Transformers - Understanding Delta/Wye Connections [250.4(A)] (12min:11sec)

  Рет қаралды 188,932

MikeHoltNEC

MikeHoltNEC

Күн бұрын

Пікірлер: 119
@kimmer6
@kimmer6 3 жыл бұрын
I supervised installs on General Electric gas turbine generators all over the world in the 1970's and 80's. Almost all were Wye connected with generator ouput voltage at 13,800 Volts. In the 90's my 10 year old nephew became fascinated with transformers. For months I heard about this and figured the guy was like me....had to tear things apart and reassemble to make them work better while the other kids were reading comic books. So I bought him a big book on transformers and distribution yards for his birthday. Stupid me. I found out that ''Transformers'' were toys that were vehicles that unfolded into robots as featured in comic books.
@mikeholt3717
@mikeholt3717 3 жыл бұрын
Lol, that is a great story!
@shanegee6165
@shanegee6165 4 жыл бұрын
It’s very necessary mike. It separates electricians from installers. Anyone can bend pipe or run rope. This is what separates men from boys
@TheTrainstation
@TheTrainstation Жыл бұрын
One of my mates is a qualified electrician, domestic work. Hes great at wiring houses because you dont need to know much apart from pulling wires around. Last week he connected up the machines in my mates carpentry shop..the bandsaw ran backward so they switched the polarity, fine. Nrxt machine they connected a big motor with star delta switching and it arced and blew. Then...they switched the polarity on this one too and boom. SMH
@davidanderson911
@davidanderson911 13 күн бұрын
I was amazed the first time I worked in a large substation, in the now closed Castle Air Force Base at Atwater, CA, to see these huge transformers had an XO terminal that went to straight to earth ground right off the side. My grandfather worked on the original construction of Grand Cooley Dam. He told stories about it that I was way too young to understand, other than it was a great source of pride to him. Thanks, Mike!
@MikeHoltNEC
@MikeHoltNEC 13 күн бұрын
I was personally at the Grand Cooley Dam and there are three "HUGE" transformers on each side of the dam. Mark A, B, and C. Then if you following the overhead buss (which I did) one terminal from each transformer tied together (Wye Secondary) and it went into the earth and it was marked "XO". Blew me a way... So I know the feeling.
@bertgh
@bertgh 9 жыл бұрын
This video explains everything so well and states it so simply that all the info that I tried to understand in other sites seems to be unnecessarily complicated. Mike, your videos are GOLD, thank you so much for uploading them.
@chardysmile
@chardysmile 7 жыл бұрын
Leonardo Moreno the ground and neutral. .are they really connected inside of the transformer??
@abebegezahegn9436
@abebegezahegn9436 5 жыл бұрын
@Mike Holt a
@carultch
@carultch 4 жыл бұрын
@@chardysmile Ground and neutral are either connected inside the transformer, or inside the secondary protection disconnect immediately adjacent to it. The transformer secondary circuit is called a separately-derived system (SDS) in the NEC. This means that it needs to have its own connection to the grounding electrode, and its own establishment of the neutral at ground voltage, otherwise the three phases would float. Transformers isolate the two sides, as they only transmit change in voltage, rather than absolute voltage. From the perspective of physics, it makes the most sense sense to make your neutral-to-ground bond inside the transformer. But because there is precedent from how we bond neutral and ground in service disconnects that are on the secondary of utility-owned service transformers, the NEC gives you the option of treating the secondary conductors like service conductors, and bonding neutral to ground in the secondary disconnect. In any case, you only want to make this connection once for the SDS, and you connect to the GEC and grounding electrode, whereever it happens.
@chardysmile
@chardysmile 4 жыл бұрын
@@carultch thanks
@davehasenford3985
@davehasenford3985 2 жыл бұрын
I'm really glad you explained at the end that geometrically, the distance between the ends of the two legs, if the two legs being a length of 12 'units' from center, is 20.8. It takes some of the mystery out.
