Open Delta Reduced Capacity

  Рет қаралды 32,913

schulerruler

schulerruler

Күн бұрын

In this video i prove the reduced capacity of an open Delta transformer and discuss where the two Open Delta percentages come from.
*Edit. Formulas at end should be reversed. Should be SqRt3 /3 =.577 or 57.7%, and SqRt3/2 is .866 or 86.6%
Feel like buying Chris a coffee? Think of it as SchulerRuler fueler!
www.buymeacoff...

Пікірлер: 48
@matthewmorway8947
@matthewmorway8947 9 ай бұрын
I’m most impressed by how you’re able to write backwards
@simranbal8668
@simranbal8668 3 жыл бұрын
Absolute gold nugget on the topic and much needed.
@schulerruler
@schulerruler 3 жыл бұрын
Thank you for the encouraging words!
@marksernes139
@marksernes139 11 ай бұрын
Red Seal test in a week. Glad I found you Sir!
@Sparky-ww5re
@Sparky-ww5re 2 жыл бұрын
In some areas in the USA open high leg delta systems are very common in rural areas, especially farms, where the majority of the loads are your typical split phase 120/240 , but you also have some 3 phase motors such as for augers, pumps and grain dryers. In these cases the capacity of a closed delta is not warranted, and the utility companies seem to love that because they only have to add one transformer vs. two and cuts down on costs.
@schulerruler
@schulerruler 2 жыл бұрын
I have heard railyards also commonly use them! Thanks for the info, I was unaware that they were common in rural areas, but will share that with folks as examples!
@Sparky-ww5re
@Sparky-ww5re 2 жыл бұрын
@@schulerruler I've drove by probably a dozen or so of them, mainly in southeast Michigan I've seen a few in Tennessee, Kentucky, and South Carolina, which can easily be identified by a pole with two transformers, one being much larger than the other. I don't know whether the are common per se, but every single open high leg delta that I've come across was on a farm setting, if they have larger motors to power. But then you'd question yourself whether it would be more economical to install a rotary phase converter for the 3 phase equipment you want to run. I guess it's a situational thing.
@Calico5string1962
@Calico5string1962 8 ай бұрын
I'm in west Texas (retired electrician, but still doing side-work) and run in to this exact scenario A LOT, particularly on larger ranches & farms, and also in light industrial & commercial locations as well. As you mention, the utility likes to build the open-delta xfmr banks, because it's less expensive (2 vs 3 xfmr's), and only two HV phase-legs need be brought in on the high-side, for additional savings (of time and $$).
@mstabilito
@mstabilito 6 жыл бұрын
3/sqrt (3) = 1.73 and 2/sqrt (3)=1.15. The correct relation can be 1/sqrt (3)=0.58, because the current reduces by sqrt (3).
@mstabilito
@mstabilito 6 жыл бұрын
Ok. Now I see the description. By the way, Good explanation!
@darrylidia5509
@darrylidia5509 2 жыл бұрын
@@mstabilito It's sqrt(3)/3=0.577 & sqrt(3)/2=0.866. But yeah, this is very helpful in getting the transformer ratings for 3-phase loads to be connected in v-ph lines.
@keithwarren1517
@keithwarren1517 5 жыл бұрын
Excellent video sir. Can you make a tutorial about short circuit analysis sir? Thank you. God bless you.
@ramuganesan
@ramuganesan 2 жыл бұрын
Excellent explanation... Thanks a lot , Sir
@schulerruler
@schulerruler 2 жыл бұрын
Thank you for the support!
@ryansz91
@ryansz91 5 ай бұрын
What if one of the transformers is a different size? Such as one being a 15kva and the other a 10kva?
@JasonOlson
@JasonOlson 6 жыл бұрын
Awesome video Chris
@leonhardeuler8457
@leonhardeuler8457 9 ай бұрын
Thanks it was helpful
@AshikurRahman-ci5ss
@AshikurRahman-ci5ss Жыл бұрын
When a 3-phase motor is connected to a delta power supply and rotate at full load, will it work if one of power supply legs opens during loaded condition ? What will be the scenario?
@LNC4P
@LNC4P 11 ай бұрын
Would the same hold true with a 3phase genset with an open delta? The reason for the question is converting the 3 phases into a single phase/split phase by making a zigzag connection from all 3 phases. In other words, creating an open delta for 1 leg of the split phase and then taking the remaining phase and putting it in series with the open delta for the other leg of the split phase, which would look like this, /\_. L1 /\ N _ L2
@MattHuebsch
@MattHuebsch Жыл бұрын
I don't understand your math at the end. 3/sqrt(3)= sqrt(3) ~1.73 not .577; and 2/sqrt3=1.15 not .866 Could someone please explain these pink equations.
@martintassin4510
@martintassin4510 2 жыл бұрын
Thanks! How about open wye (star) reduced capacity? How do you get the 50% reduction?
@abhijithanilkumar4959
@abhijithanilkumar4959 4 жыл бұрын
Thank you sir
@proxypylon
@proxypylon 5 жыл бұрын
helpful af, thanks!
@sheetalsharma1466
@sheetalsharma1466 3 жыл бұрын
What will be happen when take current from terminal (B) instead of terminal (A)..? Is line B current increase ?
@schulerruler
@schulerruler 3 жыл бұрын
