I would like to thank you for that film, it helped me a lot, that tip of potentiometer, it wasn't so much clear on the manual, and with your explaination it was so much easier. Thank you very much!!!
@gracehernelpanzou2200Ай бұрын
thanks so much sir for this great video
@waubers7814 Жыл бұрын
Thanks a lot! Very clear and straight to the point! Show de bola!
@sultanhussain60512 ай бұрын
Super Demonstration Sir love you from karachi Pakistan.
@goldenfarms29345 жыл бұрын
Extremely helpful video, thanks for sharing. 👍🏼🇺🇸
@lrcustomspty Жыл бұрын
Thanks for the video! It help me a lot!
@meiamini8574 жыл бұрын
This solved my problem, thanks a million
@tripatsinghbatra35172 жыл бұрын
Nicely explained sir
@AnwarHossain-lb5eb5 жыл бұрын
very good explanation and cleared described.....thank you very very much.
@aaronpadilla75583 жыл бұрын
Very Helpful Video. Thanks a lot sir
@marcing86105 жыл бұрын
Thanks for the film, it helped me a lot
@amindaneshpajooh46022 жыл бұрын
Excellent explanations, thank you.
@Lesman Жыл бұрын
Glad it was helpful!
@sukantomahakur2050 Жыл бұрын
@@Lesman 1st I want to give you thank you for nice explanation. sir I am facing problem that p run 1 error.. kindly advise me what I have to do
@mohammadtahirhussain37884 жыл бұрын
Very simple and nicely teach thanku
@bigkikocisneros77266 ай бұрын
Thank you
@madhavrabari47562 жыл бұрын
Thank you very much sir.. very useful video for me..
@Lesman Жыл бұрын
You are most welcome
@alivarolbasaran5953 Жыл бұрын
Thanks a lot
@vikramsinghrathore66935 жыл бұрын
Great presentation, keep it up.
@_your.aditya_9 ай бұрын
thanks Sir
@shahid8639 Жыл бұрын
So nice of you sir for the information. recently I have calibrated the same positioner on our Siemens gas turbine. Due to the position deviation. After I have done the calibration now it’s working normal. My question is why it has position deviation? And also elaborate the the frequency of calibration.
@Lesman Жыл бұрын
Typically, something changed mechanical for some reason. Could be a loose screw on his linkage, mechanical wear somewhere in the valve and or linkage. How often should he calibrate? Not unless he sees a deviation again because whatever is wearing, continues to wear. He could also use his diagnostics on the PS2 to tell him when he reached his error(deviation) limits and then he would know when to recalibrate. Or just do an annual recalibration. Typically, something changed mechanical for some reason. Could be a loose screw on his linkage, mechanical wear somewhere in the valve and or linkage. How often should he calibrate? Not unless he sees a deviation again because whatever is wearing, continues to wear. He could also use his diagnostics on the PS2 to tell him when he reached his error(deviation) limits and then he would know when to recalibrate. Or just do an annual recalibration.
@kakarkuyuk3175 жыл бұрын
Very good and helpful video thanks
@2018GEORGE5 жыл бұрын
very detailed video!
@bigkikocisneros7726 Жыл бұрын
Thank you 🎉
@satyadeepakchinnideepak97184 жыл бұрын
Great Video. I am facing a problem regarding with my rotary actuator. The valve is opening and closing manually, but the potentiometer value doesn't change. Tried to do initialisation, confused with the parameters. So kindly post the parameters for a rotary actuator. Thanks in advance.
@ericrocha46934 жыл бұрын
Very helpful video. Only issue I am running into now is when its in auto and modulating, the positioner indicates on the LCD screen an oFL code and the number 127.9, I'm not sure to how to resolve this issue.
@rajaselvatvm2 жыл бұрын
I also facing same issue please share the knowledge if u solved this issue
@Technology36745 жыл бұрын
Very good sir
@walterengeeletrica3 жыл бұрын
Muito boa a explicação! Parabéns !!!