@WhosthatTeamAFC
@WhosthatTeamAFC 6 жыл бұрын
When I see a tie like that I know I'm about to learn. And learn good.
@jf8461
@jf8461 4 жыл бұрын
I noticed the tie right away, because I happen to own the same one!
@WhosthatTeamAFC
@WhosthatTeamAFC 4 жыл бұрын
@@jf8461 You probably have a lot to teach me.
@markamber1480
@markamber1480 4 жыл бұрын
7:41 casually recommends shorting out a 12 AWG extension cord. Definitely a talk tailored for electricians...
@jf8461
@jf8461 4 жыл бұрын
Finally somebody who explains this where I can understand well! I am not an electrical engineer, but sometimes I have to do some electrical work and I found this video extremely helpful. I will definitely watch some of his others.
@dutcher517
@dutcher517 7 жыл бұрын
Mr. Holt, I have watched numerous videos of yours, multiple times. I have learned an enormous amount from you and your team. Just wanted to say thank you.
@MikeHoltNEC
@MikeHoltNEC 7 жыл бұрын
I'm so glad that God has blessed me so that I can provided this service to the industry. Thank you for the message, God Bless, Mike Holt
@dutcher517
@dutcher517 7 жыл бұрын
MikeHoltNEC I start an Electrical Power Technology with an AAS this month. I am currently an electrician apprentice and have worked on Siemens 2.3 mW wind turbines. When I have more disposable income, I will buy your DVDs. Until then, your videos are absolutely top notch. Seriously, I've watched hundreds, and yours are so clear and concise. Wish I could sit down with you and ask questions. You and that panel in the video, obviously know your stuff. Have a great weekend.
@MikeHoltNEC
@MikeHoltNEC 7 жыл бұрын
Thank you, have a wonderful day and look forward to meeting you one day at one of my seminars.
@vince6829
@vince6829 Ай бұрын
Thanks for sharing your knowledge.
@Top5DeadOrAlive
@Top5DeadOrAlive 7 жыл бұрын
Mike you are a monster, see? A monster of electricity.
@esjel9804
@esjel9804 6 жыл бұрын
Out here we call him a beast!
@mino-kw1oh
@mino-kw1oh 8 жыл бұрын
mike, another great video. thank you for your dedication to the craft.
@MikeHoltNEC
@MikeHoltNEC 8 жыл бұрын
Mino, thank you, have a wonderful day.
@guitarhvac
@guitarhvac 6 жыл бұрын
Thanks! This finally makes sense out of something many people work with all the time, but have no idea how or why it exists.
@KartiacKID
@KartiacKID 3 жыл бұрын
I would have loved having as one of my professors in college
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
Thanks for the kind words, God Bless.
@commercialsparky7776
@commercialsparky7776 2 жыл бұрын
Good video as usual, great video actually.
@lendavidhart9710
@lendavidhart9710 5 жыл бұрын
Thank you for this, i love this stuff, i should have gotten into this earlier in life Edit- thanks again i learned alot watching this.
@MikeHoltNEC
@MikeHoltNEC 5 жыл бұрын
You are most welcome.
@AM-dj5nv
@AM-dj5nv 4 жыл бұрын
Hello Mr. Holt, can you please explain 3phase delta with a corner ground? I ran into this at an oilfield in southeastern New Mexico. What’s the advantage/purpose. Could this cause step potential? Thank you very much Mr. Holt!
@mdhaskins1
@mdhaskins1 6 жыл бұрын
I love this stuff!!
@user-mz7hb1dq5x
@user-mz7hb1dq5x 2 жыл бұрын
thanks for uploading
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
You are welcome.
