NorthStar PTO Generator on Kubota B7100 Tractor

  Рет қаралды 57,275

Homestead Engineering

Homestead Engineering

Күн бұрын

Review of the NorthStar PTO Generator
Links:
NorthStar PTO Generator: www.northernto...
WGen9500DF Dual Fuel Generator: amzn.to/3OskShK
WGen6600DF Duel Fuel Generator: amzn.to/3DN9J60
WGen7500 Generator: amzn.to/3kuHwpg
Home Standby Switch: amzn.to/3dUilKm
Reliance Transfer Switch: amzn.to/2Hp5Nix
Generac Transfer Switch: amzn.to/3dZyfDw
30 Amp Cord: amzn.to/3kuvOey
Power Inlet Box: amzn.to/2HtlaWJ
Kill A Watt Meter: amzn.to/3onrD6x
Guide to selecting a backup generator: • Your Guide to Selectin...

Пікірлер: 139
@kylerayk
@kylerayk 3 жыл бұрын
2 things. Thing 1. Ditch the plywood and use angle or channel as a foundation to mount the genny to. Thing 2. Don't leave your power cord from the house to the generator all coiled up. I work at a major pharmaceutical company and we hooked up a giant diesel generator to run a building during a site shutdown. The 500MCM hookup cables didn't need to be run very far to hook the generator up to the building so they left the cables coiled up on a pallet and just hooked up each end. After a couple of hours, someone smelled something burning and it was the coiled up cables on the pallets. It's the same principal as energizing a solenoid coil without being over the armature...gets hot in a hurry.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Good "things" to know. Thanks!
@offgridwanabe
@offgridwanabe 3 жыл бұрын
A true representation of how much how horsepower it takes to make electricity
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Yes! I am thinking of actually using it to measure just what the current horse power of my tractor is by ramping up the load and finding where it fails to supply the load. I am guessing I could get to 5000 watts, 10hp. 2hp for every 1000 Watts. I'll report back the results. Thanks!
@rongray4118
@rongray4118 3 жыл бұрын
Fantastic video! You solved your "pros and cons" by installing a system with battery back up. You don't need two tractors! My wife and I are preparing to build an Earthship Biotecture style home in Northern Nevada...this is a means to generating power until the 4.6 kilowatt solar is installed. Blessings and Good Cheer to you and your family!!
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
So this system will get you by until you get your battery backed solar. Once you have that, this system will work great but of course by that time you won't need it. That's life... :)
@thatguyc5899
@thatguyc5899 3 жыл бұрын
Dave, I built nearly an identical setup about 6 months ago. I used a Winco 10kw (made in the USA), and the same carry all. Winco wanted $650 for their gen carrier. As others have said, I would not use it for continuous power but running it a couple of hours a day to keep the freezers cold and other items charged is all one really needs to do.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Yes, a couple hours a day should do the trick, The way I am using it, I only need to run it a couple hours per week and I with 200 gallons of diesel I expect I could go for about two years without utilities. Thanks!
@privacyatty
@privacyatty 3 жыл бұрын
Best video ever. I was thinking about getting one of these as a redundant backup.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Thanks!
@av1204
@av1204 3 жыл бұрын
This is my exact set up. I have a propane connect right under the plug that goes to my solark generator connect. I can use my ck2610 tractor or my propane portable generator. I store 150ish gallons of diesel and my cooking is from propane with a 330lb tank.
@davidmcgregor4691
@davidmcgregor4691 3 жыл бұрын
Great video, thank you for posting. Inherited one of these....Haven't even had time to look at it yet. Didn't realize it needed to be grounded-LOL.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Thanks for watching!
@HomesteadEngineering
@HomesteadEngineering Жыл бұрын
Update: If your connecting this to your house via a transfer switch and pass the neutral and ground through to your main panel, then you probably should not ground it at the generator. Consult an Electrician. Thanks!
