient versus Liquid Line curve. Liquid Line measured with a 10k ntc thermistor located properly. * Board will exit defrost when the liquid line temperature is 80 deg or ten minutes. * Liquid Line and Ambient temperature thermistors are tested by disconnecting sensor wires from board and measure resistance in k ohms. Verify using a 10k NTC Resistance to Temp Chart. Should be +- 5f from actual temp of location measured. * LL Sensor location may be wrong if previously worked on. With an outside expansion valve, the sensor should be between the valve and the coil distributor. Otherwise the defrost board may terminate defrost too early or it may not defrost at all except at six hour timed intervals. The six hour timed intervals will occur in heat mode to ensure proper oil circulation. * 10k ntc thermistor tips: 10,000 ohms at 77f; about 32k ohms at 32f; NTC "negative temp coefficient" means Resistance goes up as Temp goes down
@napoguevara6450
@napoguevara6450 Жыл бұрын
I don't need to go to school you teach much more than a school I have learned a lot a lot a lot ❤
@Hvac-tx2bt
@Hvac-tx2bt Жыл бұрын
Emerson has the best universal products in the industry!!
@georgeian3243
@georgeian3243 9 ай бұрын
Well done, very informative. One nice feature Trane provides for their demand defrost is a chart in Service Facts that gives you the sensor ohms but also the DC volts the board should be seeing at a particular temperature from each sensor. Saves having to ohm out the sensor in the freezing cold…a bit easier on the bare hands.
@randynimtz7176
@randynimtz7176 9 ай бұрын
extremely informative diagnostics very well explained thankyou.
@bobfrank1376
@bobfrank1376 Жыл бұрын
Your videos are always great! Up here in the Pacific Northwest defrost sensors fail all the time. They get moisture inside and can freeze and expand. The carrier sensors also have had a very bad record out of the box this year and we have replaced over two dozen of them on brand new systems.
@jlsrr2577
@jlsrr2577 Жыл бұрын
I see mice and frogs shorting out or corroding the boards. In the Pacific Northwest
@ralphnabozny8494
@ralphnabozny8494 Жыл бұрын
I always learn something from these guys.
@stevencbowen
@stevencbowen Жыл бұрын
Outstanding video! Your explanations and the accompanying video are very clear.
@TheMaximomex
@TheMaximomex 9 ай бұрын
Its a great video plus you guys are doing all that with live voltage. This video is very helpful. Thanks for everything you do.
@KL-of4fd
@KL-of4fd Жыл бұрын
Tampa Bay tech love windshield time with y'all. Thanks for sharing the knowledge
@aaronburke2469
@aaronburke2469 Жыл бұрын
As someone who's struggled to understand the concept and functionality of a heat pump this video really made it all click for me.
@jahngonzalez7424
@jahngonzalez7424 10 ай бұрын
How am I supposed to wire a universal condenser motor and still have the defrost feature operate properly?
@shuhaibnawawi8854
@shuhaibnawawi8854 19 күн бұрын
Excellent video! Just curious, what’s the “cooling” capacity (Btu/hr) and power consumption (kW) of the ASHP during defrost mode (excluding the backup resistance heater)? My guess it that it should "cool" the indoor space just enough to melt the ice on the outdoor coil.
@nathanhurst5155
@nathanhurst5155 Жыл бұрын
Excellent video fellas, can’t wait to see y’all next week at the symposium 👍👍👍
@konstantinhoruzhik9883
@konstantinhoruzhik9883 10 ай бұрын
Me too,see you all next to heat pump outdoor unit
@waitwhat....2473
@waitwhat....2473 Жыл бұрын
great job with the illustrations.
@jpfaff777
@jpfaff777 Жыл бұрын
Great video as always! Thank you guys!
@brianmcdermott2430
@brianmcdermott2430 Жыл бұрын
Great info. again. Thank you Bryan & Brit.
@bills6946
@bills6946 10 ай бұрын
I make it a point to explain in very little detail to the customer what to expect with their new heat pump. Condenser buzzing without the fan running, frost build up and steam are all normal. It eliminates unnecessary non billable service calls
@michaellicavoli3921
@michaellicavoli3921 24 күн бұрын
I’m a retired electronic tech, but a lay AC person. I made several calls for service after my Carrier4t heat pump, fan would not turn on with compressor. The start capacitor is new, but after about two weeks the fan again fails to turn on. Today, I finally got my hands on a wiring diagram and found out about the defrost circuit board. The board only cost about $60, so do you think it’s a good shot to repair this intermittent problem? Primary power to the fan goes through a relay on this CB. Another thing, C-20 on the defrost CB was noticeable warm ten minutes or so after main power was secured. Is this normal?