@jamescaraway6191
@jamescaraway6191 7 жыл бұрын
Mike: As a point of information. I would like to point out the following. A delta transformer is an isosceles triangle. All triangles have a total of 180 degrees. Because it is an isosceles triangle the angles are all equal. Therefore the angle between all angles in a delta transformer are 60 degrees. If one takes the sine of 60 degrees multiplied by 240 volts one will get 207.8 volts. In addition Y transformer is arranged in a circle. Because there are 3 equally spaced transformers the effective angle is 120 degrees. Interesting the sine of 120 = sine 60.Therefore line to neutral voltage in both delta and neutral are equal. Interesting HUH?
@MrBrandoncreel
@MrBrandoncreel 7 жыл бұрын
James Caraway delta is an equilateral triangle and that's why all angles are equal. Thus 60-degrees.
@carultch
@carultch 4 жыл бұрын
Equilateral triangles are more specific than isoceles triangles. Isoceles triangles just have two equal sides and two equal angles. Equilateral triangles have all three sides, and all three angles equal.
@selfmade128
@selfmade128 Ай бұрын
Amazing teacher
@MikeHoltNEC
@MikeHoltNEC Ай бұрын
Thank you, I try to improve each day.
@V2Guerrero
@V2Guerrero 3 жыл бұрын
It is absolutely necessary, lol
@interplucky
@interplucky 3 жыл бұрын
Really looking for WYE-DELTA configuration. Sad you didn't cover it :( The NJATC homework asks about WYE-DELTA, but doesn't explain it very well.
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
Call me 352.455.0794 anytime and I’ll help! Mike Holt
@garbo8962
@garbo8962 3 жыл бұрын
In my 50 years as an industrial electrician never came across a Y Delta. A Y primary more then likely would only be feed with 3 wires.
@tedlahm5740
@tedlahm5740 Жыл бұрын
Question; My local residential transformers are ALL Single Bushing grounded Why. Yes, only one bushing. This is multipoint grounding at each pole/transformer. Question, where is the parallel neutral going back to the power company substation? thank you
@floogon_gameing6987
@floogon_gameing6987 6 жыл бұрын
Not lookimg for that kind of transformer but this was still very informative
@richardbriley9377
@richardbriley9377 4 жыл бұрын
J
@jolyonwelsh9834
@jolyonwelsh9834 6 жыл бұрын
You can buy a 3 phase dry type transformer with a 120/240 Delta secondary all in one.
@MikeHoltNEC
@MikeHoltNEC 6 жыл бұрын
Correct.
@garbo8962
@garbo8962 3 жыл бұрын
Was told years ago that never use more then around 10% on a delta secondary with one of the secondary coils tapped for 120 volts. If too much power is pulled off one coil it produces a greater voltage drop in that coil. For every 1% voltage difference between 3 phase legs think it produces around 3% more heat in a 3 phase motor.
@spatzky
@spatzky 3 жыл бұрын
At 7:00, he said faults will not cross on delta wye grounded transformers. You are wrong. SLG, DLG, LL faults do not cross delta wye ground transformers BUT a three phase fault does.
@mikeholt3717
@mikeholt3717 3 жыл бұрын
That is NOT what Eric said, he said the fault doesn't go from primary winding to secondary winding becasue of the air gap between the primary and secondary.
@DP-hy4vh
@DP-hy4vh 7 жыл бұрын
Another way to get 208 volts line-to-line; (120 V + 120 V) * Sin 120° = 207.84 V or 208 V (rounded up)
@MikeHoltNEC
@MikeHoltNEC 7 жыл бұрын
Thank you!
@colt2657
@colt2657 6 жыл бұрын
We always multiplied by 1.73
@saifamu1989
@saifamu1989 5 жыл бұрын
Phase to Phase Voltage (Vab) is √3 times the phase to neutral voltage (Van) in magnitude but Vab would lag behind Van by 30°. This is true only in case of a Wye connection...in Delta connection, its the Current which obeys this rule.