@900_z_rider Жыл бұрын
What does it means during calibration as you mention we need to rotate the potentio meter wheel. What is the reason if that potentiometer wheel is not turning? I am facing this issue hence asking. Your valuable inputs are really appriciated. TIA
@Lesman Жыл бұрын
Your wheel may not turn if your positioner is damaged or if you’re not using enough force to turn the wheel. Please contact Siemens technical support at 1-800-333-7421 for specific questions.
@rajaselvatvm2 жыл бұрын
When I install the new positioner to double acting actuator it goes straight away 100% and I can't close and initialize..also the + and - not operating...can anyone give suggestions please
@inzamamulhaq26505 жыл бұрын
Good explanation....!
@metlaani4 жыл бұрын
Hi, Thank you for this video. It will be helpful If you guide us on the following point. When we remove Fieldbus signal cable - all control valves goes to closed position (fail close). => which is OK. When we reconnect Fieldbus signal cable - some control valve stay in same closed position (=> which is OK) where as few control valves slowly moving to open position which is not correct (=> in this case positioner set point automatically change to 100% while connecting signal cable; set point is not coming from DCS). We check positioner setting in both cases and unable to identify the reason for different action.
@muhammedshabbirkaithwi44475 жыл бұрын
Thanks a lot engineer
@tahmidchowdhury4 жыл бұрын
Our valve is roatary type and it is not responding at all in auto mode. Current input is ok. Also works in the auto mode. Can anyone some with a suggestion?? Can re-calibrarion fix the problem?
@신룰라룰라5 жыл бұрын
아주 자세히 설명을 잘하시네요...
@gamalabuzaid25294 жыл бұрын
If its part-turn and i want to adjust it fail to close instead of fail to open, how can i do it?
@jitubabusay28263 ай бұрын
What to do. 100% open in 19 ma current?????
@satyaprakash92635 жыл бұрын
nice video sir
@3174jason Жыл бұрын
I e done everything, even reset the unit My unit keep actuating to the open position. How can I correct this.
@Lesman Жыл бұрын
It's difficult to troubleshoot without knowing your configuration. Contact Siemens Technical Assistance Center at 800-333-7421 for help. They'll be able to work through the issue with you.
@mr.nizamulhoq8514 жыл бұрын
Hello Sir, Have a good day. I have recently facing problem in a newly buying Siemens PS2(2wire, 4-20ma, 2 wire, without HART) smart positioner connect with my existing Single acting, air to open linear actuator(pneumatic control valve) having 20mm stroke when I am going to newly calibation. During commissioning this new positioner with existing control valve/actuator in initial condition its display shows P 85 and NOINI mode, at that time when if i press (+) and (-) button then the actuator totally doesn’t not move.only small clicking sound hearing inside the positioner and little air Release from actuating pressure line(Y1) of positioner , however pneumatic(4kg air pressure) and electrical(4ma , 24VDc) connection is there. Interesting is if i place old existing positioner there then it easily move the actuator after pressing (+) and (- ) key in NOINI mode. Is there any problem of lever setting or restrictor setting there.i don’t change any restrictor setting in this newly buying positioner during commissioning there.i am confused if there any setting required in restrictor at positioner during newly commissioning? Anybody here who can advice me kindly please to fix this problem.
@mohanrajganesan5026 Жыл бұрын
what about the flow adjustment in positioner
@Lesman Жыл бұрын
The PS2 has speed control valves internal as a standard. On single acting there is one, and on double acting there are two. These valves can be used to restrict the air exhaust output, and therefore slowing down the speed at which the valve can close or open depending on how it is designed to act in a fail position event. The factory default is to have them completely open, for the fastest response. If for some reason you want to slow the stroke speed, adjust the screw to make this adjustment. Call Siemens at 1-800-333-7421 to speak with their technical support.
@lorenzoteatini39746 жыл бұрын
it here any version intrisically safe for ATEX Zone 0? (Eexia=?)
@pokegold1004 ай бұрын
How to repire relay for this positioner....?
@Lesman4 ай бұрын
Relays are not repairable. You may need to purchase a new relay board. Call 800-333-7421 for help troubleshooting. Once the issue is confirmed, call your local Siemens rep if a replacement part is required.