@soloch69
@soloch69 Жыл бұрын
Great video 🙌🏻🙌🏻🙌🏻🙌🏻🙌🏻🙌🏻🙌🏻keep them coming
@lukegrinder81
@lukegrinder81 Жыл бұрын
Great stuff guys! Keep up the good work! Love the content.
@sparkyobrian6417
@sparkyobrian6417 Жыл бұрын
excellent explanation, however it was rather chaotic, watch it a few times and you will see some conflicting statements, would love to see a revision B of this video in a more organized format, that being said its a great video overall.
@aldoo5985
@aldoo5985 2 ай бұрын
Question, switching 4w valve while CP working is damaging CP internal?
@jonleon9132
@jonleon9132 Жыл бұрын
Thank you for this video
@josecarlosmejia9632
@josecarlosmejia9632 Жыл бұрын
great video for defrost unit
@Josh-px6xb
@Josh-px6xb 17 күн бұрын
On the thermostat , why is it connected to w2/aux and not w1/aux? and on the indoor unit , it’s connected to w1?
@jericosha2842
@jericosha2842 Жыл бұрын
When I first started, those universal boards pissed me off lol I didn't understand them. Good mention of the 10k thermistors. Didn't know the charts were so easy to find.
@JordieG8
@JordieG8 Жыл бұрын
The American Standard / Train demand defrost works quite well. Just make sure the damn coil sensor is actually attached to the coil when you install it. I had a defrost issue the first winter with my Silver 15 and when I went to test everything I found the Coil Sensor was dangling. It was like that from the factory.
@vincentlamoureux8446
@vincentlamoureux8446 Жыл бұрын
Great video 👍
@brianstanford647
@brianstanford647 Жыл бұрын
Great video as always
@HVACS
@HVACS Жыл бұрын
Thank you, my friend.
@matthosseini4194
@matthosseini4194 Жыл бұрын
Awesome info thanks 🙏🙏
@alexivanov4269
@alexivanov4269 5 күн бұрын
Do you think the board should include Wi-Fi with logging and monitoring capabilities in 2024? Maybe no one needs these extra features.
@jamesfitzsimmons381
@jamesfitzsimmons381 Жыл бұрын
Very good video guys
@fulano787
@fulano787 10 ай бұрын
So the compressor never turns off during the defrost cycle? When our unit cycles to defrost, the compressor stops running. The frost is staying put and that’s why I’m here.
@keithlayton5483
@keithlayton5483 Жыл бұрын
My defrost is operating according to specs, but as soon as the reversing valve switches over, kills the condenser fan like its supposed to, but also cuts out the compressor. I can feel the suction line heating up, so pressure is definitely building from somewhere. Any thoughts
@alanbricking
@alanbricking Жыл бұрын
Using the electric heat backfeed is not only for customer experience it also superheat the refrigerant to defrost the condenser faster correct?
@harryschrysan3183
@harryschrysan3183 9 ай бұрын
In cooling mode the super heat only means that the refrigerant has been boiled off completely and has also picked up additional heat beyond its saturation temp. (think of it as water that has boiled off and then the steam is getting hotter and hotter). So in cooling mode when you have 10 degrees of SH it means that vapor refrigerant which could be at 40 degrees F has picked up an additional 10 degrees of heat making it 50f. That temp is insignificant. So anything upstream of the compressor it terms of temp would play almost absolutely zero role. It's the extreme change in pressure during the compression process(discharge) that increases the temperature significantly in order to defrost the system. So no the heat strip is just for the customer's comfort.
@Succeedlikeyoubreathe
@Succeedlikeyoubreathe Жыл бұрын
Reads 9.7 ohms. He tells the other guy “no it’s 9700 ohms”. Then immediately reads the book and says “it’s 9.9 ohms that’s exactly what we have there.” Typical lead man response. Priceless
@jkbrown5496
@jkbrown5496 Жыл бұрын
I'm not sure demand defrost is a good thing in a humid winter climate like SE TN. But I've not been able to find anything on the logic used for demand defrost. It has value in refrigeration and likely dry winter conditions, it seems. One thing I don't see covered for demand defrost is that it terminates on the coil thermistor temp and the jumpers on boards, (it was a column on the WR) is to set that temp from 60-90 rather than being run time. The runtime before defrost is apparently the adaptive part but left hidden in the chip. But the termination temp is important as if you try to force defrost it will come right back out if the coil temp is above the termination temp setting. Sometimes giving the illusion of a problem with the board.
@rj.parker
@rj.parker Жыл бұрын
Demand defrost terminates on LL temp or time. The Emerson board is a good universal module for single stage heat pumps. Wish they had a similar version for two stage heat pumps.