@stoobydootoo4098
@stoobydootoo4098 4 жыл бұрын
Treat the voltages as vectors (because they are!). You can do it 2 ways using trigonometry - 1) (simplest) Split the isoceles triangle into 2 right angle triangles. 60*/30*/30* on the right side. Cos 30* (0.866) = adjacent (??? Volts) / hypoteneuse (120 Volts) Simple arithmetic shows the adjacent as almost 104 Volts. It's the same on the left side triangle. Add them together = 208Volts. QED. 2) The Sin rule - A (120 Volts)/ Sin a (30*(0.5)) = B (??? Volts)/ Sin b (120*(0.866)) Simple arithmetic shows that B is almost 208 Volts. Simples! (As we say in the UK after a long running series of TV ads.)
@stoobydootoo4098
@stoobydootoo4098 4 жыл бұрын
Just to clarify, I'm referring to the Wye example. Sides A, B (imaginary line), & C. I'm calling A, & C 120 Volts. B on top is the 'unknown' Voltage.
@engrjunogarte9844
@engrjunogarte9844 4 жыл бұрын
7620/13200Y---120v/240v
@MikeHoltNEC
@MikeHoltNEC 4 жыл бұрын
Post your quesiton on MikeHolt.com/Forum.
@SJ-hw7bx
@SJ-hw7bx 5 жыл бұрын
Wouldnt 500,000 va be 500Kva????
@evanbrawner2414
@evanbrawner2414 5 жыл бұрын
S J MVA would be million, so 500 million volts. Idk why he said MVA then said 500 thousand lol
@saifamu1989
@saifamu1989 5 жыл бұрын
500,000 VA = 500 KVA = 0.5 MVA Complex Power
@rameshdathrampersad9216
@rameshdathrampersad9216 2 жыл бұрын
I understand but not everything. If we were to put more windings on each transformer of the secondary star side to give 240 line to line and 120 from line to neutral. Can they put that number of turns so that we can achieve those voltages out of a secondary star system or is the 208 / 120 is just how it works because i know or heard you can put a certain number of turns to get a desired voltage. Thanks
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
You can't get 240/120V on the secondary of a Wye configured winding.
@MrKadidle51
@MrKadidle51 Жыл бұрын
Can I connect a delta system to the secondary of a wye transformer and just not terminate the neutral? Transformer is 4160 to 480y277. However it's a 480 delta system.
@dhunsaker26
@dhunsaker26 5 жыл бұрын
I would like to find a video that explains neutrals on 2 wire power line to underground transformers.
@G30RG13N
@G30RG13N 6 жыл бұрын
Gold gold gold
@keving1774
@keving1774 5 жыл бұрын
So you're saying you're allowed to have an average of10% voltage drop?
@MikeHoltNEC
@MikeHoltNEC 5 жыл бұрын
Kevin, thanks for your comment. Can you explain where you are getting 10% voltage drop from the video?
@saifamu1989
@saifamu1989 5 жыл бұрын
Voltage regulation
@dehuifang
@dehuifang 4 жыл бұрын
the most devises allow 10% voltage drop
@smash72cutlass30
@smash72cutlass30 6 жыл бұрын
Unstable incoming power during peak times of the day especially during summer months. Brown outs ? Or does that not happen at 480v My concern is this is a 180K saw sold to my client with the understanding that at 208V will run fine given it’s 10% power allowance. Manufactured in China to run at 200V
@garbo8962
@garbo8962 3 жыл бұрын
Good luck with any electrical product made in cheating lack of quality control communist china.. Several China motors that I connected ran hotter then others. Company ordered a spare 100 HP plain Jane normal Nema frame motor. cheating China motor states to only use wire rated for 110degrees C. Asked my inspector & several sparkies if they ever came across this. All said no.
@smash72cutlass30
@smash72cutlass30 3 жыл бұрын
@@garbo8962 actually my mistake there from Japan. There whole power grid is 3phase 200V I’ve been running these saws from 3 phase 240V delta high leg so far no problems. There were initial software problems but not sure if that was power related. And this 240V is more like 253V so with a step up transformer it’s making 490V on 460V machines. Fingers have been crossed for a couple years now.
