Know More Risk: Wet System - Alarm Check Valve

  Рет қаралды 144,778

FM

FM

Күн бұрын

In this video from the Know More Risk series, learn about the arrangement, operation and alarm testing of a wet sprinkler system that uses an alarm check valve and water flow pressure switch. This is one of two typical riser configurations for wet systems.
To learn more about FM Global learning solutions, visit www.fmglobal.com
FM Global clients can access additional online training 24/7 at training.fmglob...

Пікірлер: 62
@wyleaziz5050
@wyleaziz5050 Жыл бұрын
Never been easy. Thank you!
@samlee4382
@samlee4382 3 жыл бұрын
thanks you for kindly sharing.... learned a lot by watching this demostration...
@sambarreto9639
@sambarreto9639 3 жыл бұрын
Notify the alarm company first so as to not send any type of accidental signal. Get operator number to verify call,
@sambarreto9639
@sambarreto9639 3 жыл бұрын
It's one gasket that seals two brims.
@tammieadams7933
@tammieadams7933 Жыл бұрын
good, explains it well and simply.
@froilantano1264
@froilantano1264 5 жыл бұрын
i am a installer of this... our company is a contructos of piping installation.. pumproom assimbly... thank you!!
@djjammindave
@djjammindave 5 жыл бұрын
I'm a Sprinkler system installer. My company is a contractor piping installer that works in Pump Room assembly. Thank you.
@mikesoh6469
@mikesoh6469 4 жыл бұрын
Thanks ... Very helpful explained
@JAMCJOfficial
@JAMCJOfficial 3 жыл бұрын
Thanks for sharing this. Very interesting hope I should learn more procedure specially pump controller bro.
@theshadowshago6998
@theshadowshago6998 8 жыл бұрын
thank you for this
@babugandhibose6663
@babugandhibose6663 2 жыл бұрын
Thank you sir 🙏
@mava5634
@mava5634 3 жыл бұрын
very well done
@akuusabale3906
@akuusabale3906 3 жыл бұрын
great work thanks Sir
@loughs321
@loughs321 8 жыл бұрын
I think that FM Global needs to hire me as a consultant before they publish these videos. Quite a few things that need to be addressed in this video.
@fitter5426
@fitter5426 7 жыл бұрын
Just curious. So what did you see that needs to be addressed?
@djjammindave
@djjammindave 5 жыл бұрын
Quite a few things that need to be addressed in this video. Like, for example? 1. 2. 3. 4. 5.
@sambarreto9639
@sambarreto9639 3 жыл бұрын
Nobody knows everything.
@Bud4Ooz
@Bud4Ooz 4 жыл бұрын
Wow thank you very much
9 жыл бұрын
Thank you... that is what I need...
@mahmoudmagdy8383
@mahmoudmagdy8383 2 жыл бұрын
pretty helpful
@user-jd9gx7bf5r
@user-jd9gx7bf5r 10 ай бұрын
thank u,, buddy
@p430257
@p430257 8 жыл бұрын
Thank you
@nicholasfonti8139
@nicholasfonti8139 5 жыл бұрын
thanks for the help man
@Fredengle
@Fredengle Ай бұрын
Hi not sure if you saw my previous question I had asked does new information allow a sprinkler (sidewall type ) to be installed in a dead air space ? thoughts please thank you
@overcomerboy4547
@overcomerboy4547 5 жыл бұрын
Great keep it up sir.
@aymanbiomy4756
@aymanbiomy4756 3 жыл бұрын
What about sensing lines of fire pumps and its positioning with respect to ACV, is it connected upstream or downstream from the ACV? and what about the jocky pump operation, is ACV open each time of jockey pump operation?
@profiresafetyservices9544
@profiresafetyservices9544 9 жыл бұрын
thank you.. its really helpful fo us..
@hummermusik2037
@hummermusik2037 8 жыл бұрын
nice video . where can i get a pdf file of this video
@muhammadalilala9068
@muhammadalilala9068 5 жыл бұрын
Thanks sir
@electricaltech4u45
@electricaltech4u45 5 жыл бұрын
Nice sir
@mnkarimi64
@mnkarimi64 5 жыл бұрын
Great
@Mo-pt3mj
@Mo-pt3mj 8 жыл бұрын
helpful
@sebastiankassman6724
@sebastiankassman6724 2 жыл бұрын
Where do you connect your pressure switch for alarm system
@dicko-200
@dicko-200 8 ай бұрын
electrical connection