@HerkCC
@HerkCC 3 жыл бұрын
Have the generator on the trailer they sell,. It does an awesome job coupled with my B2620
@jaybalukas6921
@jaybalukas6921 3 жыл бұрын
I run the 10000 on my 1025 deere it runs the house and the barn just fine. The tractor does use a lot of fuel. I bought a fifth gallon portable tank with a pump to keep the fuel close to the tractor when it’s hooked up. But they work great.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Thanks for sharing
@phatrides222000
@phatrides222000 2 жыл бұрын
thumbs up for the wicked grapple!
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
Thanks!
@jimmotormedic
@jimmotormedic 3 жыл бұрын
I would have thought that the tractor would have a governor that would compensate for various loads. Loading that engine down a bit won't hurt a thing and is actually beneficial. We run a kubota rtv since new and has just shy of 10 k on it. Runs a minimum of 3 hrs a day 365. From time to time I hook up something heavy to it a give it a good long run under heavy load. Smoke starts out blue then grey then black, cleans up and it loves it. Great little engine
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
I love hearing accounts like this. I do baby my equipment a bit but on occasion I do run them hard so I like hearing from folks saying that its OK and they have done it plenty with good results. Thanks!
@BluesTheBestBoyIGuess
@BluesTheBestBoyIGuess 2 жыл бұрын
If you plug it into your home circuitry you don't need the ground rod, It grounds through your system. Just make sure the 240 circuitry/receptacle is grounded to your breaker box. The ground rod is only required if you run it out in the field or if you run an extension cord that's not grounded to the house.
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
I agree. Thanks!
@ulhpilot7757
@ulhpilot7757 2 жыл бұрын
It’s called neutral bonding, but check your manual to be sure.
@thegrumpyyooper6503
@thegrumpyyooper6503 3 жыл бұрын
Just a suggestion. The generator is designed to run at a steady 540 RPM so instead of messing with the throttle set the engine RPM’s so they are just above the engine RPM needed to maintain 540 RPM to compensate for the surge when a load is added. The other thing to consider is by not running the generator at its designed RPM when there’s a load on it you’re going to put a serious load on the generator with the possibility of burning the generator out and damaging sensitive electronics in your house by giving them too low voltage. When I had my fifth wheel I had a surge protector that would cut the power off if the voltage dropped too low to protect the electronics in the fifth wheel the same principle applies here as well too low voltage is just as dangerous to electronics as a massive voltage surge. Burning a few extra gallons of Diesel is a lot cheaper than replacing the generator and damaged electronics.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Hello David, the problem is that you have to adjust the throttle to maintain the 540 RPM. This tractor and most tractors do not have the ability to maintain the RPM under varied loads. When large loads are added, the RPM drops and you have to adjust the throttle to maintain the proper RPM. When large loads are removed, the RPM shoots up past 540 and the throttle must be reduced. The way I am using it, I just keep the load constant for 2 hours while charging my solar batteries. That eliminates the problem. Thanks!
@thegrumpyyooper6503
@thegrumpyyooper6503 3 жыл бұрын
The tractor should compensate for the load on its own to some extent because the fuel pump has a governor that should increase the fuel to compensate for the the extra load. If the tractor is not adjusting for the load on it’s own the governor may be stuck and not allowing the pump to adjust the fuel for the load. The other possibility is engine is starting to get tired even on the bigger AG tractors 5000+ hours is a lot depending on how they’re used/maintained and will start to show a decrease in performance.
@KALI1080
@KALI1080 2 жыл бұрын
​@@thegrumpyyooper6503 The governer on a mechanical garden tractor engine is not going to work well for a generator. This is shown in the video. Gensets use isochronus governers. Isochronus governers maintain the speed of the engine regardless of engine load. This tractor does not have an isochronus governer. I would bet that generators like this would function better with a newer tractor that has an electronically controlled fuel system, as engine speed does not drop when load is applied.
@DMahalko
@DMahalko 2 жыл бұрын
Generator RPM is not all that critical. The charge controller does not care at 9:25 that the frequency dropped way down and keeps accepting it, no problem. Modern electronic devices with switchmode power supplies do not care much about the frequency or voltage. Induction and synchronous motors will just run a little faster or slower. Power utilities keep a tight leash on frequency because their customers are annoyed by the flickering of incandescent lights when large loads are turned on and off, and also because old mechanical clocks used synchronous motors that exactly followed the grid frequency. To keep the time correct on these clocks, the grid frequency had to average out to exactly 5184000 cycles every day. If the grid voltage went up too much, incandescent lamps would glow brighter and brighter until they rapidly burned out from running so hot. A "brownout" meanwhile is when voltage drops, and incandescent lamps glow dimmer, changing the color from white, to yellow, to reddish-brown.
