UK Ring Circuits (previously Ring Mains) for Socket Outlets

  Рет қаралды 475,756

John Ward (jwflame)

John Ward (jwflame)

Күн бұрын

Пікірлер: 760
@billpotter9716
@billpotter9716 4 жыл бұрын
Hello from the weird year 2020. I just watched Technology Connections explaining the U.S. electrical system. He casually explained that it's not nearly as weird as the U.K. ring mains. So that's why I am here. Great explanation. Yes, I now understand why it should be removed from the current standard.
@spike229
@spike229 4 жыл бұрын
ME TOO! - hello from the USA :)
@lilyydotdev
@lilyydotdev 4 жыл бұрын
lodno
@JoePro
@JoePro 4 жыл бұрын
I also looked this up after watching the Technology Connections video about our electrical system!
@BeingHumanProductions
@BeingHumanProductions 4 жыл бұрын
It was suggested to me after his video! Lol
@SoldrfMfortune
@SoldrfMfortune 4 жыл бұрын
Apparently KZbin is recommending the same videos to all of us. Greetings fellow curious cats!
@virginiahansen320
@virginiahansen320 4 жыл бұрын
Technology Connections brought me here!
@bobby_greene
@bobby_greene 4 жыл бұрын
I watched the same video from TC, but never took the initiative to follow through on my homework until the algorithm brought me here
@m4c1990
@m4c1990 4 жыл бұрын
So he doesn't have a Video on that topic? *Sadface*
@LeifNelandDk
@LeifNelandDk 4 жыл бұрын
You could have have individual fuses for the two ends of the ring to discover if the ring is broken. But that would only be for the live, as the neutral is not fused anyway.
@privacyvalued4134
@privacyvalued4134 4 жыл бұрын
Yup! I almost fell asleep though listening to this guy. The lip smacking at the end woke me up though.
@wouterkuit3508
@wouterkuit3508 3 жыл бұрын
It really was prompted by CJR electrical’s videos where he keeps going on about testing ring circuits, but before that I had seen TC’s video too combined that led me here 🙂
@sly1968si
@sly1968si 2 жыл бұрын
I was taught the virtues of the ring mains when I left school in the 80's and did my apprenticeship, just before moving into IT, and thought it was a great idea. Now in my 50's and having moved into various old properties (and always checking for signs of heat/loose connections in electrical outlets) this video has explained so much. Well worth 16 minutes of my life to totally change my mind as to the safety of electrical circuits.
@Goffic
@Goffic 8 жыл бұрын
By far and away the most lucid explanation I have ever seen. Something I've always thought should be fairly simple has always had an air of complex, don't touch, experts only etc. and John's explanation is so easy to absorb. Your a genius JW.
@peterwilson1831
@peterwilson1831 5 жыл бұрын
I don't know anything about electrics and to be honest i'm not sure how i ended up here, but i find this guy strangely captivating. I'm now considering installing a new consumer unit and ring main for no reason other than John Ward showed me how.
@cbcdesign001
@cbcdesign001 3 жыл бұрын
I know nothing about Rockets but I saw a video on KZbin and I am now considering going into outer space. Lets hope Peter Wilson was not serious.
@bigsteve6729
@bigsteve6729 3 жыл бұрын
Don't listen to the naysayers, I've seen sparks that have an IQ of no more than 50 and seem to do fine. You can lick your finger and touch the bus bar to see if it's live just do it fast, if it goes DADADADADADADADADA up your arm and you tense up it's live. Just kidding... Obviously... I did mine but I was an apprentice for two years and assisted on many a board change, and I have mild ocd the wiring is absolutely beautiful it took me absolutely ages and no one gets to appreciate it :(.
@olegs79
@olegs79 4 жыл бұрын
The Canadian Electrical code still allows ring circuits in 2015. Never used one, never seen one and didn't even know what it was until I watched this video. Great video.
@YTDmeyez
@YTDmeyez 2 жыл бұрын
Fantastic Explanation, 6 years later your video was recommended to me. All praise the algorithm.
@ForViewingOnly
@ForViewingOnly 2 жыл бұрын
Excellent teacher, excellent channel. Thanks JW. I had a 32A ring circuit in an old outbuilding, and rodents had gotten into the walls, chewed on the wires and the RCD kept tripping. I expected the worst, that the circuit had been destroyed, but the electrician isolated and removed the chewed section and I was delighted to end up with two 16A radial circuits that tested fine and with roughly the same number of sockets on each. Could have been worse.
@TheAdwatson
@TheAdwatson 3 жыл бұрын
I am a retired electronics tech who actually did some rewiring in my father's house in the UK. The old, lead-covered cable under the floorboards was beautifully layed out and neatly dressed, but as soon as it was disturbed the old rubber insulation disintegrated. I am guilty of incorporating "a borrowed neutral" into a three-way stair lighting circuit, but I am sure that the house has been completely rewired since my father sold it in the late 1980s. I could not understand the need for a ring circuit, primarily because I understood the risk of overloading in the event of ring discontinuity. This is the first video I have encountered that explains why I was correct about ring circuits.
@rayhindle642
@rayhindle642 3 жыл бұрын
Thanks JW you brought me back up to speed, having done house wiring back at college as part of my apprenticeship I went into electronics and only ever used household electrics when needing to do my own, I will keep this video as a reminder. Thanks again. Ray.
@HelloKittyFanMan.
@HelloKittyFanMan. 4 жыл бұрын
Who else came here after Technology Connections (06/20) drove you to a search?
@juppster5694
@juppster5694 4 жыл бұрын
Yep, me also!
@RaymondHng
@RaymondHng 4 жыл бұрын
I've seen this two years ago.
@devinleahy360
@devinleahy360 4 жыл бұрын
yes i did
@HelloKittyFanMan.
@HelloKittyFanMan. 4 жыл бұрын
So then it's a no for you, @@usingthecharlim.
@KeithStarr696969
@KeithStarr696969 4 жыл бұрын
Here as well from Technology Connections
@RAndrewNeal
@RAndrewNeal 3 жыл бұрын
When I first heard about these, I thought they were relics of the past. I was _shocked_ (lol) to find out that they're still in use today, and you've explained very clearly to me how they work. I wouldn't want one in my house; good thing everything here in the States is what you refer to as radial.
