@dougking7592 Жыл бұрын
There has been problems with drives here but most only blow when a/c is being used , the one that keeps causing problems I moved the drive for inside to outside above heat section to back wall in with the condenser fans were the drive would have a cover and not get rain on , praying 🙏 for the family and little men
@kenbassett5942 Жыл бұрын
Put a contactor in for the blower. Three pole , 30 amp , 24 volt lug type. On the main board there is a molex plugged into a terminal called control board. The number 7 wire is grey and the number 5 wire is brown. Tap into those 2 wires for 24 volts for blower contactor.
@David-mg2im Жыл бұрын
Next time you go back, check each wire to ground on the incoming power and see if you have a stinger. They may have to put a different transformer into the building or just convert it to a contactor style on the indoor fan. Nice video
@ian504 Жыл бұрын
Took almost a year for us to get the last drive I did. Our supply house told me that Carrier is moving away from those ABB drives due to long lead times.
@jasonjohnsonHVAC Жыл бұрын
I'd be careful the motor isn't a problem. Ive worked on thise many times and the motor was also an issue. Had motors that were megging bad. They will eat up drives/fuses.
@RalphsHeating Жыл бұрын
Use the economizer for free cooling if you can get the blower running.
@EverythingHVACR Жыл бұрын
Those drives are junk, shouldn't be in the blower section, in my opinion.
@georgebrabec1749 Жыл бұрын
Those drives are programed 40 htz cooling and 60 htz heating. I have several go bad on different Carrier RTU's. I replsced the drive with a starter overload combination. Motor has no protection otherwise. 2021 RTU, but the cobdenser coil isn't micro-channel ? That is all we see in Houston
@danobrien3109 Жыл бұрын
Might want to look at the buildings electrical. From what you described their business is they may be over taxing the electrical panel and causing some of these problems on the electrical side. The refrigerant leak is totally a manufacturer defect. I just installed a rtu last week with “ V-Line “ blower assembly. Rather a cool idea, unit is designed like a turbine and you dial in the speed and amp draw on a separate board in the control panel. It is an ICP unit so I imagine Carrier is using it as well. Maybe they have realized these drives are a bust.👍🇨🇦
@williamserver4332 Жыл бұрын
More "green" garbage like the biodiesel sludge we have east. Great video.
@JuanJuarez-en5xn7 ай бұрын
What’s the brand of the leak detector you using?
@scottporchik968 ай бұрын
Another issue which I see is where the manufacturer is mounting the Drives. I always see them fail more often when they are in a non neutral area….
@randyhuff1983 Жыл бұрын
Sad state that a 2 yr.old unit is basically shot.
@arthouston7361 Жыл бұрын
There are some people in the comment section here that are concerned about the building electrical system, and the blower motors themselves, and my experience suggests that neither of those are causal factors……and the drives are just plain junk.
@stephenbullock-yn3vh Жыл бұрын
Your totally right on this unit.the quality has gone down the tubes carrier disgrace me.they had great units back in the day. I hate that government stuck there business on eco ( less power consumption on evaporator motors.burns my arse
@weld3z Жыл бұрын
Where is the warranty ?
@elvingheatingandcoolingllc30837 ай бұрын
Good one
@AmericanFarmerHVAC2024 Жыл бұрын
Holy balls man.. I'm pissed for you. That's just unacceptable. 10s of thousands of $$ for a company to purchase, and double that for what a customer is paying. And why aren't they trying to make any improvements to these designs? They're built to fail these days. Just think if engineers listened to techs....
@DEW409 Жыл бұрын
Stupid government efficiency regulations coupled with the desire to maximize profits equals JUNK!
@wonderhomie2011 Жыл бұрын
The board in the middle sends communication to the VFD to tell it run at 50 or 100%. Carriers VFDs will FAIL, 100% within a year. Its in a poor location. They even put bypass connections because maybe they know something 🧐. If your customer wants, get rid of the VFD and place a contactor and look for a grey wire from the IFB connected to that middle board. Thats G 24V.
@jeremymanning6967 Жыл бұрын
That sucks. And they only come with a 1/1 warranty. Customer paying for this? I’d try to have carrier pay the bill.
@DW-bo3qw Жыл бұрын
No you had it right those ABB drives are junk…just take it out and put in a contactor and be done with it
@zackdepalma6184 Жыл бұрын
Stuff isn’t made like it used to be back in the day
@10minutenewhampshirebreak77 Жыл бұрын
ABB drives, they don’t survive cold weather. Also all the manufacturers have to address the condenser coil issues, coils are failing everywhere from what I’ve been experiencing.
@leviweltin1163 Жыл бұрын
York units are especially bad. Aluminum micro channeled coils are like leak city. 🤢
@10minutenewhampshirebreak77 Жыл бұрын
@@leviweltin1163 yeah, I’m not thrilled about this I have a customer with a trane rtu on it’s third coil in four years. It sucks because they think I’m doing something wrong. I have way better things to do than replace condenser coils on rtus.
@leviweltin1163 Жыл бұрын
@@10minutenewhampshirebreak77 Yeah, the only thing we can do with this cheap junk is to double down on our preventative maintenance and limit the repairs we can prevent. 😬😏
@itsmemsti Жыл бұрын
Why not cool with the economizer?
@MiHeatingGuy Жыл бұрын
The fan doesn't run 😭
@mikev.1034 Жыл бұрын
👍👍
@richlikeg3722 Жыл бұрын
Just bypass that drive, put a new coil and you back up. One less thing to deal with
@jrsaubert1 Жыл бұрын
I make them send me a whole new unit
@steveblake8766 Жыл бұрын
193 thumbs up
@buffydog21 Жыл бұрын
Too bad these air conditioning units didn't have an OBD port, like in a car. So, you could scan the computer system and didn't have to deal with blinking lights.
@tschuuuls486 Жыл бұрын
I mean they invented those newfangled liquid crystal displays. And even a $5 microcontroller can display stuff on there. But that's out of budget for US customers, i guess. I mean I can get a smartwatch shipped from china with a color screen, for $10, which includes a screen and bluetooth radio. But looking at the integration in these units, it's pretty obvious they don't want to spend any money and do the minimum. Why don't they use a custom VFD solution that can actually handle the environment for a start. No VFD on either condensor fans or compressors, a $300 bottom of the barrel Chinese Midea heatpump has most of those problems sorted.
@hardies1 Жыл бұрын
Actually I could see that that unit had a Honeywell controller on it that should be able to display any errors that have occurred and also allow you to configure and test different functions of the RTU. From what I have seen in previous videos though, I don't think Joe knows how to run those controllers and so he pretty much ignores them.