@ulhpilot7757
@ulhpilot7757 2 жыл бұрын
It’s because the tractor is under powered. My JD 1025R runs my 10KW PTO generator without needing to adjust engine RPMs regardless of the electrical draw. I set the output at slightly over optimal rpm’s and leave it.
@TheSHOP411
@TheSHOP411 3 жыл бұрын
Nice. You have some nice stuff there. I just got a 10k generator and now I have my 5k as a backup. I thought about the pto generator but I only have one tractor. Lol edited: I had posted this right before your cons. Only having one tractor is the big setback.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Good excuses to get that 2nd tractor! :)
@TheSHOP411
@TheSHOP411 3 жыл бұрын
@@HomesteadEngineering well technically I have two but I keep the other one on our property/tree farm but I am getting the bug for a much bigger tractor. Gonna keep a lookout for an older model. These new tractors with the regen modes don't impress me. Love that battery bank you have.
@sandywhite2738
@sandywhite2738 2 жыл бұрын
Nice set up, I thought you had the ghost containment system from ghostbusters of the wall.
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
LOL!
@charlesvincett84
@charlesvincett84 3 жыл бұрын
Triple power redundancy at your place....nice....
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
I can run off the utility, solar, batteries, or any one of four generators. Two generators run gas, one diesel and one gas or propane. I got the power! :)
@charlesvincett84
@charlesvincett84 3 жыл бұрын
@@HomesteadEngineering no kidding....wattage for the cottage..😁👍😎
@ajfarms630
@ajfarms630 3 жыл бұрын
This feller has got some money!
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
I had some money until I bought all this stuff! :)
@lightning4871
@lightning4871 3 жыл бұрын
You are an amassing prepper.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Thanks!
@sh839c
@sh839c 3 жыл бұрын
Nice unit, I was just looking at these yesterday. I just sold my military trailer-mounted Onan generators because the power hasn't gone out once in 6 years. That was probably a mistake. Anyway, looking at one of these now. IMD makes one with avr as well. You are correct, much better THD with these generator heads.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Uuuummmm yah, should have hung on to one of those for sure. :)
@hootowlholler3760
@hootowlholler3760 3 жыл бұрын
26 Nov 2020 Hi David. Just wanted to wish you a 🍁Happy Thanksgiving! Hope all is well in DavidLand.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Hello Hoot and happy Thanksgiving to you too! We had some company and I have been working hard the past week getting ready. Trimming, weeding, mulching and pressure washing. Puttin on the dog... :)
@davesusek3330
@davesusek3330 Жыл бұрын
Thankyou very helpfull.
@HomesteadEngineering
@HomesteadEngineering 10 ай бұрын
Thanks!
@ulhpilot7757
@ulhpilot7757 2 жыл бұрын
Instead of hanging the generator off the back of the 3pt frame, shorten the PTO shaft. It’s not that hard to do. Also the long shaft is dangerous as it could damage the tractor PTO housing if the shaft is jammed into it.
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
Probably not a bad idea to shorten the shaft and move the generator forward on the 3 point. As it is there is plenty of play in the shaft so as not to jam. Thanks!