@jwflame
@jwflame 3 жыл бұрын
They should be relics of the past, unfortunately plenty of people still insist on installing them.
@RAndrewNeal
@RAndrewNeal 3 жыл бұрын
@@jwflame Why don't they just repeal the standard for new installations? We have plenty of old wiring over here that, if worked on by a certified electrician (on the record), must be updated to meet current standards.
@paulbristow8485
@paulbristow8485 7 жыл бұрын
You described how to wire a ring main up perfectly clear,I understood it perfect! Thank you !
@seymourpro6097
@seymourpro6097 6 жыл бұрын
The ring main was introduced after a long and hard war (WW2) and materials were in short supply, previously houses with electricity had few 15A sockets each wired as a spur from a fuse box. With the advent of 13a fused plugs and ring mains (as then called) with the limited and perhaps rationed cable could be used for more houses than the same amount of copper used as single socket radial circuits. Whether a ring circuit NOW represents the best practice doesn't matter because there are probably 20 million ring circuits in existance and most electricians will meet them on a daily basis.
@daklakdigital3691
@daklakdigital3691 3 жыл бұрын
Singapore, and a few other Commonwealth countries, use Ring Whatevers. Here in VietNam Singapore invested highfises are equipped wigh clunky UK Plugs although not Ring Mains. We also use US-style flat in plugs, as well as Chinese plugs. When travelling i prefer the universal connector that comprises 2 wires wiith bared ends and fit almost anything!
@mikenco
@mikenco Жыл бұрын
I watched this when it was new. I installed a garden building on my own land for my office, it was all wired using advice from this vid without ring circuits, but higher rated cable (6mm). 5 years later, it all still works perfectly. even with a 2.7Kw heater running off it at one point, as well as a computer and LED lighting. BTW, I also have a spur direct from the consumer unit for my Ring doorbell. All common sense stuff.
@icarossavvides2641
@icarossavvides2641 Жыл бұрын
A spur off the CU for a door bell? That's got to be a first! 🤣🤣🤣🤣
@trelosenario
@trelosenario 4 жыл бұрын
Now that i moved to london i found your videos very helpfull understanting uk domestic instalations. Thank you very very much.
@LB-gr5se
@LB-gr5se 4 жыл бұрын
Where have you come from to the UK? Are you working as an electrician here, and if so what country did you learn your trade? Thanks
@Josh-vp1hw
@Josh-vp1hw 4 жыл бұрын
I will never get over how differently you Electricians in the U.K. Do things differently than us Electricians in the States. Though I know you are professional tradesmen and take great skill in your craft , and know what you are doing, something like that would never be allowed over here. Always enjoy watching the way things are done over there. Wasn't intending to be disrespectful if I was, anyways cheers from the States.
@danielpayne7368
@danielpayne7368 4 жыл бұрын
Great video. Clear explanation. Currently studying this on my Level 1 Diploma course. Makes so much more sense to install separate radial circuits throughout a domestic dwelling. Cheers!
@brianlopez8855
@brianlopez8855 Жыл бұрын
Crystal clear and comprehensive as always. Thanks.
@Twonkadoodle
@Twonkadoodle 4 жыл бұрын
Crystal clear and very much appreciated , why can’t all d I Y videos be made like this . Great job
@lohkebeats
@lohkebeats 4 ай бұрын
Came for the education, stayed for the shade this man had to throw on ring mains 😂 seriously though, very clear and useful video!
@nomadicsoul34
@nomadicsoul34 7 жыл бұрын
Fairly strong opinions being expressed at the beginning. You certainly aren't shy !
@fieldsofomagh
@fieldsofomagh 8 жыл бұрын
Old ways die hard. Ring circuits usually reliable enough.Great variety of wiring globally.Protection way better now than it used to be. A neighbour called in about faulty socket years ago. Upon investigation at the fusebox, there in place of a fuse was a 6 inch nail glowing red hot. Necessity is the mother of house fires.
@UncaBeeTV
@UncaBeeTV 3 жыл бұрын
As an American with an electrical background, I've always been interested in what a UK "ring circuit" actually is, and how it works. This is the first guy I've encountered who explained it clearly in a way I understood. Thanks for that. It does seem like a simple enough concept, but I can also see why it was probably never adopted over here, because of extra wire, expense, etc.
@UncaBeeTV
@UncaBeeTV 3 жыл бұрын
I guess now I need to understand more about what a Consumer Unit is/does.
@calmeilles
@calmeilles 3 жыл бұрын
@@UncaBeeTV UK consumer unit == US circuit breaker panel. The physical engineering is slightly different but the function is exactly the same.
@tedlahm5740
@tedlahm5740 Жыл бұрын
Very clear concise explanation of ring circuit.
@sbusweb
@sbusweb 8 жыл бұрын
I heard, and believe story that, those 2* single sockets as spurs, were often changed to double-sockets (e.g. those conversion sockets)), thereby overloading the protection requirements for unfused spurs. So, regulations changed to disallow that configuration.
@cglees
@cglees 4 жыл бұрын
13x2=......?
@sbusweb
@sbusweb 4 жыл бұрын
@@cglees 26 =) which, is usally ok for a 2.5mm cable unless thoroughly insulated. Diversity says in pratice this double-socket-spur (or indeed, 2 single sockets as spur) is allowable. However, for some reason, 2-sockets-to-1-plug adapters are allowed un-fused, which seems kind of silly!.
@_______DR_______
@_______DR_______ 5 жыл бұрын
My employer loves a Ring circuit, they'd put one in for any socket circuit consisting of 2 or more double sockets. I personally fail to see the point most of the time. It does make sense to have a 32A circuit for a kitchen/utility and I guess the little bit of extra testing involved still beats fitting a load of sockets with two 4mm cables in them. I remember one of my college teachers saying about how he'd converted a lighting circuit wired in 1mm into a ring because it was on a 10A MCB and the cables were all buried in insulation, bet that was a head scratcher for the next guy to work on it 😂
@HelloKittyFanMan.
@HelloKittyFanMan. 4 жыл бұрын
It's not Ring, like the new video doorbell button; just "ring," the generic object.
