Finally a expert Mitsubishi service tech!! Thank you very much
@BonMj2 жыл бұрын
Welcome
@u5t6364 ай бұрын
Hi how are I've a question about The indoor unit doesn't have a signal to the remote control
@florencionolido52887 ай бұрын
Good day sir Bon!thanks for sharing your knowledge 🙏 im terry from jeddah working.
@BonMj7 ай бұрын
Hi, thanks
@oiltubewalker2 жыл бұрын
Noise f supply&output by vac, not required to wait for vdc to drop unless inverter pcb failure
@jaykenlopez67714 ай бұрын
What is the cause that the boise filter is not supplying DC voltage to the control Board ? Thanks.
@BonMj4 ай бұрын
Replace the pcb
@muruganantham5952 жыл бұрын
How do we conduct the test run from outdoor dip switches for this model ? Can you please tell for us ....
@dayronchagoyen4024 жыл бұрын
Usually what is the voltage DC between P and N ?. Thanks for reply.
@BonMj4 жыл бұрын
P and N just for checking the DC voltage At inverter PCB. The voltage can up to 500VDC. For safety issues.
@BurhanSOG3 жыл бұрын
I hope the health will always be given, mister
@BonMj3 жыл бұрын
Thanks🙏🙏
@Kai-18v2 жыл бұрын
Hello sir bon. How to see refrigerant quantity at deep switch?? At VRF Mitsubishi
@kusariyanto91972 жыл бұрын
how to determine the damage to the filter pcb? thank you
@shivaHVAC3 жыл бұрын
Super sir...you are great
@BonMj3 жыл бұрын
Thanks bro
@maheradous925711 ай бұрын
Sorry . I mean all new video don't forget share to me thank you.
@JavierEduardoGonzalez-iu4ze Жыл бұрын
Condensadora PHY-450 al.momento de querer encender los relay de la tarjeta control pcb clichean y no enciende los led que puede ser ?
@BonMj Жыл бұрын
Check pcb
@sirawing8282 жыл бұрын
sir, what is the cause of the mitsubishi 1 indoor unit vrf ac not cooling enough? clean evaporator
@BonMj2 жыл бұрын
Many reasons
@maheradous925711 ай бұрын
Good job 👍
@BonMj10 ай бұрын
Thanks 👍
@shreekanay6983 жыл бұрын
Thanks Sir, great information....
@hermanfung88882 жыл бұрын
Mitsubish how to test running ?
@chunhatminh20158 ай бұрын
Do you sell that broken old PCB? I want buy it.
@BonMj8 ай бұрын
No
@jhonmichaeldalisay16532 жыл бұрын
hi bon, may i ask , ah hav vrf sytem also mitsubhi, 3 units were bring 2 times in inddor cassetes , i already change pcb inddor & thermistor but still desame error,, how ca i fix this? thanks
@BonMj2 жыл бұрын
Sorry for late reply. Try check TH 2 or TH 5 thermistor
@jhonmichaeldalisay16532 жыл бұрын
@@BonMj sir i already replaced those sensor with new both including indoor pcb main , but still p2 error, is it possible related to low refrigerant? the current pressure of suction is 115 psi only.
@BonMj2 жыл бұрын
@@jhonmichaeldalisay1653 what is your outdoor model ?
@Jrbdhome8 ай бұрын
Think you for video🇧🇩
@BonMj8 ай бұрын
Welcome
@destroyandrecreate3 жыл бұрын
Can i use this method to troubleshoot pumyp125vhms vrf mitsubishi,is it the same?
@BonMj3 жыл бұрын
For checking is same,but some design are different
@karaors89703 жыл бұрын
Nice Job 🇹🇷👍
@BonMj3 жыл бұрын
Thanks
@peramaraj2763 Жыл бұрын
I have a doubt sir error code 6607 pcb set address 009 CRC appear 009 but wire remote control only view m-net address 015 why like this ?
@BonMj Жыл бұрын
Try reset outdoor power
@wongcmy93733 жыл бұрын
Hi sir, I have replaced the N NET board and the outdoor control PCB, but the error code 7113 still happened. How could I solve it, thanks?