@wildbill23c
@wildbill23c 3 жыл бұрын
That's a really expensive cell phone charger LOL. That's a great setup, for like you said if you have multiple tractors so your only tractor isn't tied to your generator...although in a pinch its not that hard to unhook and hook back up if you needed to use your tractor to remove snow for example, then hook back up to your generator when you are finished...but having a dedicated backup generator would be the only way I'd go, if I had propane on site...in a power failure I'm not sure how natural gas supplies might get interrupted as the pumps probably shut down too I'd assume. I have a 225 gallon propane tank that just my furnace runs off of, if I got a backup generator I'd go with propane and just have a larger tank brought in. I don't have a tractor so a PTO generator wouldn't exactly be useful for me LOL. I do want to get a tractor just a lot of other things have gotten in the way this year, and its been 30 years already so what's another year or 2 waiting LOL.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
William, you might like this dual fuel generator: kzbin.info/www/bejne/nmrZp6ZontGIf9E
@peanutsmith1462
@peanutsmith1462 Жыл бұрын
That little tractor needs to be worked like that it’s not going to hurt it keep the oil changed and regular maintenance it will last it will seat the rings on the piston
@HomesteadEngineering
@HomesteadEngineering 10 ай бұрын
Yes, I have been pushing it a bit harder but not too much going forward. Thanks!
@beingsneaky
@beingsneaky 2 ай бұрын
Yeah, I would put a gate right next to the door. Heck even take the fence down.
@HomesteadEngineering
@HomesteadEngineering 2 ай бұрын
This is how I use it now: kzbin.info/www/bejne/o3-yq3WdgpqEercsi=VYLusNaSv5LCmH0v
@andylamm5571
@andylamm5571 3 жыл бұрын
With all due Respect. You must be an Engineer or something by Trade and have some deep pockets. I was following along pretty good until you walked in the Garage around the 07:00 minute mark of video when I saw that wall of Star Trek Guidance Systems, LOL...and I was lost!. I've been thinking about getting one of those Generators for my MX5400 KUBOTA. But after seeing what all it takes to transfer power to house, I'll probably just get some more coolers and build an outhouse! LOL. Thanks. Hurricane Ally. S.E. North Carolina. 15 miles from Coast.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Beefan, I hope I did not give you the impression that you have to have all this to connect to your house. You can connect with just a transfer switch or even extension cords but you must be mindful of the RPM (Voltage) as it changes with the loads. Thanks!
@andylamm5571
@andylamm5571 3 жыл бұрын
@@HomesteadEngineering oh, ok, thanks Mr. David. That makes me feel better. All my best.
@wildbill23c
@wildbill23c 3 жыл бұрын
@@HomesteadEngineering You also need to make sure you aren't back feeding power through your main service panel and back out into the main power lines if you are grid-tied....not really an issue if you are 100% off-grid though. Many people don't realize when they 1/2 ass hookup a generator to their house mains that its back feeding that power back out into the main electric lines and can injure or kill a line worker trying to restore power.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
@@wildbill23cYes, you need to use an actual transfer switch NOT a suicide cord like you see some folks do. Thanks!
@joemamaluc312
@joemamaluc312 6 ай бұрын
@@purplesocks9745 A separate 30 amp (in this case ) 2 pole breaker directly under the main breaker. You mount a rocking on off device that either keeps the main in and the 30 amp out, or the 30 amp in and main out. That will conform to code.
@BrianPhillipsRC
@BrianPhillipsRC 3 жыл бұрын
Was your cable going between the Gen and the Wall getting hot? I thought you mentioned it was a 30 amp plug. Wither way, at 78Amps was the last reading I saw, and such a cool setup! Makes me jealous!!! Now I want to copy you, only with a 60 hp tractor.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
OK, I was not very clear about this... The Amps you see on the solar power are relative to the battery voltage seen just to the left. So 90 Amps at about 55 Volts = about 5000 Watts. That's well within the (240V) 30 Amp circuit (7,200 Watts). Ya follow or am I just making it worse?
@1of7
@1of7 2 жыл бұрын
Great info and video. How would you rate the NorthStar PTO Generator after a year and half usage. I have a 1988 B8200 I've owned since new. It has been great and I'll keep it forever. I'm looking to purchase a PTO generator and would like to hear any additional comments from you. Thanks for the video. Very helpful.
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
I run it about every 3-6 months for about an hour or two just to keep it in shape. It has worked perfectly with no issues so far. I run it at about 3-4k Watts output to charge my battery bank. Nothing bad to report. :)
@1of7
@1of7 2 жыл бұрын
@@HomesteadEngineering Thank you for your response. Good info.