@jdnoble69453 жыл бұрын
Absolutely brilliant video, I have identified my problem , my actuator was starting at 100% and therefore could not do the auto initialise. Can anyone say how to reverse the 100 to 0% using parameters 7 and 38. rise and FALL. when you have done' rise' or'fall' to reverse the action do you just go back to idle or do you initialise again?
@rajaselvatvm2 жыл бұрын
Hi u have solved this issue ..bcoz I also facing same issue
@azereliyev3563 Жыл бұрын
@@rajaselvatvmsalam siz nasil yaptidiniz
@basavarajbasava84503 жыл бұрын
Nice
@petersantos53225 жыл бұрын
muito esclarecedor obrigado.
@mr.nizamulhoq8514 жыл бұрын
Dear sir, have a good day. Thanks for uploading such type of excellent video. i have recently facing problem in a a newly buying Siemens PS2 positioner connect with existing Single acting linear actuator , 20mm stroke.during comissioning this new control valve/actuator in initial condition its display shows P 85 and NOINI mode, at that time when i press + and - button the actuator totally not move.only small sound hearing inside the positioner and some air release backside of positioner , however pneumatic and electrical connection is ok.if i place old existing positioner there then it easily move the actuator after pressing + and - key in NOINI mode. Moreover when i go in Log 5 ,NOINITM mode 30% open the valve in both YEND1 and YEND2 once i press both + and - key.once i release button then actuator go to zero condition.it doesn't hold at all. If its abnormal what can i do.would you please advice me. if i press only either + or - button then actuator not move in YEND1 and YEND2 mode.but when i press both + and - button simultaneously then it open actuator only 30% but not hold at all then when press hand button its display range message. will you please advice me its normal or abnormal? Really i am facing a horrible condition for this positioner at my site and i am apologetically wish to get you kind advice please. Thanking You, Engr.Nizamul hoq. proprietor. United Mechatronics Engineers. Bangladesh. Email: united.mechatronics@gmail.com Mobile : 0088-01814792505 and 0088-01935675378(whatsapp) Skype: nizamul.hoq1
@shahrukhsatkut41196 жыл бұрын
difference between 2 port & 3 port seimens valve positioner
@satyaprakash92635 жыл бұрын
thanks
@supercriticalburner5 жыл бұрын
Can I skip the leak test?
@jimhaldeman94435 жыл бұрын
Yes, the leak test only occurs when it is initiated by the user.
@shahzebali82815 жыл бұрын
How can we factory reset it ?? Kindly rep plz
@jimhaldeman94435 жыл бұрын
50.PRST Preset Reset all parameters which can be reset by 'Init', 'PArA' and 'diAg'. ALL Reset initialization parameters '1.YFCT' to '5.INITM'. Init Reset parameters '6.SCUR' to '49.LIM'. PArA Parameter assignment 9.3 Tabular overview of the parameters SIPART PS2 with and without HART Operating Instructions, 02/2016, A5E00074631-AB 151 Parameter Function Parameter values Unit Reset parameters A to P of the extended diagnostics function as well as parameter '52.XDIAG'. diAg
@aadeshjain64306 жыл бұрын
hello, can u plz tell me the inner parts like i/p converter etc. of a ps2 smart positioner.. plz reply me
@smartlife43694 жыл бұрын
are u got answer than share with me
@aadeshjain64304 жыл бұрын
@@smartlife4369 no..i didnt get yet..
@didinachtergaele5 жыл бұрын
Great video, but I have a problem today ....... all ok, just, it works invert. 20mA = closed - 4mA is open (ballvalve valve - 90°) ? Who can help me. Many Thanks :-)
@didinachtergaele5 жыл бұрын
I'll try again tomorrow, exactly as you described.
@jimhaldeman94435 жыл бұрын
3.21 Reversing the Action There are two ways to invert the action and display, one requires re-initialization. No re-initialization procedure This procedure inverts the physical action and display of the positioner. ● Parameter "SDIR" reverses the physical action - From AUT or MAN mode, press button for 5 seconds. Observe parameter name in the lower right corner. - Continue to press button until "SDIR" Parameter is reached. - If "SDIR" Parameter displays "riSE" change to "FALL" or vice versa. Use and/or buttons to change option.