@001Neal100
@001Neal100 7 жыл бұрын
4mm cable is harder to pull through, more expensive to buy and the wires are more difficult to screw 2 into the back of the terminals on socket oulets. Just a few disadvantages of radial to balance things a bit.
@jwflame
@jwflame 7 жыл бұрын
Radial circuits don't have to be 32A, or use 4mm² wire.
@corydorastube
@corydorastube 4 жыл бұрын
Cheap, easy and dirty. Typical UK.
@jahcoma
@jahcoma Жыл бұрын
I’ve put a few new sockets on existing 32amp 4mm wire radial no problems love it.
@strangelove9608
@strangelove9608 3 жыл бұрын
I shoud not say this, or even go there, but the holy grail of all audipophile nutters is their own spur and somehow the magic electricity is different and everything is better with a dedicated spur. Loved the video, learnt lots please ignore previous comment 8) .
@camjohnson2004
@camjohnson2004 Жыл бұрын
In Australia we use Daisy Chain setup for each circuit. for GPO's max per daisy chain circuit is 10A, so every GPO on that daisy chain can't exceed 10A total. In Aus you will usually find 3-4 circuits for GPO's Usually the bedrooms and lounge room will be on 1, Kitchen, depending on how many high voltage devices are to be used (Microwave, Fridge, Freezer, kettle, toaster etc you will have either 1 or 2 circuits for the Kitchen. Dining room and Bathroom will occupy 1 circuit and then you will have your outdoor appliances such as Laundry Lights will be on Separate loop with 10A max per single circuit, Hot Water heater on a 40-60A circuit, Electric stove and cooktops for kitchens will be on a a shared 40-60A circuit separate to the GPO's. This makes up your general house power. For Additional appliances (EV charging, Air Conditioning) dedicated circuits are required for each and amps per circuit will be based on the needs for the appliance +10%.
@icarossavvides2641
@icarossavvides2641 Жыл бұрын
And whats a "GPO" in Australian?
@camjohnson2004
@camjohnson2004 Жыл бұрын
​@@icarossavvides2641GPO means general power outlet. In other words where you plug your appliances into.
@melelms9948
@melelms9948 20 күн бұрын
Thank you John, really big help, explained very clearly.
@trueriver1950
@trueriver1950 5 жыл бұрын
The most compelling reason for ring mains/circuits as compared with separate cabling to each socket (as in the forties) is that they give the user maximum choice in where to plug in portable appliances, without increasing the amount of wiring in proportion to the number of outlets. The intention is that in a room with plentiful sockets there will not be any need for long leads on portable equipment (trip hazards) or multi way adaptors (which can be a fire hazard). Why not use a radial? The advantage of the ring over the radial is that you can test for loop resistance. This detects whether there are any poor connections at any point in the ring, which could lead to a fire risk. You can test this at any point in the ring, without visiting all the sockets. This test is the reason for most of the rules about spurs. Secondly, if a poor connection does develop, it's less likely to cause a fire unless a second poor connection arises. This is because most of the power will flow to the socket that's in use by the line of least resistance. The dodgy socket gets hot when it is used, and hopefully the consumer will notice. That socket does not get hot when other sockets are in use (unless there are TWO dodgy connections) In contrast, in a radial, if there is a poor connection at an unused socket, that socket will get hot whenever sockets are used that are further from the CU. If that socket is rarely used, or is a permanently plugged in appliance, the consumer is unlikely to notice the hot socket till it bursts into flame. So the extra cabling back to the CU is for testing and safety. There is a coherent case to support this You clearly feel the the disadvantages outweigh those advantages, but it's only fair to mention that there is some sense to the design. It's not totally daft, as you seen to imply
@madaddams
@madaddams 3 жыл бұрын
I only did a short course as part of a mechanical engineering day release course many years ago, so my knowledge is limited as since then I've only done DIY electrical work, appliance repairs adding the odd spur, wiring up sheds, or simple light circuits. I'm old enough to remember the days when the previous wiring circuits were still used in many older houses, before these came in; if I remember right, sockets were on the same type of circuit as lights are now (can't remember what they're called), and people would often run half a dozen things, radio, lamp, iron etc, off the light socket on the ceiling. Overload became a serious problem back then, and we had warnings about it on the tv. Now, on a circuit such as your diagram, a person could have a 12 way tower, plus half a dozen USBs on each socket, and from those towers, further extension leads. There are no warnings about overload! I know my example is at the extreme end but, even though many things draw much less power than they used to, surely we're heading towards some serious problems. Circuit breakers are so good these days, that I've almost forgotten how to change a fuse in a plug, but are they really good enough, that we can safely keep on plugging things in the way we do? Isn't it time we had warnings on the tv again? Or am I worried about nothing?
@vtbn53
@vtbn53 5 жыл бұрын
I could have done with a ring circuit to power my twin 2400W boiler elements for my still. I actually like the concept. Cheaper than having 20 amp circuitry installed.
@Dog-whisperer7494
@Dog-whisperer7494 9 ай бұрын
Great explanation John , genuinely you can have the same number of spurs as you have sockets on the ring , in theory you can have as many sockets as you like as long as you don’t exceed a certain floor area of a 100 square metre. But as you rightly say it comes down to common sense. Till recently a domestic property ie a two story house had three ring mains , and two lighting circuits,one for the ground floor one for the upper floor and the kitchen had its own ring main because there would be quite a few high power appliances such as fridge freezer washing machines tumbler dryers microwave , electric toaster kettle food mixer and if you could afford it a dishwasher. Personally I think ringmains still have their place . In houses . Because if you have a fault on say the ground floor ring you still have the upstairs ring as well with the lights .
@jonwilkins192
@jonwilkins192 4 жыл бұрын
Hello John, I'm finding your videos to be an excellent learning resource, thank you! Could you, at some time, please do one on adding a garage consumer unit?
@MrSJT
@MrSJT 4 жыл бұрын
I defo use ring mains for kitchen appliances with a few isolators in a cupboard so that it becomes a balanced load on cables and hidden away from worktops make a neater job, I would use it to feed for example, cooker hood, hob ignitor, dishwasher, waste disposal, hot tap, bolier. Fridge will be on its own RCBO circuit for obvious reasons such as going on holiday you don't want some thing to trip the RCD and affect the fridge if it wasn't wired in separately.