@PaulTaylor-ko8jy
@PaulTaylor-ko8jy Жыл бұрын
Good old cooking oil always works for me LP cylinders and good old cooking oil or Willie Nelson's gas always works for me moonshine gases even better
@tomashbaugh8891
@tomashbaugh8891 2 жыл бұрын
Dave, those Kubotas have multiple pto ranges correct? Would that help or hinder? Can someone respond with knowledge or experience? And did you try with your 2601? Thank you
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
Yes, My B7100 has high and low range on the PTO. I run the generator in high range. I can run it in low range and it has more torque that way but it revs too high. I have run it many times now and have slowly gotten more comfortable running it with higher loads. It does just fine, no problems so far. Thanks!
@hootowlholler3760
@hootowlholler3760 3 жыл бұрын
Hi David. Love your channel. I would worry about my tractor. Did you keep this one?
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Hello Hoot, I am keeping both the tractor and the generator. I have owned this tractor for 20 years. I don't think I would use my new tractor to run the generator but it is a good use of my old tractor to get a lot more life out of it. Thanks!
@hogrush
@hogrush 2 жыл бұрын
You don’t want your pto shaft perfectly level. That’s where your vibration is coming from. Each joint needs a bit of an angle. Look at your truck driveshaft. Make the pitch similar.
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
I will definitely check that out. Thanks
@notsoserious0944
@notsoserious0944 3 жыл бұрын
Have some doubts about the diesel burn rate although buying a stand alone, self-regulating diesel gen would pay for a lot of oil.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
I don't have the exact burn rate but I think it would be around 0.5 gallons/hour. I guess I will just have to do a test or just measure it during the next time I have to use it. Thanks!
@notsoserious0944
@notsoserious0944 3 жыл бұрын
@@HomesteadEngineering Had some thoughts about running one on my BX (22 hp) with a five gallon tank. Running close to WOT (probably) it wouldn't make it through the night. I would be burning the same diesel, loaded or not which I find annoying :-/
@Annon89
@Annon89 Жыл бұрын
Be careful that you aren’t grounding the generator when you are plugging it into a grounded system. You only want one grounding path. If you have two when something happens you could energize the generator and the ground around it.
@HomesteadEngineering
@HomesteadEngineering Жыл бұрын
I believe that is correct. In general, I would ground and bond a generator when used stand alone and not ground or bond it when connected to a transfer switch. That is because the ground and bond from the generator will usually pass through the transfer switch and be grounded and bonded at the main panel. Thanks!
@joemamaluc312
@joemamaluc312 6 ай бұрын
Today, Systems typically have two paths to ground. One a domestic water supply and two a driven ground rod. Depending on impedance, you may have ore than one ground rod.
@BGWenterprises
@BGWenterprises 2 жыл бұрын
My uncle had one of those 80s early 90s hydrostatic b7100s, It had a 2 speed pto. . Is it possible you didn't have it in the 540 speed? Usually rated engine speed for a set pto rpms is quite near high idel, or maximum rpms of engine. The engine just sounds closer to mabe 2k but I could be wrong. Though it's interesting to consider running a light load with a gen at rated speed, but under speed the engine for possibly reducing fuel use a smidgen. 0.01c
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
Hello Bruce, I had the PTO in high gear. I can run it in low gear but it revs much higher for sure. Its actually pretty good on fuel consumption. Thanks!
@kb6069
@kb6069 2 жыл бұрын
What a great video, I am trying to set up something very similar to this set up. I have a question if you don’t mind. If you had a bigger horse power tractor to a smaller generator would that be a problem? My tractor is 35hp (engine) and I’m thinking about a 7,200 generator. (14 Hp. Recommend pto) Is that some kind of problem?
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
KB, As long as the PTO shaft is turning at the right RPM it should not matter how much HP the tractor has. I don't see having too much potential HP as being any kind of problem at all. You simply won't be using all that extra HP. Off the top of my head I think it takes about 2 HP for every 1000W of electricity. It will probably be a bit less efficient but it should work fine. Thanks!
@paule.harrison4044
@paule.harrison4044 3 жыл бұрын
Hi and thank you for the video! Is the oscillation from the driveshaft, tractor or generator? Thanks!
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Paul, I am not sure yet but I guess its from the PTO drive shaft (not the tractor or genny). I may try to balance it. Thanks!
