Performing an Electrical Inspection According to the InterNACHI® SOP

  Рет қаралды 27,042

International Association of Certified Home Inspectors (InterNACHI)

International Association of Certified Home Inspectors (InterNACHI)

Күн бұрын

Пікірлер: 57
@NewYorksFinest1
@NewYorksFinest1 4 ай бұрын
Does the garage where the fuse box is need to have a smoke detector/carbon moxie sensor?
@internachi
@internachi 2 ай бұрын
Good question for the inspector.
@dwaynes5983
@dwaynes5983 11 ай бұрын
Thank you for great video. As for testing GFCI I use tester to show a real-world problem.
@internachi
@internachi 11 ай бұрын
Thanks for sharing!
@DansVlog
@DansVlog Жыл бұрын
If a panel does not have a main disconnect, isn’t there supposed to be no more than six throws?
@internachi
@internachi Жыл бұрын
Correct.
@geraldjoshschultz6100
@geraldjoshschultz6100 4 жыл бұрын
Neat video and very informative, thanks! However, he refers to being "grandfathered" in several times. InterNACHI drills into you, in several courses, that there is no such thing. CPIs are to inspect according to CURRENT standards and best practices. They refer to code a lot as well, which was another point that was to be avoided according to the InterNACHI coursework. Great information and nice folks, regardless. Thanks for the video!
@internachi
@internachi 4 жыл бұрын
Thanks for the info! Thank you for watching and commenting. More videos are at www.nachi.org/webinars
@MannyTheCook
@MannyTheCook 5 жыл бұрын
Missed that the circuit breakers were not labeled. The SOP does not require removal of the front panel cover, but double neutrals and aluminum wiring is a must have observation. I also check to make sure the breakers specially the A/C are the proper amperage, I have seen 60 amp breakers on heat pumps that require a maximum breaker of 35 amps this is considered unsafe.
@internachi
@internachi 5 жыл бұрын
Great feedback, Manuel. Agreed. Thanks for watching our videos.
@jamesmilton8990
@jamesmilton8990 5 жыл бұрын
I am a new inspector, and i have heard mutliple say removing the dead front is not required, but everyone seems to do it anyway. Is this just an unwritten rule that everyone does it even thought its not required? Is it that customers just expect it so inspectors do it?
@MannyTheCook
@MannyTheCook 5 жыл бұрын
Do not practice what you feel is a safety issue to you !
@internachi
@internachi 5 жыл бұрын
Hi, James. You're permitted to remove the dead front. The standards do not require its removal. But you may exceed the standards. It's up to you. Here's a good article on that point: www.nachi.org/exceed-or-not-exceed.htm
@kirkshirley1319
@kirkshirley1319 3 жыл бұрын
We don't use aluminum wire anymore, we use an Aluminum Alloy wire called AA8000. This alloy does not require the use of NOALOX. NEC does not require the use of NOALOX.
@internachi
@internachi 3 жыл бұрын
We don't use aluminum, but home inspectors look for it.
@Thefalltopics
@Thefalltopics 5 жыл бұрын
Gotta say, pretty concerned about how easily this guy places his hands inside the box... being comfortable with electricity is one thing, but for those new inspectors out there, this is not a good way to present the information... this stuff can kill you. Remember future Inspectors, always make safety a priority #1
@Joe_S.
@Joe_S. 5 жыл бұрын
Shaun Agreed. Immediate failure.
@Joe_S.
@Joe_S. 5 жыл бұрын
“Remember to be very, very careful. This is energized equipment.” [Just completed fingering the entire inside of the panel]
@aroofinspector7180
@aroofinspector7180 5 жыл бұрын
@@Joe_S.Hahaha, I was cringing the entire time
@internachi
@internachi 5 жыл бұрын
Good comment. Ray is a licensed electrician and he goes beyond the standards of practice, as most inspectors do.
@internachi
@internachi 5 жыл бұрын
Yep. We understand. But many home inspectors pull off the dead front, just like I did for 10,000 home inspections. I want to see inside. So did my client.
@ubaldoperez1539
@ubaldoperez1539 10 ай бұрын
Deox is not required per code and it’s optional, wire manufacturers coat their wire with deoxidazing c
@internachi
@internachi 7 ай бұрын
Thank you for watching and commenting.
@omnione12
@omnione12 2 жыл бұрын
How many hands did that Panal Have?
@internachi
@internachi Жыл бұрын
Not sure.
@educationpower1823
@educationpower1823 5 ай бұрын
It's amazing how cavalier the inspector is to being exposed to energized live parts. Good example of what not to encourage the public to do. Novalox is not a nec requirement since 1987 when the aluminum alloy was corrected.
@internachi
@internachi 5 ай бұрын
He's a master electrician.
@jpeters3031
@jpeters3031 5 жыл бұрын
Correct me if I am wrong but there are no requirements for Arc Fault or GFCI breakers in the panel. Also the panel cover is painted, should that be unpainted and grey?
@Gunny_101st
@Gunny_101st 5 жыл бұрын
AFCI and GFCI are only required after a certain age of house/panel. Check local listings. And there is nothing wrong with painting the exterior of a panel. Exterior only.
@internachi
@internachi 5 жыл бұрын
Hi, Jay. Good question. I think I understand your question. Home inspectors are not code inspectors. Many home inspectors inspect a home without much regard to the age of the house. That's because a defect is a defect. And since a defect could hurt someone, "grandfathering" is nearly meaningless.