@garbo8962
@garbo8962 3 жыл бұрын
@@smash72cutlass30 Think I heard or read years ago that Japan might be one of the counties that run on 50 Hertz and not the 60 Hertz here in USA. Speed of an AC induction motor is Hertz times 60 ( 60 seconds in 1 minute ) divided by pair of poles minus losses. So a 2 pole motor running on 60 Hertz will run around 3460 to 3500 RPM ( Used most often for pumps ). The most common by far the 4 pole motor running on 60 Hertz will run around 1740 to 1760 RPM. We had a pump running off a VFD ( DRIVE) that ran at 70 Hertz most of the time. I asked service tech if motor was rated to run that much over the stamped speed and how does this affect life of motor. Of course he had no ideal.
@smash72cutlass30
@smash72cutlass30 3 жыл бұрын
@@garbo8962 50 hertz 100% true there motors are all wound accordingly. Problem comes when you purchase a used machine most will need a independent transformer to step up or down which ever gives you the closest power to the name plate. Most are just 200V doesn’t even give you a option. Just hooked one up 480 down to 200 just to give it the power it’s used to. Big problem if your power from the poco is high to begin with.
@engrjunogarte9844
@engrjunogarte9844 4 жыл бұрын
A banking transformer is configured to OPEN WYE/OPEN DELTA. Can this be reconfigured to OPEN WYE/OPEN WYE? What will be its secondary output voltage...Thanks and appreciate for reply.
@MikeHoltNEC
@MikeHoltNEC 4 жыл бұрын
Order the transformer configured the way you desire it to be. But I have a question, what in the input and output voltages?
@trevonwalker8022
@trevonwalker8022 4 жыл бұрын
Is the neutral 120v kinda confused about the neutral in the transformer. I’m so good at electrical in the field but the book work honestly discouraged me
@MikeHoltNEC
@MikeHoltNEC 4 жыл бұрын
Don't put yourself down, you just need to get the right book and you need to have video that explains the book. All of our products have this. I suggest you visit MikeHolt.com/Products and get our theory program.
@jonasnewell6094
@jonasnewell6094 4 жыл бұрын
I used Mr. Holt’s books to be able to pass my journeyman’s test and then the master electrician test. I put in an extra 30 min a day studying and it paid off, but it pays off more when there is an issue and you can troubleshoot it because you understand it or at times know what resource to use to find the answer. The book work can be very confusing at first, but eventually it will all tie together. I’m confident in saying if every electrician gave up when they became confused we wouldn’t have any electricians but men like Mike can help your career.
@MikeHoltNEC
@MikeHoltNEC 4 жыл бұрын
@@jonasnewell6094 Thank you, that is why we do what we do,! We love the stories about how the products help people out for the long game. Congrats on all of your successes and if we can help you in any way please let us know. Not sure if you have seen any of our business or leadership products products yet but as you continue along your career you may find these helpful as well, www.mikeholt.com/product-category-list.php?id=5. Take care and thanks again.
@jonasnewell6094
@jonasnewell6094 4 жыл бұрын
So I decided to get the business management skills books because like you said, I want to advance in my career and being able to learn from others success and mistakes is invaluable. I appreciate all your help and thank you for being a blessing. Do you have any videos explaining the que and delta connection in motors and why they are used?
@MikeHoltNEC
@MikeHoltNEC 4 жыл бұрын
@@jonasnewell6094 No, but I'm sure if you search the Internet you'll get your answers.