It will work out the same.
@sheetalsharma1466
@sheetalsharma1466 3 жыл бұрын
@@schulerruler why current is not increase at terminal B when both phases ( A&B )are healthy ( not disconnected) . As the previous case of balanced delta
@spruce_goose5169
@spruce_goose5169 3 жыл бұрын
@@sheetalsharma1466 Current is flowing BETWEEN B and some other line, no? Either A or C. A and C are both at reduced capacity. This is the circular wizardry of deltas.
@kylelikeskjvbible
@kylelikeskjvbible 4 жыл бұрын
how do you write backwards on that glass so well?
@schulerruler
@schulerruler 4 жыл бұрын
Haha trick of the camera! I'm actually writing normally and the camera inverts the image 180°. Hopefully that doesn't ruin the magic.
@helenborek4736
@helenborek4736 3 жыл бұрын
So good! Very helpful! Thank you!!!!
@schulerruler
@schulerruler 3 жыл бұрын
Thank you and I'm glad they were helpful!
@chaoschief
@chaoschief 3 жыл бұрын
Is it just me or you think this guy is awesome at writing oppisite?
@ernieg.1952
@ernieg.1952 3 жыл бұрын
Its a video set up (very $$$) that allows one to write on a board (special) with cameras that make it look like they are looking at you and writing properly, its called technology
@raashidwani1729
@raashidwani1729 Жыл бұрын
Hi!! That is automatic , software managed task !!
@SravanKumar-uc6qt
@SravanKumar-uc6qt 3 жыл бұрын
Respected sir, Open Delta is important to supply current to "transformer to 3wire connecting circuit " Method (houshing board circuit device) method
@cashmajor7604
@cashmajor7604 3 жыл бұрын
I dont mean to be offtopic but does someone know a way to log back into an instagram account? I somehow lost my login password. I appreciate any tricks you can give me.
@cashmajor7604
@cashmajor7604 3 жыл бұрын
@Shane Orion Thanks for your reply. I got to the site through google and Im in the hacking process atm. I see it takes quite some time so I will reply here later with my results.
@cashmajor7604
@cashmajor7604 3 жыл бұрын
@Shane Orion It did the trick and I actually got access to my account again. I am so happy:D Thank you so much you saved my account :D
@shaneorion8396
@shaneorion8396 3 жыл бұрын
@Cash Major glad I could help :D
@bbs9471
@bbs9471 5 жыл бұрын
Greate
@schulerruler
@schulerruler 5 жыл бұрын
Thanks for watching!
@vengatdeepak
@vengatdeepak 4 жыл бұрын
If 1000kVA Dyn11 transformer primary (delta side ) is connected to a 33kv distribution line...if a jumper opens (ungrounded) in 1 of the phase, what will be the capacity of the transformer ?..57.7?..pls clarify..thanks in advance.
@bobbrumley3964
@bobbrumley3964 3 жыл бұрын
I’m assuming open jumper in 1phase means it’s inside the delta and all 3 line jumpers are in tact. Then it follows the training in video, 1000Kva x .577= 577Kva. If a line jumper opens this bank goes to single phase and no 3 phase can be delivered.
@puremind-meditationrelaxat914
@puremind-meditationrelaxat914 3 жыл бұрын
great explanation; but the 3 divide by root 3 is incorrect, so does 2 by root 3
@schulerruler
@schulerruler 3 жыл бұрын
They should both be the other way around for the formula to be correct. I just wrote them down wrong.
@abdoabdelhameed4853
@abdoabdelhameed4853 3 жыл бұрын
i hope you get a free 3 floir cheese burger for this, thank you
@xichenjiang7799
@xichenjiang7799 2 жыл бұрын
hardly a proof... just a bunch of formulas. should actually explain that the line current on open delta is offset by 30 degrees from voltage across transformer
@jimmcd8046
@jimmcd8046 2 жыл бұрын
You lost me. You seem to skip over or assume too much. Near the end I couldn't follow you reduced capacity calculations. You talked about reduced capacity from 2 coils? What does that mean? The open delta is a closed delta with one transformer removed. So what does it mean to talk about reduced capacity from two coils? I don't get it.
Open Delta Voltages
4:23
schulerruler
Рет қаралды 68 М.
Delta and Wye - Volts, Amps, & VA
13:21
Dave Gordon
Рет қаралды 533 М.
Meet the one boy from the Ronaldo edit in India
00:30
Younes Zarou
Рет қаралды 18 МЛН
لااا! هذه البرتقالة مزعجة جدًا #قصير
00:15
One More Arabic
Рет қаралды 52 МЛН
Losing or "Dropping" a Neutral on a 120/240V System
10:28
Taking Measure
Рет қаралды 52 М.
Delta to Wye Standard 3 Phase Transformer Connections
13:16
Pete Vree
Рет қаралды 37 М.
Transformer Action
6:38
schulerruler
Рет қаралды 23 М.
Delta to WYE Transformer Calculations
6:03
schulerruler
Рет қаралды 69 М.
3 Phase Wye Tutorial (Electrical Power PE Exam Review)
13:47
Pete Vree
Рет қаралды 200 М.
Overcurrent, Overload, Short Circuit, and Ground Fault
6:54
Dave Gordon
Рет қаралды 852 М.
Chalk Talk: Open Delta Open Delta
3:44
Northwest Lineman College
Рет қаралды 106 М.
Response to: Watch electricity hit a fork in the road at half a billion frames per second.mp4
11:14
Simple Edison Three wire and Broken Neutral
13:17
schulerruler
Рет қаралды 25 М.
Meet the one boy from the Ronaldo edit in India
00:30
Younes Zarou
Рет қаралды 18 МЛН