@JSParadiso
@JSParadiso 2 жыл бұрын
You shouldn’t test gfci outlets using the built in test button. The test button does not produce an actual ground fault it just opens the gfci outlet circuit and does not necessarily confirm that the gfci is functioning correctly.
@dwaynes5983
@dwaynes5983 11 ай бұрын
Problem with a painted cover it's hard to see if a problem.
@CharlesBuell
@CharlesBuell 3 жыл бұрын
Deox is not required and if you can see it it is not installed properly. The ONLY recognized test of a GFCI or AFCI is the button on the device itself---never the button on a third party tester. A second recep for a countertop is not required unless it is over 9 square feet.
@internachi
@internachi 2 жыл бұрын
Got it.
@edwinjenkins1894
@edwinjenkins1894 2 жыл бұрын
@@internachi again, what does “got it” mean?
@Bscott-390
@Bscott-390 3 жыл бұрын
Dude not worried bout that deadfront being energized....
@internachi
@internachi 3 жыл бұрын
It's always a concern. Safety first. Go home at the end of the day - #1 rule.
@barryyeslow8267
@barryyeslow8267 3 жыл бұрын
FAIL: Subpanel must not have a main bonding jumper. Deox is not required by Code or cable manufacturer. FAIL: Main breaker in main panel should be marked "service disconnect". FAIL: there is no grounding locknut on the conduit in the main panel coming from the meter socket. FAIL: the conduit in the main panel is required to be sealed because it goes from exterior of building to interior of building. FAIL: no mention of grounding electrodes to ground rod or water pipe. GFCI test button on receptacle is only approved method of testing. Depending on code when installed, only receptacles within 6' of sink are required to be GFCI. Later codes require all countertop receptacles to be GFCI and/or AFCI protection.
@CharlesBuell
@CharlesBuell 3 жыл бұрын
grounding locknut only required if any of the concentric rings are left. Hard to tell but looks like they have all be removed.
@internachi
@internachi 2 жыл бұрын
Got it.
@edwinjenkins1894
@edwinjenkins1894 2 жыл бұрын
@@internachi Got what? Can you actually comment on the issues presented? Or are they all non issues? Is there a main bonding jumper present, is that the small green clamp and screw?
@BillC-64
@BillC-64 Жыл бұрын
@@edwinjenkins1894 Sub panels should not have the ground and neutral bonded together at any sub panels, only at the main. The claim "Subpanel must not have a main bonding jumper." The video clearly shows him pointing to the ground "bonded" to the enclosure. That is NOT a problem. That is correct. It's the next thing he says that's important. He then says it is "Isolated" from the neutral. That is also correct. As long as the neutral is isolated from the ground it's fine. This house is little odd in that their main breaker is in a separate location acting like an old disconnect switch, so it's that main breaker panel that will have the ground and neutral together.
@srichey7203
@srichey7203 2 жыл бұрын
I didnt see a legend
@internachi
@internachi 2 жыл бұрын
Right.
@grscklyr4dfbz
@grscklyr4dfbz 3 жыл бұрын
I can read! If you're going to do a slow crawl and read just as slowly I'm going elsewhere.
@internachi
@internachi 3 жыл бұрын
So sorry to see you go, grskly4dfbz.
@dallas5374
@dallas5374 2 жыл бұрын
Lots of misinformation in this video. Scary.
@internachi
@internachi 2 жыл бұрын
You can send them to ben@internachi.org.
@theoldtimelinexxx453
@theoldtimelinexxx453 5 ай бұрын
If I saw an inspector wearing a vest like that, I would take a shot of whiskey
@internachi
@internachi 5 ай бұрын
Bourbon.
Performing a Fireplace Inspection According to the InterNACHI® SOP
5:23
International Association of Certified Home Inspectors (InterNACHI)
Рет қаралды 8 М.
How to Perform an Electrical Inspection According to the InterNACHI® SOP
24:21
International Association of Certified Home Inspectors (InterNACHI)
Рет қаралды 94 М.
#behindthescenes @CrissaJackson
0:11
Happy Kelli
Рет қаралды 27 МЛН
Sigma girl VS Sigma Error girl 2  #shorts #sigma
0:27
Jin and Hattie
Рет қаралды 124 МЛН
УЛИЧНЫЕ МУЗЫКАНТЫ В СОЧИ 🤘🏻
0:33
РОК ЗАВОД
Рет қаралды 7 МЛН
Performing a Plumbing Inspection According to the InterNACHI® SOP
38:13
International Association of Certified Home Inspectors (InterNACHI)
Рет қаралды 27 М.
Performing a Home Inspection with Jeremiah Wheelersburg, CPI®
2:31:57
International Association of Certified Home Inspectors (InterNACHI)
Рет қаралды 53 М.
Electrical Rough-In Inspection (New Construction)
10:34
Performing a Heating Inspection According to the InterNACHI® SOP
10:59
International Association of Certified Home Inspectors (InterNACHI)
Рет қаралды 11 М.
How to Perform a Plumbing Inspection According to the InterNACHI® SOP
15:02
International Association of Certified Home Inspectors (InterNACHI)
Рет қаралды 57 М.
Tips on Inspecting Furnaces with CPI Lon Henderson
32:03
International Association of Certified Home Inspectors (InterNACHI)
Рет қаралды 23 М.
Common Electrical Defects Discovered During a Home Inspection
50:21
InterNACHI® Ben Gromicko
Рет қаралды 13 М.
Inspecting an Electrical Panel - How I Do It
11:49
HouseKnowHow
Рет қаралды 16 М.
#behindthescenes @CrissaJackson
0:11
Happy Kelli
Рет қаралды 27 МЛН