@freakerhunter8857
@freakerhunter8857 3 жыл бұрын
About how long do you have until you have to fill up your tractor with fuel after continuous running of the generator?
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
I will have to do a test to find out exactly. My wild guess would be about 10 gallons for 24 hours running at 3000 watts output. Just a guess.
@freakerhunter8857
@freakerhunter8857 3 жыл бұрын
@@HomesteadEngineering that would be my guess as well. My farmall Super H does about 14 hours give or take at around 3/4 throttle. Just gotta change the oil after a few longs days of running.
@larryvisser1086
@larryvisser1086 3 жыл бұрын
We’re you not able to cut the PTO shaft to bring it closer in?..
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Larry, I don't know why I did not even think of that. I may go back and shorten it up a bit. Thanks!
@mainelyelectric
@mainelyelectric 3 жыл бұрын
I have a B2650 that’s setup for a front snow blower with the center PTO running down under the front axle to a set of pillow block bearings with the PTO spline shaft there where the shaft of the blower connects to But I was always wondering if I could DIY/weld build a small generator attachment for that shaft! When I am actually running the snowblower that shaft is turning at 2600 RPM I was hoping I could design some type of generator head that could directly couple between that shaft with a universal joint and run at the engine speed but generator heads either run at 4 pole 1800 or 2 pole 3600 rpm But I could set the engine lower and always raise the RPM with a gearbox for a smaller generator head.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
That sounds like a fun project. Good luck!
@PaulTaylor-ko8jy
@PaulTaylor-ko8jy Жыл бұрын
Taking a farm tractor use it as a generator or a car or anything else to use it as a generator farm tractors much easier to take the back of it up use as a generator power your lights
@Burago2k
@Burago2k 3 жыл бұрын
How is the kubota worn out, it looks like its in perfect condition, you yourself said even the engine is good, i think thats because of your newer tractor, thats what puts it in your head that its worn out
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
The engine is definitely good and the tractor still has some life in it. I actually use it all the time. It is a bit worn though. The joints are a bit loose and have a lot of stiction. It is difficult to switch from 2 wheel to 4 wheel drive. Its just used. It is very noticeable when switching from this one to the new one for sure. Thanks!
@tjellis1479
@tjellis1479 3 жыл бұрын
was the seperate driveline $375.00 usd?
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
It was $110 from Northern Tool : www.northerntool.com/shop/tools/product_200596633_200596633 Note: it is only 16HP max
@Bman01234
@Bman01234 2 жыл бұрын
I’d like to do a similar setup on my X758, how much hp is your tractor?
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
Brendan, I believe it was 16HP when it was new and probably less now. Not sure but I would guess you need 2HP for every 1000W of generator and I don't like to run my equipment at 100% duty cycle. Thanks!
@PurpleCollarLife
@PurpleCollarLife 3 жыл бұрын
6:45- amazing battery bank and solar system! Nice work. We found your channel from a comment you left on GP Outdoors. Sub'd! We'd really appreciate if you would look at our channel if you aren't already following us. Thank you!
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
I'll check it out. Thanks!
@PurpleCollarLife
@PurpleCollarLife 3 жыл бұрын
@@HomesteadEngineering Thank you!
@jerryhayden8720
@jerryhayden8720 3 жыл бұрын
About what year is your old Kubota tractor?
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
About 94ish
@jerryhayden8720
@jerryhayden8720 3 жыл бұрын
@@HomesteadEngineering just wondering. I like the way it looks and am thinking about looking for a older subcompact tractor. I've had so many of the Craftsman and MTD ones that I'm wanting to get something better but can't stand to pay what they want for the new ones and they even want so much for one day 5 years old that ya may as well get a new model. Anyway I liked what I saw in yours. Thanks for the reply.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
@@jerryhayden8720 The old B7100 has served me well for over 20 years now. I have moved the world with it. I paid $7,500 for it used and I think its worth maybe $5,000 today. That said, there is a WORLD of difference between the old tractor and the new one. The skid steer quick attach alone makes a huge difference. The quick hitch makes a big difference as well. Power steering (huge) and a faster moving loader. Three speeds and easy four wheel drive. I paid $25k for the B2601 and a bunch of attachments. Ho[e you find what your looking for.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
@@jerryhayden8720 More tractor videos: kzbin.info/www/bejne/qKTap3ljp5aHiKc
@LemuelDunleavy
@LemuelDunleavy 2 жыл бұрын
What are the real world applications for this? Just curious.