@jonathanbignall1198
@jonathanbignall1198 3 жыл бұрын
Very interesting thanks John. I often wondered why the ring circuit concept was introduced.
@lynx911able
@lynx911able 5 жыл бұрын
Always wired 30 or 32A with 4mm2, you are on the safe side in any scenario. For bedrooms you could use 2.5mm2 with 20A MCB which is more than enough for average house
@bigsteve6729
@bigsteve6729 3 жыл бұрын
Cost you a fortune in cable would have to take half a brick depth out to cap that up 🤣
@Roq-stone
@Roq-stone 5 жыл бұрын
How’d you get the current to pass through the hole 7:06?
@brendansimmons3435
@brendansimmons3435 4 жыл бұрын
albert sparks hopefully not it’s the cpc
@credibility63
@credibility63 4 жыл бұрын
Because it's a ring it will still offer protection from the other side. If it was a radial circuit it would be a safety issue. Always try not to have punched holes in your cpc
@lawrencedoliveiro9104
@lawrencedoliveiro9104 4 жыл бұрын
Remember, the paper is insulating. So the hole is actually a break in the insulation. Logically, it must conduct.
@pyrioncelendil
@pyrioncelendil 4 жыл бұрын
Magnetic induction.
@Roq-stone
@Roq-stone 4 жыл бұрын
Lawrence D’Oliveiro 😂🤣😂🤣😂🤣
@zedman442
@zedman442 8 жыл бұрын
20A radials for the win. Chances are most houses now have some sort of radial circuit from a spur...off a spur off a spur. Swap the MCB for a 20A to be on the safe side.
@HelloKittyFanMan.
@HelloKittyFanMan. 4 жыл бұрын
* Spur FROM a spur FROM a spur.
@CurmudgeonExtraordinaire
@CurmudgeonExtraordinaire 4 жыл бұрын
Come to think of it, I use a similar "circuit design" on my electrical fence (that adds extra incentive for my dogs to not try to go through the yard fence). If a wire gets broken, both sections of the fence still have power. I can see a reason why the ring circuit could have an advantage from a fault tolerance standpoint, but I would still size the wire so that even if the ring was broken, it could still handle as much current as the circuit breaker for the circuit. I never rely on a house that I buy to be wired *correctly* since a previous owner might have thought he was competent to do DIY electrical work (and he wasn't) or the builder was using somewhat unskilled workers who didn't particularly care whether they did it right for the wiring installation. I've seen cases where 110VAC was on the *ground* at an outlet because some wires were touching in an outlet box. To be fair though, this was an old house which was originally built without electricity and there were still remnants of previous electrical wiring designs. There were places in the attic where some of the old asbestos and tar wiring insulation was still around (although it wasn't being used). There were also some remnants of the old "knob-and-tube" style where wires didn't have insulation on them and bare wires were run while being separated from contact with the materials of the house (or each other) by porcelain knob and tube insulations.
@lindosland
@lindosland 2 жыл бұрын
I'd like to suggest that a ring main does have an advantage in that it halves the resistance to the furthest socket, while using easier to handle cable. Also in most situations it begins down one side of a house or room and returns along the other, enabling sockets on both sides. The alternative of two radials would double the resistance by comparison unless 5mm cable were used. Resistance can matter especially when using things like grills and halogen ovens where a small drop in voltage results in a large drop in radiant heat (I experienced this problem). It's true that electronic devices are generally neither large current devices, nor very sensitive to voltage, but if you are feeding two radials down each side of a room, why not just join the ends and complete a ring, halving the resistance. I agree that the potential to overload the ring cable with loads near the consumer unit makes a nonsense of the ring in principal when it comes to pushing 26A cable to 32A, but again, in practice, the ring will often begin some distance from the area it feeds, such that the feed to every socket has a reasonably balanced feed, the initial long feeds serving to balance the current sharing. One thing that surprises me is that you, like others, work on the assumption that the cable is required to carry only 32A worst case, when in reality MCBs will sustain around 1.5 times their rating for a long time without tripping (depending on the type of MCB), so the cable has to take 48A in fact. I think the sensible answer is to simply require that all circuits using 2.5mm cable have a 20A MCB while all circuits or spurs using 4mm cable can have a 32A MCB. With the cables thus protected at source no further rules are needed regarding spurs or number of sockets. In a bungalow my preferred method is to take spurs in 4mm cable down to each socket from junction boxes, from a 2.5mm ring in the loft that has no sockets directly on it, leaving the ring uncut where possible as it runs through the boxes. This makes life easier in many ways - no threading of two cables down inside plastic conduit (which I always use), no need to put two wires into each socket terminal, and easy access to junction boxes for adding sockets. Plus less opportunity for arcing with less joins. Of course this works well in a floored loft with easy access to the edges, but not perhaps in one piled high with glass fibre insulation. One reason that the ring worked better in the past was that it served fewer sockets, whereas today a lot of extra cable is wasted looping down the wall and back up (wiring across walls from socket to socket is not encouraged because of the increased risk of drilling into cables when fixing to walls.) My solution of using 4mm cable down from the ring shortens the cable length in the ring and is ideal in every respect.
@jeremykemp3782
@jeremykemp3782 Жыл бұрын
You are missing the point, if there is a break in the cable nobody knows and nothing trips and everything keeps working. including electric oiled radiators if some lost their gas boiler for example. The wire would then burn and cause a fire!!!! Putting in a smaller fuse like you suggest would then limit people who would actually need the amperage one day for an electric heater or two because it would trip. A 4mm radial cable with a 32 amp fuse is a perfect solution, one for upstairs and one for downstairs. Obviously a separate one for an electric shower or an electric oven/cooker. 10mm or whatever they require.
@lindosland
@lindosland Жыл бұрын
@@jeremykemp3782 The days of electric resistive heaters are surely over - too expensive to run and too wasteful of valuable power. My five air to air heat pumps heat my large bungalow taking only 400W each max, all run off the ring circuits with no extra wiring. With a COP of 5.5 they deliver 5.5 kW of heating for every 1kW used (Mitsubishi, cost £800 each, £1500 istalled) Electric shower is also not a good idea - prefer 3kWimmersion heater on cheap rate. Modern fan heaters are 2kW, not 3 as used to be the case, and two fan heaters will run happily off a 20A 2.5mm circuit. There's also something to be said for a lower trip current - it avoids the need to rate the cable for 1.5 times the nominal MCB value. In practice MCBs rarely trip even on overload, and wiring rarely overheats to anything like the point of burning. And MCBs are easily reset if they do trip, alerting the user to the need to plug less in.