@BonMj3 жыл бұрын
7113 Check inverter board and control board wire connections Dip switch setting ,correct?
@wongcmy93733 жыл бұрын
@@BonMj The control board wire connections and Dip switch setting are correct. check the inverter board P - N 550 VDC ? thanks
@nickymorley49494 жыл бұрын
Maybe you should add, for clarity, that a 6607 fault is normally caused by a lost indoor unit.....😁
@HotdawgMusicStuff2 жыл бұрын
I have a fault with an outdoor unit (address 52) with error code 6607. There is no LED lit up on the control board so I think this board is faulty. The other condenser unit coupled with it is address 51 with error code 7100 for capacity error but it still runs full speed and the attached FCU's are cooling ok. I suspect the unit with address 51 has error 7100 because the unit address 52 with error 6701 is not operating to provide full capacity to the system. I also have another outdoor unit on a different system with 3 x outdoors(address 58,59 & 60). Address 58 has the same error 6607 but there is power on the control board LED so I am confused. The video states that no LED lit up on control board but with AC and DC power supply means faulty board.
@wilsonalfredo4362 жыл бұрын
good evening teacher my name is Wilson Alfredo I live in Angola Africa and I would like to know how much the set of these Mitsubishi plates costs I work with these types of devices and here it is difficult to clean these types of material Moisés filtro, control PCB e Filtro PCC..?
@BERESHIDA20082 жыл бұрын
ALfredo those are not very cheap parts , but they depend where you live
@laworder60923 жыл бұрын
Cheers buddy
@BonMj3 жыл бұрын
Thanks .
@mbl46893 жыл бұрын
Is it possiblity cause by indoor for this error 6607?
@BonMj3 жыл бұрын
Yes.check controller
@mbl46893 жыл бұрын
If yes, is it FCU main PCB or other spare parts?
@BonMj3 жыл бұрын
@@mbl4689 check remote control or system controller got problem may be
@BonMj3 жыл бұрын
@@mbl4689 indoor if one of the pcb faulty ,only the unit cant on.for other still can work
@mbl46893 жыл бұрын
The CU just 1 to 1 replace few days ago.. 😅 then start error 6607
@EncikTangga3 жыл бұрын
Thnx share ilmu
@BonMj3 жыл бұрын
Thanks
@technicalmindkhan55733 жыл бұрын
Vrf unit Error 2502 and 32 show error sir how to soled
@janshaw5472 Жыл бұрын
i can't make out contrl filter and inverterpcb 😅
@windyoceanrise3 жыл бұрын
Hi Sir, our team encounter error code 6600.. how to solve overlapping N-MET address?
@windyoceanrise3 жыл бұрын
Mitsubishi PUCY-P300YKA 2 units with same address.. how to set? thank you very much for the reply
@BonMj3 жыл бұрын
6600 Check all indoor unit address . (1 to 50) Check all outdoor address (50 to 99) If found the address wrong setting,please correct it. Off the power supply all indoor unit and outdoor unit and system control more than 5 minutes and on back
@BonMj3 жыл бұрын
@@windyoceanrise 2 outdoor units should set, Example master unit 51,slave unit 52
@BonMj3 жыл бұрын
Or CU 1 (51) CU 2 (52) CU 3 (53) CU 4 (54) Indoor FCU 1 (01) FCU 2 (02) FCU 3 (03)
@terrychoo59403 жыл бұрын
Usually 6607 is PCB issue ?
@BonMj3 жыл бұрын
6607 communication problem, normally power trip or outdoor pcb faulty.
@merwingibit76853 жыл бұрын
how to trouble shoot error code 5301
@BonMj3 жыл бұрын
Pls check inverter board. P & N =550 VDC
@bibin38073 жыл бұрын
Bro it good make a details video
@BonMj3 жыл бұрын
Thanks
@merwingibit76853 жыл бұрын
sir tanong q lng pano po itrouble shoot ang error code 5301