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
Lemuel, I use it to charge my solar battery bank when there is no sun for a few days. I would plan to use it more in case of any type of emergency. Thanks!
@LemuelDunleavy
@LemuelDunleavy 2 жыл бұрын
@@HomesteadEngineering Ok. Cool! Thanks for answering!
@taylorsutherland6973
@taylorsutherland6973 Жыл бұрын
Definatly shorten the shaft
@robertduncan2742
@robertduncan2742 3 жыл бұрын
What about pulley sizing
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
What pulley?
@PaulTaylor-ko8jy
@PaulTaylor-ko8jy 10 ай бұрын
Like it wood work better Paul Taylor good size generator
@derrickdrew17
@derrickdrew17 3 жыл бұрын
That tractor only has 13hp pto.. thats not that much, try it on your other kubota. It should have a tad bit more pto hp
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Yah and that's when it was new and on a good day. Its fine for what I need to do. It can charge my battery bank in 2-3 hours. I don't really want to use my new tractor for this purpose. Thanks!
@derrickdrew17
@derrickdrew17 3 жыл бұрын
@@HomesteadEngineering i thought i read that you didn't, yea in a emergency, the bigger one will do if you really are in a bind
@tarstarkusz
@tarstarkusz 2 жыл бұрын
This is really inefficient. Whatever money you saved not buying an engine generator will be spent in gas. Generators are set up by the manufacturer to be well matched to the engine and you get the highest BSFC possible. Not to mention inconvenient. Also, if your load drops, you could have a blown engine. If you have the throttle up to deal with a high load in your house and that load disappears, there is no governor to close the throttle. These are meant, so far as I can tell, for remote farm work.
@HomesteadEngineering
@HomesteadEngineering 2 жыл бұрын
It has been my experience that the PTO running off my tractor uses a lot less fuel than my engine generators. I would guess maybe 0.6 gallon/hr. Dropping the load would result in a near instant increase in throttle. I don't think this would result in a blown engine unless you were at very heavy loads and not present. You do make a good point though and something folks should be aware of for sure. Thanks!
@matthall9093
@matthall9093 3 жыл бұрын
Pto shaft is def out of balance
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
How would you balance it? Maybe I will try pulling it apart and rotating one click then put it back together. That might shift the rotating masses a bit (if that's possible).
@HerkCC
@HerkCC 3 жыл бұрын
Dude ....no it isn't. Optical illusions with the safety sleeve.
@matthall9093
@matthall9093 3 жыл бұрын
@@HerkCC the pto shaft would be the only thing to cause the wobbling and vibration. My 30 years of grey hair experience speaking here. I have bought many a pto shafts off the shelf, made in China that are bent, out of alignment or not balanced properly. Another recommendation is to not have the pto shaft running in alignment with the implement. They tend to run smoother at a slight angle.
@matthall9093
@matthall9093 3 жыл бұрын
@@HomesteadEngineering I usually take mine to a local driveline shop for balancing. Can be done quickly and inexpensively
@HerkCC
@HerkCC 3 жыл бұрын
@@matthall9093 what hair I still have is gray as well. I believe the overall vibration is from it not being mounted on a solid platform. I run the very same generator mounted on the O.E.M. trailer.....and as you pointed out ....at a slight angle for proper phase of the shaft rotation......but I do see my safety sleeve dance around to mimic vibration when in operations.....
@guytech7310
@guytech7310 3 жыл бұрын
I Wouldn't recommend it since your going to be racking a lot of hours on the tractor. Just go with a standby diesel generator.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
Hello Guy, These diesel engines will typically outlast the tractor by 2-3 times. By running the PTO generator I am getting all the life out of my investment. That said, I would not run it on my new tractor, its only going to run behind my old worn-out tractor. Thanks!