@dawkinsm
@dawkinsm 4 жыл бұрын
Very interesting as always but twice as amusing 👍😃 love your commentary on this video!
@mattl9702
@mattl9702 3 жыл бұрын
Great video! You’d make a fantastic news “READER” the last word of each of your sentences are very “PRONOUNCED” non the less, you really seem to know your “SUBJECT”
@joeambaye8681
@joeambaye8681 2 жыл бұрын
Thanks for an excellent factual presentation 👍
@steveide2448
@steveide2448 Жыл бұрын
Excellent explanation thanks, needed a refresher.
@Danvito13
@Danvito13 2 жыл бұрын
Major newsreader vibes but I learnt a lot, thanks!
@adrianwheaton4408
@adrianwheaton4408 5 жыл бұрын
I agree with John ring mains can be potentially dangerous I had a situation where I did some work on a property I tested the ring a couple of weeks before when I changed the distribution board and then I went back to add a socket to find the ring now wasn't continuous luckily there was a freshly decorated wall where a socket looked as if it was tampered with as it was put back on wonky so I pulled the socket off to my surprise there was a loose connection to get to the point I filled out a cert on that property a couple of weeks before now if I never went back that ring circuit could still be a potential danger
@Pandafaust11
@Pandafaust11 3 жыл бұрын
Came here from Delroy. As an Aussie sparky I found ring circuits weird but probably only still in the standard because it exists in old homes. A lot like engineers still having to deal with imperial machine threads and sizes.
@pauldavis2108
@pauldavis2108 4 жыл бұрын
The one big saftey advantage I can see with a ring circuit would be in the case of a connection going resistive or resistive break. Connections going resistive is where fires start. The connection becomes very hot due to the voltage drop across the unintentional resistance. In the case of a ring circuit though since power is still supplied from the other end the resistive connection will see no voltage drop and no power dissipation.
@UCCLdIk6R5ECGtaGm7oqO-TQ
@UCCLdIk6R5ECGtaGm7oqO-TQ 8 жыл бұрын
I'm not big fan of ring circuits, but there is the benefit that the overall resistance of the circuit is reduced considerably when you have that last leg back. I mean, it does effectively nearly double the effective CSA of the conductor, and thus capacity of the circuit, by just having that (often short) return leg. I could see there being a lot more burnt-up sockets/cables if radials with many sockets on them where more common, as connections inevitably loosen over time, resistance (impedance?) increases, and then folk go and plug electric heaters and the like into them. I know regular testing should defeat this possibility, but really, how often do people actually get their installations tested? In my experience, the answer is: much, much less than they should.
@m.s.8112
@m.s.8112 4 жыл бұрын
Exactly my opinion! Leaving the ring complete as is it is and reducing the breaker to 25 A would be the best option with the safety add on that a broken wire would not be able do result in an overload. Long radials always have voltage drop issues at their endings.
@bigsteve6729
@bigsteve6729 3 жыл бұрын
Very comprehensive thank you, I thought it was a great point about a wire in the ring losing connection and creating a scenario where the circuit is able to draw more than the rated 26 amp. Even worse if they are double sockets which is way more likely. Anyone is able to test this with a simple continuity check.
@richardghost5701
@richardghost5701 3 ай бұрын
Ace video with great explanation
@PhilsFlicks77
@PhilsFlicks77 2 жыл бұрын
Thank you John. That was very clear and well explained :-)
@gapster77
@gapster77 4 жыл бұрын
I come from a industrial/commercial installation background 15yrs+ , but for the last 5yrs I have been working in Domestic. I was recently instructed by my boss to add a F.C.U. in a garage for a new Electric Door. When I arrived I found the existing Socket within the Garage that I was to spur off of, was itself a spurred off of a Socket Outlet on the adjoining Kitchen Ring. I called my Boss and expressed that I felt it would be better practice to either add a leg to the existing spurred socket to make it a part of the ring main, or to add a F.C.U. to the Ring within the Kitchen, which could then feed this existing spurred Garage Socket Outlet, and then spur off of it to feed the new F.C.U. for the Garage Door. My Boss said it was fine because it was an F.C.U. I disagreed, and expressed that it was about protecting the cable leaving the Kitchen Ring, and that the F.C.U. was only protecting anything it gave power to. I’m sure I was right, am I?
@ishkebab
@ishkebab 7 жыл бұрын
The problem with a 4mm2 radial is that the ccc drops to only 30 amps installed in trunking reference method B if cables entering db are installed using 50x50mm trunking as an example which is quite common if in a garage etc. You can't really omit overload protection on a socket radial circuit protected by a 32amp mcb if say it was a kitchen radial. So there are disadvantages in using this method.
@palanivisu1344
@palanivisu1344 4 жыл бұрын
Let's see what kind of shamble this are , brilliant the way you mentioned 😀
@anonamouse5917
@anonamouse5917 2 жыл бұрын
I guess it made sense to the committee in the '40s. It does not make sense today. At least you use an efficient voltage. 120V requires way too much copper.
@benaldi2
@benaldi2 3 жыл бұрын
Thanks for your time.
@anthonyschofield7807
@anthonyschofield7807 3 жыл бұрын
I have split many ring mains into two radials on 25 amp RCBOs,usually due to cumulative earth leakage,the bane of all RCD protected circuits with today’s ever increasing electronic supplies
@notanf1show237
@notanf1show237 Жыл бұрын
Im actually working in a house that has the lights wired by individual wires from the board to every room, it was built in Ireland in the late 40s and has never been updated most if the cable is vir and falls apart if you look at it
@nrg-5003
@nrg-5003 3 жыл бұрын
16:00 i Loved your hint of frustration there, rings have no place in this day and age and if the next edition or regulation want to do something sensible and worthwhile then they should ban these massively outdated ridiculous circuits.