@dane5167
@dane5167 4 жыл бұрын
If I’m using a driver, and I want to find out the amps, do I do the watts devided by the secondary or by the primary? Let’s say I have 300 watts pulling and I devide it by the secondary 12v that’s 25 amps would that trip 20 amp breaker? And if I devide 300 by 120v it’s only 2.5. So what is the amperage actually being used on the primary
@MikeHoltNEC
@MikeHoltNEC 4 жыл бұрын
Post your question on MikeHolt.com/Forum.
@drawingtime2589
@drawingtime2589 2 жыл бұрын
If a line voltage on the primary are connected to each other wouldn't that result in an arc blast please help me to understand why these diagrams show them connected to each other
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
Nope, because this is a 'winding' that has sufficient impedance' and the load on the winding will be practically zero amperes when there is no load on the secondary. I'm sorry but I can't explain the entire theory related to your answer.
@drawingtime2589
@drawingtime2589 2 жыл бұрын
@@MikeHoltNEC Thanks for the reply, so- this primary winding is like a very very -very- long heating element? In theory? That's it for now, I know yall are very busy!
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
@@drawingtime2589 Well.... you can't use the example of 'resistance' since this is related to induction (but you are kinda right).
@drawingtime2589
@drawingtime2589 2 жыл бұрын
@@MikeHoltNEC thanks I've been pondering this for quite some time
@walexsyfigueroa1146
@walexsyfigueroa1146 4 жыл бұрын
12 _3 romex
@Espiritiv
@Espiritiv 3 жыл бұрын
Why does the USA use 120V systems and not 240V like other countries?
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
Good question, let me know what you discover.
@Sparky-ww5re
@Sparky-ww5re Жыл бұрын
The reason has little to do with practicality, and 120 volts is used for historical reasons. You see, back in 1879 when Thomas Edison produced the first practical incandescent lamp, it used a carbon filament, and worked best at 100V. Edison's first electrical power plant on Pearl Street in New York City in 1882, supplied 110 volts DC. Less than a decade later, in the mid 1880s Tesla designed and patented the alternating current system which was far more efficient and could serve customers miles away instead of blocks, 110/120 Volts AC became set in stone, since it was backwards compatible with the carbon filament lamps at the time, and for decades, AC and DC mains power would coexist. Switching over to 220- 240V like much of the world uses, would obviously be very expensive and impractical, since everyone would have to buy new equipment or install step-down transformers in their homes and businesses. The 230V 50Hz system used in Europe & much of the world, is actually a more efficient system than we have in North America.
@twn5858
@twn5858 4 жыл бұрын
Does the neutral on the wye carry less amperage? Why are there 3 120 voltage lines and only one neutral?
@MikeHoltNEC
@MikeHoltNEC 4 жыл бұрын
The answer is not something that can be answered via a post. I suggest you search the Internet on calculating neutral current for a three-phase system.
@carultch
@carultch 4 жыл бұрын
Look at the timing of three phase balanced waveforms at once, with 120 degrees of phase separation each. When phase A is at full amperes, phases B and C are both at -50% of full amperes. One phase is at -50% and increasing, the other phase is at -50% and decreasing. The current adds up to zero, among the phase conductors alone, given balanced currents on all three phases. Phases B and C are sharing the job of carrying the return current of phase A, while they are also supplying current of their own timing. You could theoretically cut the neutral conductor (not something I would advise), and the phase conductors would carry the full round trip current on their own, given balanced current among all three phases. Worst case scenario of any imbalance, the neutral will carry a current equal to the largest current among the three phases. That is why you need only the one neutral conductor. Certain situations of extreme nonlinear loads may require a 200% sized neutral, given triplen harmonics that are multiples of 180Hz on harmonic intensive loads. These harmonics add up, rather than cancel out, on the neutral conductor. But for most loads, a 100% neutral is enough.
@GH-oi2jf
@GH-oi2jf 2 жыл бұрын
There is no reason to have more than one neutral, because the neutral should be at the same potential to ground (zero, ideally) for each phase.
