OVER-CURRENT RELAY SETTINGS CALCULATION FOR TRANSFORMER and Relay Coordination

  Рет қаралды 36,919

RELAY PROTECTION ELECTRICAL

RELAY PROTECTION ELECTRICAL

Күн бұрын

Please use the Coupon for my Udemy Course for free subscription
Code-
EB667EA4A5ADBF9D33BC
Link:-
www.udemy.com/....

Пікірлер: 40
@Deb0029
@Deb0029 14 күн бұрын
Very helpful ❤
@pietervdberg7055
@pietervdberg7055 Жыл бұрын
Thank you for a very clear easy to follow video on the topic. Made a lot of things clear for me. I posted a question under another comment about t=0.6s for LV and t=0.8s for HV. If you could answer we will highly appreciate it.
@relayprotectionelectrical
@relayprotectionelectrical Жыл бұрын
Thank you for your valuable comment. Tms of LV and HV can be so chosen that both the HV and LV over current relat trip simultaneously. Now a days if LV OC trip then there will be an inter trip will be sent to HV master trip relay from LV OC relay. Now for the time 0.8 S. 0.8 S is the maximum time that can be given to the transformer to trip as it should not exceed far end line in zone-3 time which is normally set as 0.8-1 S . So if Zone3 encroach lower voltage level far end FDR should not trip prior to transformer trip and i.e. why 0.8 S is the time for transformer trip in back up OC.
@pietervdberg7055
@pietervdberg7055 Жыл бұрын
Thank very much for the explanation.
@pietervdberg7055
@pietervdberg7055 Жыл бұрын
@@relayprotectionelectrical Another question please that I forgot to ask. The I(set) value being 110% of full load current and then calculate I(set)(s) = I(set)/CT ratio, is it the same as relay pickup current that is used in some calculations. Some I have seen are 120% and others as 125% of full load current. Is the formula to calculate t.m.s. for normal inverse curve? Thank you.
@surendrakverma555
@surendrakverma555 Жыл бұрын
Excellent lecture Sir. Thanks 🙏🙏🙏🙏🙏🙏🙏🙏🙏
@relayprotectionelectrical
@relayprotectionelectrical Жыл бұрын
Most welcome
@rakeshparmar8570
@rakeshparmar8570 2 жыл бұрын
Good explanation
@taimur649
@taimur649 2 жыл бұрын
Very informative
@Abi-og5jr
@Abi-og5jr 8 ай бұрын
How did you got the value t = 0.6 for lv and t=0.8 for hv
@syed_taha_ahmed
@syed_taha_ahmed Жыл бұрын
Do you have posted video on transmission line over current relay settings? How receiving and sending end relays are set? Please make a video on current discrimination and overcurrent relay settings for transmission lines.
@santhoshr53
@santhoshr53 2 жыл бұрын
Plz make video on Calculation for instantaneous over current
@salamkadhim6949
@salamkadhim6949 Жыл бұрын
شكرا جزيلا
@samadhanmore3760
@samadhanmore3760 Жыл бұрын
Determine the time of operation of the two relays
@MansourAlramlawi
@MansourAlramlawi 2 жыл бұрын
Many thanks for your explination, could u share with us a reference for these calculations?
@syed_taha_ahmed
@syed_taha_ahmed Жыл бұрын
What does numeric relay indications I> I>> and I>>> means?
@KarrarH-el4th
@KarrarH-el4th Жыл бұрын
PLZ Why this values of t=0.6 & 0.8 from what get it plz
@pietervdberg7055
@pietervdberg7055 Жыл бұрын
Yes please can you clarify the times of t=0.6s for LV and t=0.8s for HV. Is it a general norm for different voltages. Is specified in IEC etc Hope to hear from you.
@relayprotectionelectrical
@relayprotectionelectrical Жыл бұрын
@@pietervdberg7055 Thank you for your valuable comment. Tms of LV and HV can be so chosen that both the HV and LV over current relat trip simultaneously. Now a days if LV OC trip then there will be an inter trip will be sent to HV master trip relay from LV OC relay. Now for the time 0.8 S. 0.8 S is the maximum time that can be given to the transformer to trip as it should not exceed far end line in zone-3 time which is normally set as 0.8-1 S . So if Zone3 encroach lower voltage level far end FDR should not trip prior to transformer trip and i.e. why 0.8 S is the time for transformer trip in back up OC.
@AjeetKumar-iq7fp
@AjeetKumar-iq7fp 2 жыл бұрын
Thanks sir
@mustafakhalidjasim3160
@mustafakhalidjasim3160 Жыл бұрын
Why you have used z%equal to 12%,where you get it?, thanks