@austinhologroski
@austinhologroski 3 жыл бұрын
Why doesn't the alarm get set off everytime system is filled? Water is still going from the intermediate chamber into the flow switch.
@caldershot9702
@caldershot9702 3 жыл бұрын
Austin Hologroski probably because he closed the ball valve on the alarm line which is, by code, not supposed to be there. That’s the one with the yellow handle he said must be open at the beginning. At 50 seconds...
@sambarreto9639
@sambarreto9639 3 жыл бұрын
Sometimes it does go off ,its possible the alarm shut off valve is closed or the switch itself could be bad.
@dicko-200
@dicko-200 8 ай бұрын
alarm panel can be silenced and set for test.
@greeny2189
@greeny2189 7 жыл бұрын
they put that control so low so he had to bend down haha
@romeozaire174
@romeozaire174 3 жыл бұрын
Instablaster
@realgoku8384
@realgoku8384 4 жыл бұрын
Question : if the system pipes above the.Riser and check valve all the way to the sprinkler branch lines and heads are full of water why is it that the water is going from below the wet check valve / through intermediate chamber and out the ITV or pressure switch ?
@sambarreto9639
@sambarreto9639 3 жыл бұрын
I wish I could see the unit but if water is making it to the pressure switch it indicates that although all appears set ,the clapper is not sitting properly and the intermediate is taking in water.basically a false alarm.
@realgoku8384
@realgoku8384 3 жыл бұрын
@@sambarreto9639 yea I read this now ( what I asked ) and kind of don't even understand what I was asking anymore but oll have to re watch the video later and see and come back to here and tlk about it more with all the great people on this. Thanks tlk again later
@sambarreto9639
@sambarreto9639 3 жыл бұрын
A regular check valve only stops water from flowing back to where it is fed from. But since you mentioned an intermediate then I'm thinking you are talking about an Alarm Valve ,which is basically a check valve with gauge , drain and alarm ports as well as a test valve for alarms and a bypass which allows water to flow into above clapper without lifting it to cause false alarms. These days a lot of systems are straight pipe as well with a water flow switch eliminating the Alarm Valve.
@sambarreto9639
@sambarreto9639 3 жыл бұрын
When the system fills with water the clapper kind of waggles a little bit ,equalizes ,then sits flat. If she doesn't sit completely flat with the pressure equalized on top and bottom, it's because there could be a pebble ,or obstruction on the seat, then the water will still swallow in through the intermediate and trigger the Alarm Pressure Switch or Water Motor Gong. Sometimes small leaks come from a bad rubber gasket or soiled seat.This type of tiny seepage can cause a false alarm that builds up over time, maybe a few days or a week,, the build up of water pushes the pressure switch alarm .The seat can be cleaned with a little emory cloth or the gasket may need to be replaced. A quick trick is to open up the drain all the way allowing the water to flush through Alarm Valve chamber and knock out whatever could be obstructed , then closing the drain the system will equalized again and the clapper has another chance to reset itself flat . Don't tell anyone, just kidding.
@realgoku8384
@realgoku8384 3 жыл бұрын
Wow Holy crap I concur
@monizag
@monizag 7 жыл бұрын
why must the pressure gauges show same reading?
@fitter5426
@fitter5426 7 жыл бұрын