@ulymunoz1105
@ulymunoz1105 7 жыл бұрын
I have three phase motor 230v3p can connect to transformer delta connection. L1-L2 & neutral is 120V neutral L3 235v
@MikeHoltNEC
@MikeHoltNEC 7 жыл бұрын
Please post your question on the Code Forum at www.MikeHolt.com, under the Engineering Section.
@smash72cutlass30
@smash72cutlass30 6 жыл бұрын
I’m hooking up a large 3phase saw that was purchased overseas and ran at 200v 3phase. I’m installing a 45kva 3phase 480V primary delta to y secondary 208v is concidered within the 10% voltage allowance on he equipment. I always thought the 10% was for voltage problems from utility company provided your starting with the proper voltage. In this case I’m already higher to start. Has me concerned if there is flux in the incoming.
@MikeHoltNEC
@MikeHoltNEC 6 жыл бұрын
What do you mean by 'flux in theincoming?' Send a link about this topic.
@millerelex
@millerelex 9 жыл бұрын
Lol, Spokane, sounds like cocaine.
@MikeHoltNEC
@MikeHoltNEC 7 жыл бұрын
Thank you for the suggestion, I'm in Seattle right now and knew I was still calling it wrong.
@carultch
@carultch 4 жыл бұрын
It is said as "Spo-KAN" with the stress on the end syllable. The silent E is a red herring, because the end sounds like can rather than cane.
@millerelex
@millerelex 4 жыл бұрын
@@carultch I graduated Shadle in 94
@jjsh9849
@jjsh9849 5 жыл бұрын
Do the experiment.
@carultch
@carultch 3 жыл бұрын
Ryan Jackson did the experiment. kzbin.info/www/bejne/rYiVZaqsrcSbrMU
@MsTommyknocker
@MsTommyknocker 3 жыл бұрын
Wye = Star?
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
This is not a term that is commonly use for 'Wye" but it's a perfectly good term to use for 'Wye.'
@carultch
@carultch 3 жыл бұрын
If we had four-phase electricity, the topologies would be called Plus and Square.
@MsTommyknocker
@MsTommyknocker 3 жыл бұрын
@@carultch Excuse me, But What are you replying to?
@Rico702Vegas
@Rico702Vegas 3 жыл бұрын
TURBINE... not turban.
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
Thank you! I didn't realize that I said it wrong, I'll work on doing a better job!
Delta and Wye - Volts, Amps, & VA
13:21
Dave Gordon
Рет қаралды 531 М.
Little brothers couldn't stay calm when they noticed a bin lorry #shorts
00:32
Fabiosa Best Lifehacks
Рет қаралды 18 МЛН
Пройди игру и получи 5 чупа-чупсов (2024)
00:49
Екатерина Ковалева
Рет қаралды 3,2 МЛН
а ты любишь париться?
00:41
KATYA KLON LIFE
Рет қаралды 2,9 МЛН
Parenting hacks and gadgets against mosquitoes 🦟👶
00:21
Let's GLOW!
Рет қаралды 12 МЛН
2017 NEC - Switch - Neutral Connections [404.2] (14min:30sec)
14:31
Delta and Wye Primary Systems
7:03
Michael Jones
Рет қаралды 5 М.
Why there is no Neutral in Transmission Lines?  Explained | TheElectricalGuy
8:46
Gaurav J - TheElectricalGuy
Рет қаралды 197 М.
The why behind a wye-delta open bank.
48:51
Tim Vassios
Рет қаралды 1,4 М.
How is 208 volts different than 230/240 volts?
6:25
HVAC School
Рет қаралды 158 М.
Delta-Wye Wiring Connections
5:26
Dave Gordon
Рет қаралды 38 М.
What is the Difference Between Single Phase and Three Phase???
23:11
Electrician U
Рет қаралды 578 М.
Little brothers couldn't stay calm when they noticed a bin lorry #shorts
00:32
Fabiosa Best Lifehacks
Рет қаралды 18 МЛН