@PhilReynoldsLondonGeek
@PhilReynoldsLondonGeek 8 жыл бұрын
Knew nothing of the circuits in our first house. Second had a ring circuit on each floor. Third, one for front four rooms, one for back three (a bedroom plus the kitchen and utility). All three bedrooms had one socket on the ring and one on a spur. There was, bizarrely, a 2A socket attached in one of them as well. This ring was later properly extended as more sockets were needed. My own places, single ring in first flat, two likely rings in second - one covered only the kitchen, the other all the rest. Third and fourth flats had single rings, current bungalow has two probable rings - once again one is just for the kitchen.
@davidca96
@davidca96 6 жыл бұрын
I never knew the UK did this, its a good idea in theory but the fact that its so easy to end up putting too many amps through the conductor from a single point failure is scary.
@3rdalbum
@3rdalbum 4 жыл бұрын
Note that 26 amps is what the cable is intended to carry, but the standard for manufacturing that cable is probably that it can handle 32 amps without getting hot enough to start a fire in any of the materials it's likely to be in contact with. (And the materials used in houses are probably also regulated so that they cannot ignite from the temperature that your house wiring is likely to get to...) I'm pretty sure I broke the loop at one point (my baton light in the garage fell down in a storm and I snipped the wires off) and it was that way for months and nothing bad happened. I did hurry up and replace it when I read about the existence of ring circuits though! But nothing bad happened.
@stefantrethan
@stefantrethan 8 жыл бұрын
Thanks for explaining this peculiar arrangement. Around here you are not allowed to rely on a fuse at the end to protect a wire, ever. It has to be at the beginning. The only exception is short proof wire (with thicker insulation), for example the spur feeding a fuse or circuit breaker from a bus bar.
@UCCLdIk6R5ECGtaGm7oqO-TQ
@UCCLdIk6R5ECGtaGm7oqO-TQ 8 жыл бұрын
The fuse in the plug that plugs into the sockets isn't to protect the circuit, it's to protect the cable on the plug connected to whatever device you're plugging in. It's the distribution board/consumer unit MCB device that protects the installation circuit wiring. This makes sense as, if your installation circuit has a 32A capability, and you plug some little table lamp into a socket on that circuit, then you don't want to have to have a 32A capable flex on that lamp alongside a 32A capable lamp holder, and 32A rated switch. Rather, you design them with say, 0.5mm2 flex, 5A rated switch, 5A rated lamp holder, and install a 3A fuse into the plug to limit the maximum current the device can draw in order to protect the device from ever being able to overload the hardware it's constructed of. British socket outlets are designed to handle 13A generally (3120 watts @ 240V), and so the largest fuses available for the plugs that plug into them are 13A. This prevents there ever being the possibility of a fault on the plugged-in device/cable being able to draw current greater than the installation socket can handle, which is important when they're commonly connected to 32A @ 240V (7,680 watts) circuits.
@stefantrethan
@stefantrethan 8 жыл бұрын
The point is that spurs will have a 32A breaker on a 2.5mm^2 wire, John makes that point at 11:00.
@TheChipmunk2008
@TheChipmunk2008 8 жыл бұрын
A spur will never be loaded to more than 26 amps. And despite what they SAY, 2.5mm will take 32 amps quite happily, it just exceeds the design temperature. That's why we have margins of safety
@terryhayward7905
@terryhayward7905 Жыл бұрын
The one point that you did not mention is that the earth connection must also go to a point on the socket back box, even the plastic back boxes will have a terminal for that.
@Phil_AKA_ThundyUK
@Phil_AKA_ThundyUK Жыл бұрын
Cheers JW love your videos.
@ExtremeEngineering
@ExtremeEngineering 6 жыл бұрын
below comment is not good john but i appreciate you about your work because i know that what hard work are required for sharing some knowledge for others thanks john
@theCybershot123
@theCybershot123 5 жыл бұрын
Thanks again for a very important subject
@xxhellspawnedxx
@xxhellspawnedxx 2 жыл бұрын
Electrically it's the same to attach a spur to the MCB directly as it is to attach it to a socket out on the ring, but isn't the issue that modern MCB's have two ports on either side, designed for one wire each? There is space to jam more wires in there for sure, especially if you use smaller gauge wires, but you won't necessarily get sufficient contact and grip on all your wires when you start doubling or tripling them up in the ports. Just a thought as to why people mind this sort of addition to a circuit.
@craydonproudman6393
@craydonproudman6393 3 жыл бұрын
Hello John, love the videos, crystal clear and based in reality. I'm a basic DIY'er but want to do things safely and in accordance with the standards/guidance where possible. I live in a victorian terraced house in Wales. It has a modern CU but what I'm not sure about is whether it has a ring or radial circuit. Is there an easy way to find out? I've had a look at a couple of other videos but am left confused... Many thanks, Craydon
@3scottiedogs
@3scottiedogs 8 жыл бұрын
Hello John. Thanks for all the videos. Have you though about a short intro on the organ at the start Monty Pythonesque styleeeeee. Good Luck lad
@jrr851
@jrr851 4 жыл бұрын
I watch technology connections, but the KZbin algo started feeding me videos of UK electrical contractors. I found it very interesting comparing to what we have in the US. Ring circuits seem like insanity to me from US standards. Also. 32a on 14awg wire at 240v seems like an insane amount of power to have at a regular power point. Considering the average us outlet is 15A at 120v for a maximum of 1800w. 32a at 240v is 7200w. That is madness to me.
@Cjbx11
@Cjbx11 4 жыл бұрын
This is why all U.K. plugs contain a fuse which are typically rated at 3, 5, 10 or a maximum of 13A. The maximum loading on a U.K. socket is 3KW which is approximately 12amps.
@appealingpit
@appealingpit 2 жыл бұрын
Very interesting wiring structure
@AlexA-zg7mq
@AlexA-zg7mq Жыл бұрын
So the wire comes out the consumer unit to start the ring, but you just also return another 2.5mm wire back into the unit. Do you need to connect the wires to the same terminals in the consumer unit
@alashiya9536
@alashiya9536 8 ай бұрын
yes
@kite7214
@kite7214 5 жыл бұрын
Thanks John. Simple explanation. Much appreciated. Keith
@RandyDarkshade2
@RandyDarkshade2 8 жыл бұрын
For some reason my 1 bedroom flat has three socket circuits. I have three 32A breakers in my consumer unit all labelled "sockets" I have never figured out why the sparky who wired the flat decided to do that lol. I am not sure if I have radial or ring. I wanted to add a socket in the bedroom and when I removed an existing socket it only had one cable going to it.