@guytech7310
@guytech7310 3 жыл бұрын
Not with a generator racking up hours. People own & use 70+ year old tractors. Issue is that the hydraulics are running when the engine is running. Especially if that Kubota tractor uses a hydrostatic drive instead of direct drive. If there is a crisis & one machine you really need to rely on is your tractor.
@farmingsmallkubota1783
@farmingsmallkubota1783 3 жыл бұрын
@@HomesteadEngineering Diesel engines need to be worked hard like that so they don't wet stack. will not hurt that tractor at all. My Multiquip Welder Generator has 4300 hours on it and runs at 3600 rpms when generating power not worried a bit. These Kubota engines are used in refrigerator units that run 24/7 well over 11000 hours before an overhaul is needed.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
@@farmingsmallkubota1783 Sweet! I love hearing that because I do run that little Kubota pretty hard in my garden as well. Maybe I will crank it up a bit higher next time I need to charge the batteries. Thanks!
@matt426h
@matt426h 3 жыл бұрын
As a fellow B7100 owner I was curious as to how the tractor would perform. They were built like tanks but lack the higher hp of today’s tractors of similar size. Evidently the internal governor cant match the power demands of the generator as it would with a mower or tiller. The generator rpm needs are too sensitive. From what I’ve been told the general rule of thumb for engine hp to generator wattage is roughly 2 hp per 1000 watts. The b7100 according to kubota is 16hp at the flywheel and 13 at the pto. So you are probably maxing out the engine around 6500 watts and considering the hours on the tractor the actual power numbers might put you down closer to 5500 watts. If you plan to keep it on generator duty you might want to consider adding a water temperature gauge to the tractor. A simple method would be an inline adapter to hold a temp sensor in the top radiator hose. The majority of the D750 engines didn’t have water pumps and used thermo siphon technology. They like running hot.
@HomesteadEngineering
@HomesteadEngineering 3 жыл бұрын
This was the first time I tried it. In the future, I will just crank it up and drop about 3,000 watts on it and leave it there. No adjusting. Thanks!
@joemamaluc312
@joemamaluc312 6 ай бұрын
I dropped a D950 in my B7100, That extra HP makes it a beast. Full set of gages, Alternator with a real water pump. I push snow with it, never bogs, nothing stops it except loss of traction.
Emergency Preparedness - PTO Home Generator
14:26
Living Our American Dream
Рет қаралды 3,4 М.
Power Your Home with Your Compact Tractor! PTO Generator Pros & Cons!
25:08
Tractor Time with Tim
Рет қаралды 83 М.
The Joker wanted to stand at the front, but unexpectedly was beaten up by Officer Rabbit
00:12
规则,在门里生存,出来~死亡
00:33
落魄的王子
Рет қаралды 27 МЛН
哈莉奎因怎么变骷髅了#小丑 #shorts
00:19
好人小丑
Рет қаралды 55 МЛН
Cheap vs. Expensive Generator (Surprising Results)
25:49
Ambition Strikes
Рет қаралды 733 М.
DuroStar Diesel Generator - No Power Output Since New
1:45:56
James Condon
Рет қаралды 188 М.
Best Tax Return Ever?! We bought a 1977 Kubota B7100
22:46
Three Creeks Towing & Off-road Recovery
Рет қаралды 7 М.
WINCO 15KW PTO generator first run on the KUBOTA
8:14
The Salty Paultard
Рет қаралды 9 М.
Predator 5000 generator running the ENTIRE HOUSE ( full cost and setup )
27:44
Flail Mowing - Kubota B7100
7:16
Jared Watson
Рет қаралды 217 М.
NorthStar PTO Generator on Kubota B7100
13:58
Homestead Engineering
Рет қаралды 4,7 М.
Restoring a Tractor PTO Powered Generator.  Now it's a Mobile Welder and Whole Home Generator
18:35
Country View Acres (Formerly Smalltown442)
Рет қаралды 127 М.
CHEAP & SAFE Way to Connect My PTO Generator, Will It Power The Entire House?
19:12
The Joker wanted to stand at the front, but unexpectedly was beaten up by Officer Rabbit
00:12