Very Well Explained. Every student and people working with this systems should watch it.
@heatingsolutions1232 ай бұрын
Thank you for your feedback!!!
@nemanjagradinac54195 ай бұрын
Fantastic rig you’ve made my friend, and literally the best training video on this topic I have ever seen. You’ve got an excellent way of explaining everything in various conditions and you’re clearly very talented in your job and capable of teaching others in simpler terms! Well done mate 🤙 and absolutely spot on!
@heatingsolutions1235 ай бұрын
Wow, what a comment!!! Thank You so much🤝
@makelemerhawi223316 күн бұрын
Very useful training. I have learned in 36:26 minutes more than 5 years installation company. 10q
@heatingsolutions12315 күн бұрын
Good to know! Thank you!
@HenryBartlett-b1l27 күн бұрын
Very useful. Thanks.
@heatingsolutions12319 күн бұрын
Good to know. Thank you!
@peetersoovik1807 Жыл бұрын
Very good video and explanations. Well done!
@heatingsolutions123 Жыл бұрын
Many thanks!
@hrvojehorvat6073 Жыл бұрын
Excellent video showing in live water flow in heating system. It would be better if author would insert some slides with diagrams
@heatingsolutions123 Жыл бұрын
Noted
@garyf51928 ай бұрын
Nicely done.
@heatingsolutions1238 ай бұрын
Thank You!
@gaultier12911 ай бұрын
Great video, very interesting! How can one measure/set the flow on risers without these transparent tubes in a real world scenario when using the ASV-M and the ASV-PV?
@heatingsolutions12311 ай бұрын
Here is a video how to measure ASV-I. ASV-M has no scale, but you can measure it also: kzbin.info/www/bejne/bIi1ZKSoZZqHqas
@gaultier12911 ай бұрын
Great, thanks!
@etlerandrea Жыл бұрын
Excellent!
@heatingsolutions123 Жыл бұрын
Glad you liked it!
@pungusattah Жыл бұрын
Great video. I do have a question, would you have a radiator valve and a PICV? Won't you lose authority in the radiator valve in that scenario? I thought a DPCV and radiator valve to maintain the authority and PICV directly to a larger coil or coupled with an actuator to vary flow. Thanks
@heatingsolutions123 Жыл бұрын
Shure you can not have radiator valve with thermostat and let's say PICV on riser. You will loose authority on radiator valve. On radiator valve closing PICV will open. Good solution would be radiator valve (with presetting RA-N) and DPCV (ASV-BD+ASV-P/PV). Or you can use directly dynamic radiator valve RA-DV without DPCV in a smaller systems. Dynamic radiator valve RA-DV is similar to PICV (Danfoss AB-QM).