@nathanwiley2858
@nathanwiley2858 Жыл бұрын
where is a good place in florida to be a service tech at
@georgedvojacki9770
@georgedvojacki9770 Жыл бұрын
Hey Brian great video. I'd like to add 1 thing, but let me know what you think. When you have a thermister in open air I use a thermometer the same as you. Although instead of checking it against resistance I use my meter in Temperature mode and check the temperature Of the thermister. If they're within a couple of degrees of one another then that thormister Should be good. Let me know what you think?
@rj.parker
@rj.parker Жыл бұрын
Usually a meter will read a k type thermocouple and not a 10k ntc thermistor. What kind of meter do you have?
@minnesotasalamander5913
@minnesotasalamander5913 Жыл бұрын
Good video.
@richseahag4980
@richseahag4980 Жыл бұрын
How do ductless wall hung units that go into defrost overcome the cold outlet air temperatures into the conditioned space without back up resistance heaters ?
@mackenziegray2090
@mackenziegray2090 Жыл бұрын
indoor fan should shut off while in defrost
@Howie875
@Howie875 Жыл бұрын
@@mackenziegray2090 Are you sure? Standard heat pumps need the indoor fan running during defrost. Its hard to understand at times, but when the system in defrost the indoor coil it is acting as an evaporator, and it is absorbing heat while the refrigerant turns from a liquid to a gas. This refrigerant vapor then goes to the outdoor unit where it is compressed and condensed, which releases heat, with the outdoor fan off to concentrate the heat in the outdoor coil and melt the frost. If the indoor fan was off during this time, the refrigerant would not pick up much heat and the defrost cycle would not work. Please let me know if a ductless system has a different arrangement.
@RichardParkerTheRealtor
@RichardParkerTheRealtor 10 ай бұрын
When it’s 35 or lower outside my heat pump turns off and won’t turn back on until temperature outside is back to 35. So I will constantly run my heat strips for days until temp outside go back up you think my heat pump is broken?
@EsauRodriguez-m1y
@EsauRodriguez-m1y 3 ай бұрын
But how can you change the time
@fredlogan3849
@fredlogan3849 Жыл бұрын
the board drops out the yellow wire to disengage the contactor [ momentarily]
@chrisdeanndavison3626
@chrisdeanndavison3626 Жыл бұрын
8:25 I will respectfully disagree. I find the snap action thermostats failing (also thermistors failing) are the major cause of defrost issues. They get stuck and will not close. I've seen many encased in ice on a 15 degree day test open. If I smack them with the handle of my screwdriver, they will often close. I replace the thermostat and no more defrost issues. I also live and work in a much colder climate than Florida, maybe that's the difference.
@npeay6297
@npeay6297 Ай бұрын
I was gonna say... because I just came across one, and I attached it to an ice pack, and it still wouldn't close. It's still not cold enough where I'm at for the coil to get below freezing
@tbone9405
@tbone9405 Жыл бұрын
If you have rolling blackouts in very cold weather, the defrost board will lose its accumulated run time due to loss of memory. Then the frost will build up so thick you will not have any usable heat in very damp conditions.
@Howie875
@Howie875 Жыл бұрын
That does not make sense. The compressor will not run during the power blackout so it will not ice up during this time. It starts accumulating run time below icing conditions and will defrost every 30, 60 or 90 minutes thereafter and clears its run time memory during every defrost cycle. If you are having rolling blackouts with that short of a duration, I do not believe the unit would heat anyway and that is more of a power supply problem than a heat pump problem.
@tbone9405
@tbone9405 Жыл бұрын
@@Howie875 I’ll try again… if your outdoor coil is frosted up and near defrost cycle, and you lose power for a short time, the defrost timer loses its memory of the run time. So when power is back on, and the frost is still there if will not defrost for another 30,60,or 90 min. You have very little heat, and if conditions are causing frost build up, it will just run, run, you may have small amount of backup heat but that won’t heat your house without the proper heat pump capacity. I have seen this many times.
@Howie875
@Howie875 Жыл бұрын
@@tbone9405 Let me clarify. After the unit misses it's defrost cycle, it is true it will have some frost on it and won't work as good as it should. But as soon as it comes back on, the defrost timer starts to work because the coil is frosted over and then it will defrost on the next cycle, either 30, 60 or 90 minutes and then will work perfectly again. Just missing one defrost cycle will not add that much extra frost on the coil. The outdoor coil gets plenty of heat from the hot gas line during defrost and most systems have a defrost termination, because all the ice melts before the timed defrost is over and if you do not terminate it, you will trip the high-pressure switch because the condenser fan is off during defrost. So, it's only a 30, 60 or 90 minute period of reduced capacity. The only time I have seen frost or ice so thick that it would not respond properly to a defrost cycle is on a system that has run for many, many hours without a defrost.
