Just came across the same issue couple weekends ago . I pulled all that INTELLIGENT 💩 out , brazed in a traditional expansion valve , solenoid valve , coil , and mechanical thermostat, customer is good for a long time . Those EEV always 💩 mainly on weekends ,and not all supply houses stock those . Good video 👍🏼
@HumanRightsRevolutin2 жыл бұрын
Thanks for the video Bill and thanks for your honesty. We're all learning
@soloch692 жыл бұрын
Great 👍🏻 video like always thank you for sharing your skills and all the great information keep them videos coming
@winstonwright36132 жыл бұрын
Nice video, Bill. Glad to see you back with videos more regularly. As for that valve... I agree that it was bad 100%. The key, for me, isn't whatever voltage you measured, or whether it was consistent, but rather that the board reported the valve as open when it wasn't. That's not a function of the board, it simply reports what the valve tells it. The valves position sensor was reporting open when it wasn't. So it was bad. Now whether the board giving wonky voltages CAUSED it to fail or they went bad independantly... who knows. Nicely.done either way; you took care of the customer. Catch ya later brother.
@Thermoelectric72 жыл бұрын
The valve doesn't have a position sensor, doesn't report back to the controller. Instead the controller drives the valve closed but "overdrives" it, which cant hurt the valve but if there's any misstep it'll make sure closed is actually closed. From there it will count the steps as it opens. In theory stepper motors are pretty good and will track very precisely so shouldn't need feedback.
@schmitty992 жыл бұрын
Great video. Loved seeing the step by step of okay if this is fixed but doesn't run correctly what's the next thing to look at.
@FrostHVAC2 жыл бұрын
Great video, I'm starting to run across more of these walk ins, the information you teach is nothing less than valuable. For me though, when it rains, especially in central Florida, I don't risk it, I get the heck off the roof. Lightning around here is dangerous as heck and can be very spontaneous (meaning it may jus seem like only rain, but that lightning is sneaky). Plus I've got soaked enough times in my career, 😂
@EverythingHVACR2 жыл бұрын
great video Bill! preparation to braze is important I agree
@saltrue15552 жыл бұрын
Very good video. Thank you for your teaching God bless
@jerryfrigeration2 жыл бұрын
Nice video and yes it was educational. It happens when one thing fails then another and another. I have to say if you have Chris for tech support you are made.
@throttlebottle59062 жыл бұрын
1:24 uphill condensate drain line? is there a trap outside the box? probable doubling trapping issue and condensate backing up/freezing coil. the box door opening/closing may cause it to flow and drain out when used often, but an overnight defrost would likely vapor-lock and cause issues.
@DWAYNE2ism2 жыл бұрын
wow, great video. you have the imanifold probes.
@davejohnsonnola79082 жыл бұрын
Have not worked on Intelligen yet, but FWIW, at the training I went to last month presented by Don Fort, three things he stressed: 1.tranformer tapped correctly? 2. IF clean install practices performed, nitrogen flowed, that mechanically the EEV itself seldom is faulty. The solenoid coil, molex plug or connections, and thermistor probe all fail, but the EEV seldom since fails as opposed to a common TXV that deals with opposing forces, the EEV body is much simpler. 3. Recommended surge protection for all units with control boards.
@throttlebottle59062 жыл бұрын
going by the overall original install, do you think they nitrogen purged while brazing? probably hacked in god knows what used "poisoned" refrigerant, etc etc etc. the condensate drain wave(uphill low spot trap inside the box), if there's a trap outside the box, it's double trapped vapor locking with no flow and icing up.( pile of ice on the floor!)
@analogmoz2 жыл бұрын
Man, I love seeing non super-techs figure out crap using gumption and horse-sense.
@XISorryExpertIX2 жыл бұрын
I deal with these units a lot. Whenever the coil ohms out fine 9/10 times it is the board. I test by forcing the unit into a defrost and check voltage coming out of the board. That transformer being tapped wrong from jump street most likely caused the board issue
@throttlebottle59062 жыл бұрын
my guess, by the great prior installer workmanship. they did not nitrogen purge at all when brazing and the tubing totally is filled with black schmutz of death. probably wise in all those cases to install a filter/dryer inside the cabinet, directly before the new EXV with new tubing between them. flow your nitrogen folks!
@anthonywoolf90872 жыл бұрын
Nicely done frustrated me just watching I get the nightmare part lol
@finalcountdownx26042 жыл бұрын
He might not be the best tech, but at least he's honest.
@davidreyes13132 жыл бұрын
Great video you the best
@PleaseExplainMe2 жыл бұрын
And thats the reason why we use logbooks and non fadable refrigerant stickers. Every gram has to be registered.
@sjefoekel60582 жыл бұрын
Its called progress they tell me, energy efficient blablabla, stick in txv and be done with it for the next 20 years.
@Holop882 жыл бұрын
I agree the other day I had intelligen lock out because they had power outage. I know ECM save energy but I dont see how eev saves energy
@sjefoekel60582 жыл бұрын
@@Holop88 in this case it saves nothing, quite the opposit. It is suposed to be able to work with very low condensing pressures And save compression energy, however this setup will not allow it. The other backdraws are they fail all the time, sensors, boards coils what have you. The manufacturer also wants a dedicated electrical circuit for this evaporator also. I dont see any savings to be made versus A standard txv.
@IFIXCASTLES2 жыл бұрын
Sjef agree!
@TCRTechLife2 жыл бұрын
What’s up with the drain lol
@danpresson Жыл бұрын
Awesome video
@Holop882 жыл бұрын
I dont like the iced up compressor though. You could be flooding back did you check sh using your own temp probe and gauges?
@markcotter23552 жыл бұрын
good job bill, Last video with the big beard. A moment of silence please.
@Eddy632 жыл бұрын
Good vid and good fix ... Did you decide on a new meter yet ? Thx ...
@roqueherrera8471 Жыл бұрын
Chris from Bluon?
@DWAYNE2ism2 жыл бұрын
lol, tech support Chris.
@felipeballi88042 жыл бұрын
thank you.
@loramurray7954 Жыл бұрын
What brand probes are you using?
@nickk20571 Жыл бұрын
You forgot to switch that to 448A refrigerant.
@edwinbates85622 жыл бұрын
What brand of Earpiece is that?
@IFIXCASTLES2 жыл бұрын
Lessons learned!
@throttlebottle59062 жыл бұрын
Hack and Moe were at the bar before noon on that install. 🤣 this comment 100% inspired by Nor-Cal Dave 😝
@shine-cg9uf2 жыл бұрын
❄👍💪🇺🇸 nice vid.
@ritawilliamson13942 жыл бұрын
I see you get ur blue rags from RSC lol
@t.a.servicehvact.a.service31892 жыл бұрын
new system $3000 repairs $6000 good deal :)
@harrydickson45752 жыл бұрын
👍👍👍
@Ivansgarage Жыл бұрын
Did ac/refrig for thirty years, how the the hell can all that electronic shit make a system better, if I left a box down for 3-4 days would not have had a job... UN-believable
@johnpastorello14922 жыл бұрын
Coconut oil on that beard. BTW nice touch on the brazing.
@jasonroberts73692 жыл бұрын
That compressor is still icing up do not think you solve the problem
@jrh86 Жыл бұрын
Ffs never seen insulation like that, mashed potatoes 🤣🤣