I am glad it could be helpful. Thanks for your watching!
@PattysLab3 жыл бұрын
Really clear thanks for the video series!
@electricalautomation3 жыл бұрын
Glad it was helpful!Welcome!
@lizartzaunai5098 Жыл бұрын
how do you know what EL3xx series to choose for analog inputs(4a20mA) thanks
@MIhsanRahmatullah Жыл бұрын
The maximum resolution only 360p?
@electricalautomation Жыл бұрын
I just tested and it can do 1080p. So please check your internet network speed.
@ngochan37064 жыл бұрын
Thank you for your great video
@electricalautomation4 жыл бұрын
Welcome to my channel, thanks for watching!
@Alex-pz7kr3 жыл бұрын
Hi, what about errors( wire break, overflow)? In Siemens Plcs we have 0 - 27648 fo scale and -32768 or 32767 for errors
@electricalautomation3 жыл бұрын
As showing 13:40, if you use 3174, then 4 - 20mA is 0x7736, overflow will be 7FFF, 0mA is E233, wire break. Also please view 15:29.
@Alex-pz7kr3 жыл бұрын
@@electricalautomation So if I use EL315x ( 4 - 20mA, 0- 32767), wire break will be =32767. Am i right?
@electricalautomation3 жыл бұрын
@@Alex-pz7kr ( 4 - 20mA, 0- 32767) for EL315x is correct. But I am not sure this module will do =32767. Most likely it can not diagnose the wire break and overflow. I would recommend you use EL317X
@Alex-pz7kr3 жыл бұрын
@@electricalautomation Thanks. I have also a question about scaling. There's a typical scaling formula result= ( Yi -Ymin/Ymax-Ymin) * (Xmax - Xmin)+Xmin; You use result = ( Xmax- Xmax)/ Ymax * Yi; Why you not add Xmin in your version? Thanks in advance
@electricalautomation3 жыл бұрын
@@Alex-pz7kr Hi, because Ymin = 0.0v, and Xmin = 0 in this case. Pls see 33:40, the green comments
@rubraver3 жыл бұрын
Hello!! Great channel!!! got some question regarding this analog configuration. When I'm using a 0-10v potenciometer on the input and wanted to connect on the output a 12v fan, wich variable should be the one giving me the correct data to the output? and how to link the output with this value? Thanks in advance.
@rubraver3 жыл бұрын
Should be enough with scaling or unscale must be done also? sorry, I'm trying different plc from siemens so I'm a bit lost.
@electricalautomation3 жыл бұрын
Hi Bro. If you are using Beckhoff, for the Unscale, that is just the next video #4. named "Analog Output 0-20mA/4-20mA EL4014 'UNSCALE' programming" kzbin.info/www/bejne/qIOcoIGXpK6LsNk
@electricalautomation3 жыл бұрын
If you are using Siemens, you also find the right channel, please view the video "Analog Input Scale Library and Norm_X/Scale_X in TIA Portal" kzbin.info/www/bejne/g5SQe417qqyrfNk, and "Analog Output Unscale" kzbin.info/www/bejne/Y6vTk3irjbarq9E