@sbusweb
@sbusweb 8 жыл бұрын
Very often when adding many more sockets, the most convenient approach is to put them all on a new circuit, rather than disturbing existing wiring... Hence many new socket circuits. Another scenario I've come across is old electric storage-heater wiring being converted to socket circuits...
@RandyDarkshade2
@RandyDarkshade2 8 жыл бұрын
I had two in the lounge and two in the bedroom, one in the hallway and three in the kitchen. So it's like one for tyhe kitchen sockets, one for the bedroom and one for the lounge. Hallway outlet is on the lounge circuit, I know that cause I was messing around one day and tripped it out from the hallway outlet lol
@add2k
@add2k 8 жыл бұрын
Being a smaller building but having three breakers for sockets, I would guess you will have three radial circuits. They should not be on 32a breakers, Ideally 16a or 20a.
@unclejoeoakland
@unclejoeoakland 4 жыл бұрын
Wow... I can almost admire this in concept. Wow.
@outaspaceman
@outaspaceman 2 жыл бұрын
Wish you’d been teaching my C&G Electrical Installation course…
@Graza25
@Graza25 3 жыл бұрын
I always used to argue with my lecturer at uni about ring circuits. He explained that if you create a ring circuit, there will be NO current within the cable. His point was that because it was acting like a massive battery terminal. So, he decided to show this with an ammeter. As you can imagine, even with a load, the ammeter displayed zero load. Now, i wasnt convinced. i argued with this lecturer for over 2 years and ended up giving up. He always took the stand that there is NO load on the ring. The point i was trying to make to him was that yes, even though the meter displayed a zero load. It was simply because the meter could NOT measure it due to it being a ring (In theory, the meter was never going to be in series as im sure you know when measuring current it has to be in series (Voltage is measured across)) as the ring was always attached at either end. Just wanted to rant a little there :)
@mattybt400
@mattybt400 7 жыл бұрын
Great video. Answers most DIY questions!
@charlesparnell5338
@charlesparnell5338 7 жыл бұрын
I'm from the US and now live in the UK. We use radial circuits; which are much easier to deal with, add to. My wife's grandfather just had a conservatory built here, and he asked if I would add 4, 2 gang sockets. I thought no big deal. but it seems like its going to be. My plan is to break into the ring main with a 30amp junction box, and run the 4 sockets down off of that. I have calculated their amperage and voltage needs as 2.75 amps/187 volts being drawn in that room as they are only plugging in a 32" lcd, a sky box, and a couple of 60w lamps. I've been told by some sparkys, that this should be no problem. However, I'm seeing online that you can only spur off 1 socket from the ring main with the junction box. is this true. No one can seem to agree on this. I may just run a radial from the CU, straight back to the conservatory and be done with it. why are you guys still using such antiquated wiring schemes? What are your thoughts. Thank you!
@charlesparnell5338
@charlesparnell5338 7 жыл бұрын
or just put in a 13a fcu after the junction box, then I can put in the 4 dual gang outlets?
@jwflame
@jwflame 7 жыл бұрын
With a 13A FCU you can have as many sockets as you want, and this would be the easiest and cheapest solution (also why many conservatories end up with this arrangement). With a direct connection you are only allowed one socket, more would allow the cable to be overloaded, as 2.5mm² cable is only rated to about 26A, rings have 32A circuit breakers. The overload protection is provided by the fuses in the plugs, 2x13A being approximately the maximum rating for 2.5mm² cable.
@charlesparnell5338
@charlesparnell5338 7 жыл бұрын
John Ward thank you for the advice!
@Alozhatos
@Alozhatos 4 жыл бұрын
This is super common in Commonwealth countries like my country, Malaysia...
@DavePawson
@DavePawson 2 жыл бұрын
Thank you John.
@stephenlittle7534
@stephenlittle7534 5 жыл бұрын
That end comment is a load if B.S. A long time ago we split the house into top and bottom ring mains and one for the kitchen that was when I was say 20 years old. I am 67.now there is nothing I repeat nothing wrong in a ring mains circuit at all.
@kevalbertmooka
@kevalbertmooka 5 жыл бұрын
@Mark Sesum you can have a fault on any radial circuit, making it potentially lethal.
@patnutoris4054
@patnutoris4054 5 жыл бұрын
You did not get the content of the video.
@MrBoreray
@MrBoreray 5 жыл бұрын
@Mark Sesum -When the ring is completed you double the load carrying capacity of the circuit +reduce to a minimum the voltage drop.
@sbusweb
@sbusweb 8 жыл бұрын
I would have added to the video, the use of FCUs being useful in some circumstances, essentially creating a 13A radial circuit wired however you like, connected into the Ring.
@cygnus108
@cygnus108 3 жыл бұрын
A great learning channel...thanks
@kevalbertmooka
@kevalbertmooka 5 жыл бұрын
Most of the sparks I know, use ring mains. Never have any problems with them.
@kevalbertmooka
@kevalbertmooka 5 жыл бұрын
@Mark Sesum 38 years in the trade for me,
@s1udgeguts
@s1udgeguts 5 жыл бұрын
@Mark Sesum Back in the late 70s, the electricity board in Yorkshire had a special on electric showers. They would supply and fit a 3kw shower far cheaper than anyone else. Turned out, they ran a piece of 2.5 to a junction box attached to the first bit of 2.5 cable they found.
@Chris-be8mh
@Chris-be8mh 4 жыл бұрын
Why did you use a comma after “know”? Lol
@dopiaza2006
@dopiaza2006 4 жыл бұрын
@@s1udgeguts A 3KW shower would either be a dribble or very cold.