@relayprotectionelectrical
@relayprotectionelectrical Жыл бұрын
You can get %Z of Transformer in nameplate .
@sudampatra5608
@sudampatra5608 Жыл бұрын
Can we use relay rest ratio here
@dawodtawer1953
@dawodtawer1953 2 жыл бұрын
Hello everyone I hope someone answer my question I have six generators (1 MVA each)feeding 11 kv switchgear through transformer 0.4/11 kv i need to add two more generators (1 MVA each) with parallel transformer 0.4/11 kv to same switchgear. My question is do i need to change the protection settings?
@mageshgopi5644
@mageshgopi5644 Жыл бұрын
System prospective current value increased and system impedance has reduced . So a comprehensive short circuit calculation and protection setting study is required
@pietervdberg7055
@pietervdberg7055 Жыл бұрын
@@mageshgopi5644Yes agree with this reply. When operating transformers in parallel the total impedance of the transformer combination will reduce, depending on the number of transformers and their impedances. Similar to connecting resistors in parallel. This will cause the total system impedance to decrease resulting in an increase in the prospective short circuit current. So yes in depth calculations and analysis of the network is required. Consider introducing a busbar system with busbar incomers from generators and transformer feeders as well as bus couplers for different sections to avoid paralleling transformers but to provide flexibility of the network. Not sure what the network looks like. Also bear in mind that when the network is changed such that the system impedance is decreased and fault currents increase substantially you might reach a point where the fault current could exceed the max fault current rating of switchgear, cables, etc
@badshahibrahim8475
@badshahibrahim8475 2 жыл бұрын
Sir please make for Motor feeder 🙏🏻🙏🏻🙏🏻🙏🏻
@relayprotectionelectrical
@relayprotectionelectrical 2 жыл бұрын
Ok I will
@badshahibrahim8475
@badshahibrahim8475 2 жыл бұрын
@@relayprotectionelectrical yes sir I hope 👍🏻
@Deepak_Kumar1993_
@Deepak_Kumar1993_ Жыл бұрын
​@@relayprotectionelectricalw8ing for long time
@ganeshachally4881
@ganeshachally4881 2 жыл бұрын
Sir why you didn't take the power factor in calculating the full load current
@relayprotectionelectrical
@relayprotectionelectrical 2 жыл бұрын
Maximum fault current is considered in this case and i.e. why unity pf is considered for this purpose.
@badshahibrahim8475
@badshahibrahim8475 2 жыл бұрын
Thank for it 👍🏻👍🏻
@lokeshjuneja2039
@lokeshjuneja2039 11 ай бұрын
volume is very low in video.
@AjeetKumar-iq7fp
@AjeetKumar-iq7fp 2 жыл бұрын
Part 2
@great_India3344
@great_India3344 2 жыл бұрын
TMS formula is written wrongly
@relayprotectionelectrical
@relayprotectionelectrical 2 жыл бұрын
Yes it is. But TMS calculated is right. Thank you for watching video carefully...
@jitendragujarathi1282
@jitendragujarathi1282 2 жыл бұрын
Volume very slow sir
@relayprotectionelectrical
@relayprotectionelectrical 2 жыл бұрын
Kindly use headphone for better hearing.
@jitendrasoni4105
@jitendrasoni4105 Жыл бұрын
Aawaaz khatam hai kya😢😢😢😢
RELAY SETTINGS AND CO ORDINATION|PART 1_PHASE FAULT|ELECTRICAL TECHNOLOGY AND INDUSTRIAL PRACTICE
20:38
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 76 М.
Overcurrent Protection Basics | How to Set Overcurrent Elements in Protection Relays
16:02
Little brothers couldn't stay calm when they noticed a bin lorry #shorts
00:32
Fabiosa Best Lifehacks
Рет қаралды 18 МЛН
My Cheetos🍕PIZZA #cooking #shorts
00:43
BANKII
Рет қаралды 25 МЛН
Lehanga 🤣 #comedy #funny
00:31
Micky Makeover
Рет қаралды 28 МЛН
Protection Relay Setting Calculation for Transformer Feeder Relays
20:49
Overload Protection vs Short Circuit Protection? |Overcurrent Explained
5:01
ElectricalEngineeringPlanet
Рет қаралды 36 М.
These Illusions Fool Almost Everyone
24:55
Veritasium
Рет қаралды 2,2 МЛН
INFINITE RANGE ELECTRIC CAR - DIY Build
24:28
Drew Builds Stuff
Рет қаралды 731 М.
Can you solve these number puzzles?
8:03
MindYourDecisions
Рет қаралды 49 М.