The pressure gauges don't need to be the same. Alarm checks and riser checks are nice because you don't have to drain the entire system to work on something before the system riser. The purpose of an alarm check is the operate the system without a flow switch. Most alarm check especially older ones have a retarded chamber on them that allows a flow of water during a pressure surge so the pressure switch don't operate. That system this guy has in the video the pressure switch would trip every time there was a pressure surge cause there's no allowance from a retarded chamber. And when there is a pressure surge that alarm check locks the pressure surge in above the clapper. So more often than not the gauge above will be higher than the one below.
@caldershot9702
@caldershot9702 3 жыл бұрын
fitter542 nfpa requires 50psi above city or 125 psi whichever is greater. This is clearly American though. No retard chambers used in Canada for the most part. Excess pressure pumps are used.
@sambarreto9639
@sambarreto9639 3 жыл бұрын
Pressure on wet systems can show higher readings above clapper because when at night water pressure rises with less neighborhood use ,water pressure goes from below clapper to above clapper through Alarm Valve bypass and stay locked in above. I believe some older models allows water to go from top to bottom through an intermediate bypass(small hole from below to above and vice-versa ) as to not lift the clapper causing a false alarm ,this type of bypass keeps readings looking balanced. When they get clogged the can cause false alarms.
@sambarreto9639
@sambarreto9639 3 жыл бұрын
Does not always show the same, if you just filled system at that moment and presure doesn't match, one or even both gauges need changing would should be calibrated every five years anyway.
@abuhanif6849
@abuhanif6849 4 жыл бұрын
Hii
@ash1775
@ash1775 3 жыл бұрын
Why is it so loud? We have a sprinkler room where i work and one day i was getting my chemicals and it randomly kicked on and the room is small, and you can hear it thoughout the entire facility, it blasted my ears and I still can't hear right
@sambarreto9639
@sambarreto9639 3 жыл бұрын
If it's a Dry system the compressor can kick on once in a blue moon to upgrade air pressure that holds back water pressure. If the compressor kicks on every few minutes or less indicates a small leak on air supply line from compressor to system. Sensor line.Yes the compressors are loud and should be braced as to avoid excessive shaking.
@chrischilders7498
@chrischilders7498 5 жыл бұрын
Does fm global want to hire someone that knows how there’s systems work? This guy has never worked in sprinkler industry.
@antonganykin8912
@antonganykin8912 2 жыл бұрын
Помой Волосы и подстригись наконец то
@ericcius1498
@ericcius1498 5 жыл бұрын
Alarm valves don't have intermediate chambers.
@sambarreto9639
@sambarreto9639 3 жыл бұрын
Yes they do
@sambarreto9639
@sambarreto9639 3 жыл бұрын
Alarm valves have intermediates because when a head pops and the clapper opens water flows into the intermediate ,then into the alarm line triggering signal
Know More Risk: Wet System -“ Riser Check Valve
3:08
女孩妒忌小丑女? #小丑#shorts
00:34
好人小丑
Рет қаралды 48 МЛН
Meet the one boy from the Ronaldo edit in India
00:30
Younes Zarou
Рет қаралды 15 МЛН
WORLD'S SHORTEST WOMAN
00:58
Stokes Twins
Рет қаралды 191 МЛН
Running With Bigger And Bigger Feastables
00:17
MrBeast
Рет қаралды 126 МЛН
Know More Risk: Safety Bungs
3:49
FM
Рет қаралды 9 М.
System Reset: Model F Dry Valve - Dry Pipe Fire Sprinkler System
15:05
Viking Sprinkler
Рет қаралды 28 М.
Fire Sprinkler System- Wet Alarm Check Valve Explained
1:08:05
FireSprinklerSifu
Рет қаралды 4,8 М.
How Does a Hydraulic Ram Pump Work?
8:56
Practical Engineering
Рет қаралды 7 МЛН
Alarm Check Valve Assembly Process
4:49
Buy Firefighting Equipmnet from SIIFUU
Рет қаралды 58 М.
Static Pressure and Manometer Basics
32:33
HVAC School
Рет қаралды 175 М.
Fire Sprinkler Systems Explained
11:29
Stuart Lloyd
Рет қаралды 1,3 МЛН
女孩妒忌小丑女? #小丑#shorts
00:34
好人小丑
Рет қаралды 48 МЛН