@s1udgeguts
@s1udgeguts 4 жыл бұрын
@@dopiaza2006 3kw was the highest rating you could buy at the time. It was neither a dribble nor very cold
@francissichali9080
@francissichali9080 Жыл бұрын
Since I came across JWs youtube videos I follow him whenever I need clarification on electrical installation. Here is one query JW !How would one supply BS7671 compliant ring circuit for sockets outlets using with 32 A RCCB when the generator supply has a lowly rated MCB say 20A or less
@lansdorf
@lansdorf 5 жыл бұрын
Makes sense to me ,often thought about doing it that way using rcbos
@lewisbrand
@lewisbrand 6 жыл бұрын
What this actually demonstrates is that a new cable size needs to be adopted. Instead of 2.5mm2 or 4mm2, 3mm2 is what is required.
@nsoper19
@nsoper19 4 жыл бұрын
What happens if you don't delete the extra part of the ring at 12:45? Can you have a figure or 8 circuit?
@jwflame
@jwflame 4 жыл бұрын
The sockets would still work in that arrangement, but it's not recommended as all of the load for the 2nd half of the '8' will be concentrated at the single point in the middle, which could result in one of the cables in the first half being overloaded.
@73deoldtimer
@73deoldtimer 5 жыл бұрын
I was an indentured apprentice with the electricity board in the 60's and when we did 5 years, combination of college work, on the job training and special short speciality courses in and out of house and finally not to forget the 6 ,months initial basic workshop training which I well remember as being intensive and very diverse. We were taught about domestic wiring ring circuits amongst many other things and it was drilled into us that they were not and never have been ring mains, such reference to 11,000 volt ring mains, RMU's, et al, being the electricity supply company local, underground and overhead distribution network and nothing to do with house wiring. I cannot accept that using radial circuits only and abandoning the 32 Amp ring circuit is a good idea as the days of people wanting a handfull of 13 Amp sockets in a room are long past. The ring circuit has been a good system and still is in my opinion and in our small bungalow we have at least 10 x 13 Amp SSO's in all rooms and many more in the kitchen. Having sufficient sockets and a few spares obviates the need for trailing leads and use of dreadfull cheap multi way extention leads. We were taught to ensure all connections were sound and that ring circuits were exactly that and were properly tested. I accept the potential risk of having an incomplete ring conductor and that in the old days before mcb's were available the 30 Amp rewireable fuse was very crude protection and open to abuse with oversized fuse wire fitted by unskilled, unqualified people. But the 32 Amp mcb will trip quickly on overload and even in worst case scenario where they is a discontinuity in the ring circuit I doubt a fire situation would result. Notwithstanding this, and as a trained engineer now, we know and have accept that with any installation whether it be electrical, mechanical or structural, things can and do go wrong and that is why we must ensure that all engineering work is undertaken by qualified professionals and that final testing and inspection of their work is carried out independantly by a trained and experienced person. Also, it is a requirement that such work is re-tested at specfied intervals in accordance with IEE regulations. Thank you for the video, which I enjoyed watching and which has given me food for thought. However, I do feel that you have over played the situation and that you have not explained why the UK 13 Amp system of fused plugs and ring circuits is a much better one than many of the methods used in other countries. Some wiring and the cheap and very nasty sockets and plugs I have seen are possitively lethal. Our 13 Amp plug top is the result of decades of development and when you examine a trade standard BSI approved make, you will appreciate just how superior it is, both mechanically and electrically bar none.
@MotorbikeHamster
@MotorbikeHamster 6 жыл бұрын
Hi John, we have been getting defects from fixed wire testing for the additional wire at the fuse for a spur. I thought it was ok. Thanks for confirming it. I wish people who do the testing knew this too
@zeeshanyousaf7184
@zeeshanyousaf7184 2 жыл бұрын
Great video, I would like help to understand how I can satisfy the the formula Ib
@jwflame
@jwflame 2 жыл бұрын
That formula doesn't apply to a ring circuit. Rings are a special case, and it's assumed that the loads on a ring circuit will be evenly distributed, so that the current is fairly evenly shared between the two cables connected to each socket outlet, so that the current in the cables won't exceed 20A.
@danstark205
@danstark205 8 жыл бұрын
thanks so much for the info..perfectly explained, per usual.
@keiarash5058
@keiarash5058 2 жыл бұрын
I have an argument for using ring circuits: Lets say you install a 32A ring circuit, but with 4mm2 cables instead. This way, if a fault in the middle of the ring happens, the ring will be split into 2 radials with the correct size breaker and cable (32A breaker, 4mm2 cable). Therefore, all appliances on the ring will be operational and compliant even during a fault. However, if you chose a radial circuit, you wouldn't have the same degree of resilience. If a fault happens in the middle of a radial, the appliances downstream of the fault will be guaranteed to be non-operational. This is the same reason why we use ring circuits when designing a HV Ring Main system, provides more resilience.
Double Pole Fuses - Fused Neutral
8:18
John Ward (jwflame)
Рет қаралды 21 М.
Lighting Circuits Part 1
24:18
John Ward (jwflame)
Рет қаралды 1,5 МЛН
Мясо вегана? 🧐 @Whatthefshow
01:01
История одного вокалиста
Рет қаралды 7 МЛН
Леон киллер и Оля Полякова 😹
00:42
Канал Смеха
Рет қаралды 4,7 МЛН
When you have a very capricious child 😂😘👍
00:16
Like Asiya
Рет қаралды 18 МЛН
My Viewers Sent Me Their Repair Fails - Can I Fix Them?!
22:45
TronicsFix
Рет қаралды 76 М.
Tests for Ring Final Circuits
23:02
John Ward (jwflame)
Рет қаралды 251 М.
RING and RADIAL CIRCUITS. WHAT ARE THE DIFFERENCES.
10:13
LEARN ELECTRICS
Рет қаралды 116 М.
What electrical work are you allowed to do in your own home?
10:39
5 Mistakes Everyone Makes Changing Sockets ❌
11:44
Artisan Electrics
Рет қаралды 701 М.
Radial Circuits
13:42
John Ward (jwflame)
Рет қаралды 217 М.
WORST DIY ELECTRICS I'VE EVER SEEN! 🤯
22:52
Artisan Electrics
Рет қаралды 815 М.
Shared or Borrowed Neutrals on Mains Electricity Circuits
18:15
John Ward (jwflame)
Рет қаралды 374 М.
Мясо вегана? 🧐 @Whatthefshow
01:01
История одного вокалиста
Рет қаралды 7 МЛН