@tbone9405
@tbone9405 Жыл бұрын
@@Howie875 This is how a defrost board works on a typical heat pump. The memory is on kept by voltage from the 24 volts coming from the hvac’s transformer, which is always on. The defrost is controlled on most heat pumps with a bimetallic thermostat, located in the outdoor unit attached to to the coil, it closes about 28 to 35 degrees. Then the defrost board starts counting minutes of run time, when it reaches 30,60 or 90 depending on the pin settings, it will initiate a defrost cycle, the mechanical bimetallic thermostat will typically open at 60 degrees. If power is lost the board will not keep the count. When power returns if will start over. The frost is still there because ambient temperature is below freezing at this point. Hopefully that helps. In more moisture prone areas this is problem. Also some power companies cause this problem, when they cycle the equipment for some programs. I was stating this issue for educational purposes, as I have experienced this in my many years of service, may not be a problem in your area, but someone may have experienced it. If your goal is to have the last word, then you can have it,lol
@Howie875
@Howie875 Жыл бұрын
@@tbone9405 I have a very clear understanding of a defrost cycle. I have many years' experience myself. The only time you lose your accumulated run time is when you lose complete power, and if your losing complete power often enough to continually lose your accumulated runtime and interfere with defrost then you probably won't have enough power to heat the conditioned space anyway, and that is not a heat pump problem, that is a power supply problem. A power cycling program, if wired correctly, should have no effect on the defrost memory. A correctly wired cycling device normally just cycles of the compressor by de energizing the compressor contactor, and the board should interpret this as the thermostat being normally satisfied. An incorrectly wired cycling device that opens either the hot or common from the transformer would kill the accumulated run time memory. All I am saying, respectably, is that one missed defrost cycle is a problem that will self-rectify itself at the very next defrost cycle, period. I hope we can agree on that.
@sheldon8115
@sheldon8115 Жыл бұрын
How does the board enable quiet mode on the unit 🙋🏼‍♂️
@rj.parker
@rj.parker Жыл бұрын
It stops the compressor when going into and out of defrost, waits 30 seconds, energizes the reversing valve and starts the compressor. It reduces the typical noise when operating the reversing valve with the compressor on.
@sheldon8115
@sheldon8115 Жыл бұрын
@@rj.parker thank you for your explanation. Very interesting
@NoorRefrigerationsystem
@NoorRefrigerationsystem Жыл бұрын
❤❤
@timrowe234
@timrowe234 Жыл бұрын
Good training guys! Please be an example to the young bucks and wear safety glasses when you’re face is right in front of electrical cabinet 😊 Stay safe
@tbone9405
@tbone9405 Жыл бұрын
Not ice, FROST!
@marcchipping4397
@marcchipping4397 Жыл бұрын
Long live gas boilers
@infohvacjanc4303
@infohvacjanc4303 11 ай бұрын
U are ama…
@borshardsd
@borshardsd Жыл бұрын
Ty kalos[?] team for another great video
@Bigmandoloco
@Bigmandoloco 4 ай бұрын
Gentlemen 🫡
Heat Pump Component Tour (In 3D)
20:51
HVAC School
Рет қаралды 139 М.
Heat Pumps - Preparing for Heating Season Part 1
29:32
HVAC School
Рет қаралды 25 М.
Кто круче, как думаешь?
00:44
МЯТНАЯ ФАНТА
Рет қаралды 6 МЛН
The IMPOSSIBLE Puzzle..
00:55
Stokes Twins
Рет қаралды 179 МЛН
Why no RONALDO?! 🤔⚽️
00:28
Celine Dept
Рет қаралды 81 МЛН
Heat Pump Secrets They Don't Want You to Know
11:55
Skill Builder
Рет қаралды 395 М.
Troubleshooting the Goodman Defrost Board
14:52
John Jennings
Рет қаралды 88 М.
Temperature Rise How to Measure it and Why it's Important
7:54
TAS Academy HVAC Training Videos
Рет қаралды 1,9 М.
Heat Pump Heating Reminders w/ Bert
31:07
HVAC School
Рет қаралды 52 М.
How Does the Heat Pump Defrost Cycle Work?
7:13
Energy Vanguard
Рет қаралды 4,1 М.
How Defrost Works on a Heat Pump! Explained Step by Step!
7:55
AC Service Tech LLC
Рет қаралды 115 М.
Heat Mode Charging and Testing Class
1:14:02
HVAC School
Рет қаралды 91 М.
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Jersey Mike HVAC
Рет қаралды 44 М.
Why is Everyone Talking about Heat Pumps?
9:15
JerryRigEverything
Рет қаралды 539 М.
What should I do if my heat pump freezes?
8:14
Taddy Digest
Рет қаралды 54 М.
Кто круче, как думаешь?
00:44
МЯТНАЯ ФАНТА
Рет қаралды 6 МЛН