sir for per unit system, why do we multiply by 1000 and Mega to VA.
@bibinthomasa33064 жыл бұрын
Thank you sir
@MikeJohnMentzer2 жыл бұрын
Sir if the load given is having a negative PF, will the load be represented by a resistor and capacitor in parallel or series So the value of X from V^2/ Q will be the reactance for the capacitor?
@lokesh62294 жыл бұрын
Sir at 15:16 you have taken MW/MVA for p.u calculation why? it should be 40MW/.9= 44.44MVA then p.u will be 44.44/30=1.48
@anywarthomas49142 жыл бұрын
May you enlighten me more how got KV base = 11kv on the Left hand side of T1. I thought the KV base on the left hand side of T1 = 33*33/11
@abhinavthodupunuri24647 ай бұрын
the rating of transformer 1 is not exactly 33/11, it is 11/33 that is the primary circuit (left side) has voltage 11kv and secondary circuit (transmission lines) has voltage of 33kv
@turkmaneoussama54734 жыл бұрын
Thanks a lot I don't understand how the base voltage for each section is selected (2 example)
@vankamchowdaiah99854 жыл бұрын
Transformation ratio is n2/n1;but T2 it will n1/n2
@engineeringforme33183 жыл бұрын
sir u are great
@vankamchowdaiah99854 жыл бұрын
In case of kv rating of T/F
@sriiisriii7953 жыл бұрын
💚💚
@arjunjoshi10154 жыл бұрын
Plz help me to improve my basics
@arjunjoshi10154 жыл бұрын
@@lecturesinelectricaleng sure sir I need ur mail Id