Protection Relay Setting Calculation for Transformer Feeder Relays

  Рет қаралды 25,942

Julius Salutan

Julius Salutan

Күн бұрын

Performed relay setting calculation for the following relays:
- Phase Time Delay Overcurrent Relay (51)
- Ground Time Delay Overcurrent Relay (51G)
- Phase Instantaneous Overcurrent Relay (50)
- Ground Instantaneous Overcurrent Relay (50G)
- Phase Under-Voltage Relay (27)

Пікірлер: 28
@ASIFKHAN-ui7jp
@ASIFKHAN-ui7jp 7 ай бұрын
Excellent explanation. Thanks
@surendrakverma555
@surendrakverma555 Жыл бұрын
Excellent lecture. Thanks 🙏🙏🙏🙏
@karthikeyan3140
@karthikeyan3140 Жыл бұрын
Great explanation sir..
@ahmedelmasry7435
@ahmedelmasry7435 2 жыл бұрын
Thanks Engineer
@ImranKhan-nu6xw
@ImranKhan-nu6xw 2 жыл бұрын
Very nice appreciate you sir g
@AAEL2010
@AAEL2010 9 ай бұрын
Thank you ❤
@shihabahmedalkatrani3050
@shihabahmedalkatrani3050 Жыл бұрын
Thanks 🙏
@9999afshin
@9999afshin 5 ай бұрын
Nice
@lilmamaw1204
@lilmamaw1204 2 жыл бұрын
thank you po sir
@juliussalutan8006
@juliussalutan8006 2 жыл бұрын
Welcome sir
@TheSurgeArrester
@TheSurgeArrester Жыл бұрын
Care should be taken when following the steps mentioned here especially when it is across transformer. There are points which are important are not considered in the setting calculation.
@gerryboypanot7344
@gerryboypanot7344 2 жыл бұрын
Thanks sir.........
@juliussalutan8006
@juliussalutan8006 2 жыл бұрын
welcome sir
@gerryboypanot7344
@gerryboypanot7344 2 жыл бұрын
@@juliussalutan8006 Tacloban din ako sir....
@juliussalutan8006
@juliussalutan8006 2 жыл бұрын
@@gerryboypanot7344 LIT graduate ako sir we back 1997
@cracklyoyster6625
@cracklyoyster6625 2 жыл бұрын
Why was 35430A used instead of 1288A as 11KV fault current in the computation of 11KVside pickup current?
@emmanuelmanteaw7931
@emmanuelmanteaw7931 2 жыл бұрын
I have same question.. why the 35430 is used instead of the 1288
@rodsilver19
@rodsilver19 Жыл бұрын
Same question here
@sanjaykashikar940
@sanjaykashikar940 Жыл бұрын
It is to be taken 1288A. As you can't divide LV current by HT ct ratio. Needs correction.
@PhilsChannel
@PhilsChannel 2 жыл бұрын
I have seen your bus bracing rating, How do we select bus bracing? And when do we use 1sec against 3 secs?
@juliussalutan8006
@juliussalutan8006 2 жыл бұрын
When it is based on ANSI 37 standard, bus bracing will be based on momentary network. For HV & MV switchgears, the corresponding asymmetrical RMS and asymmetrical peak short circuit currents have to be considered. Whilst, for LV switchgears, it's symmetrical RMS and asymmetrical RMS are being considered. All these information have to be clearly specified in a dedicated table once we prepared a power system study report. In my previous experience, we normally indicate in the drawing the asymmetrical RMS rating of the bus (for MV/HV SWGR) only and symmetrical RMS rating of the bus (for LV SWGR). For HV/MV SWGRS, the standard values for assymetrical RMS raring are 25kA, 31.5kA & 40kA in 3 seconds. But my last project ( nuclear power plant project), we used 50kA 3 seconds (which is rarely used in other facilities). The assymetrical crest rating of the SWGR will be considered/verified by the manufacturer once they start production of the SWGRS. Meanwhile, for LV SWGRS, the standard values in the market for symmetrical RMS rating are 25kA, 31.5kA, 40kA, 50kA, 65kA in 1 second. 80kA or 100kA is seldom used. One of my projects, a GOSP ( gas oil separation plant) we used the latter ratings. The assymetrical RMS will also be considered based on the actual short circuit study (maximum) that has to be provided to the SWGR manufacturer as well.
@PhilsChannel
@PhilsChannel 2 жыл бұрын
@@juliussalutan8006 Thank you for your response. But how they choose the 3sec for MV/HV and 1 sec for LV applications? why only 1 sec and 3 sec? Why not 2sec, 4sec or 5 sec at most?
@juliussalutan8006
@juliussalutan8006 2 жыл бұрын
@@PhilsChannel as we know energy is directly proportional to the square of the current multiply by time. So the 3-second rated time has a higher short circuit withstand capability against rated 1 second. MV/HV has been rated in 3 seconds to facilitate the coordination time interval (CTI) in which upstream protection device time delay becomes longer as it requires to coordinate downstream protective devices. We need to consider also the relay operation time, lock out relay operation time, circuit breaking interrupting time, etc.. Thus, upstream HV/MV switchgears are being designated with a higher rated time i e. 3-sec but it could be 1 second as well. From your question why not use 2s, 4s or 5s? Im not sure how it was agreed by the industry practitioners or by any standard ( i havent seen yet). Its has been an industry practice to use 1 second or 3 seconds for switchgears and 2 seconds for transformers.
@PhilsChannel
@PhilsChannel 2 жыл бұрын
@@juliussalutan8006 Great response. Thank you for your sharing.
@bagusirawansaputra
@bagusirawansaputra Жыл бұрын
Why for 51P, you are using 1.5 pu ? why you are not using 1.1 or 1.2 since if exceed the 1 pu, I think it transformer will slowly damage ? and For 50P, what it 2,5 pu ? It is consider through fault current refer to IEEE 242 and or it has consider transformer inrush instead of 2nd harmonic block ?
@allenchesteralcantara2580
@allenchesteralcantara2580 11 ай бұрын
How to get po yung 4330A @ 0.4kV thank you
@Al-rk6gm
@Al-rk6gm Жыл бұрын
reference book pls
@abdalhameedstohy9207
@abdalhameedstohy9207 11 ай бұрын
Supply the equations
LOVE LETTER - POPPY PLAYTIME CHAPTER 3 | GH'S ANIMATION
00:15
Жайдарман | Туған күн 2024 | Алматы
2:22:55
Jaidarman OFFICIAL / JCI
Рет қаралды 1,8 МЛН
I CAN’T BELIEVE I LOST 😱
00:46
Topper Guild
Рет қаралды 115 МЛН
تجربة أغرب توصيلة شحن ضد القطع تماما
00:56
صدام العزي
Рет қаралды 50 МЛН
Differential protection
8:53
stephen brooks
Рет қаралды 131 М.
Protection Relay Setting Calculation for MV Motor Feeder Relays
30:00
Current Transformer vs Voltage Transformer : What’s the Difference ? TheElectricalGuy
12:32
Transformer Inrush & Damage Curve in ETAP
12:42
Smart Educare
Рет қаралды 2 М.
Transformer Overcurrent Protection - What to Consider When Setting Protection Relays
25:30
Overcurrent, Overload, Short Circuit, and Ground Fault
6:54
Dave Gordon
Рет қаралды 821 М.
IDMT Relay setting calculation|TIME GRADATION|RELAY CO-ORDINATION
14:05
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 38 М.
LOVE LETTER - POPPY PLAYTIME CHAPTER 3 | GH'S ANIMATION
00:15