Pressure Testing Gas Lines For Leaks! Natural Gas & LP Propane!

  Рет қаралды 78,166

AC Service Tech LLC

AC Service Tech LLC

Күн бұрын

Пікірлер: 37
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
The E-Book and Paperback at our Website: www.acservicetech.com/the-book The Paperback at Amazon: www.amazon.com/shop/acservicetech Support the Channel- www.patreon.com/acservicetech Tool List- www.amazon.com/shop/acservicetech For those that are looking for the tools used in the videos: (Linked Below) IFGC 2018- amzn.to/2nAbe4d IMC 2018- amzn.to/2VujJdH 8oz bubble leak detector with dabber- amzn.to/2omGfJo Blue-Cal bubble Leak detector bottle- amzn.to/2M3KdiP Big Blu bubble leak detector bottle- amzn.to/33nnFzk Related Videos: CSST, Gastite, Tracpipe WardFlex- kzbin.info/www/bejne/eoOmlZxpl7t5jrc Sizing Gas Lines- kzbin.info/www/bejne/g4qWYnuigcmhaq8 Leak Testing Gas Lines- kzbin.info/www/bejne/fHuvkniqlK2lhLc Electrical Diagnosis Tools: UEI DL389 Multimeter amzn.to/2xAdaJf UEI DL479 Multimeter with temp sensor amzn.to/2jtsUbJ Magnet Jumpers- amzn.to/2PyKPQZ Alligator Jumpers- amzn.to/2PxqJXn Irwin Wire Stripper/Cutter/Crimper amzn.to/2dGTj2V Vacuum Tools: JB 6 CFM Vacuum Pump - amzn.to/2nqbvo8 CPS 4 CFM Vacuum Pump - amzn.to/2DxgPwY Appion Valve Core Removal Tool - amzn.to/2uYr8WL Appion Blue 3/8" to 1/4" Vacuum Hose - amzn.to/2uYlVyc Appion Red 3/8" to 1/4" Vacuum Hose - amzn.to/2uYg6Ro Yellow Jacket 1/4" by 1/4" 3’ hose - amzn.to/2umtcod Appion 1/4" by 1/4" and 3/8” hose - amzn.to/2Zyxzx9 Uniweld 1/4" by 1/4" 2’ hose - amzn.to/2GFov1Y CPS Vacuum Micron Gauge - amzn.to/2v1nM3O Supco Vacuum Micron Gauge - amzn.to/2v1JRiA JB Vacuum Pump Oil - amzn.to/2mGrlXy Checking the Charge: Yellow Jacket Refrigerant Gauge Set amzn.to/2aenwTq Refrigerant hoses with valves amzn.to/2aBumVI Yellow Jacket Gauge set & hoses amzn.to/2vLVkV9 Yellow Jacket 4 Port Manifold w Hoses amzn.to/2BkuGIq Digital Refrigerant Scale amzn.to/2b9oXYl Ratcheting Service Wrench amzn.to/2dGV4Nh FieldpieceSMAN360 Digital Manifold Set amzn.to/2BdoaD4 FieldpieceSMAN460 Digital Manifold Set amzn.to/2nB4Fe6 Compact Ball Valve for Refrigerant Hose amzn.to/2KUisW8 QuickDisconnect 90 for refrigerant hose amzn.to/2MMtVcg RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn Fieldpiece ST4 Dual Temp Meter amzn.to/2wc1ME3 Fieldpiece Bead K Type Temp Sensor amzn.to/2DBwKfs Fieldpiece Wet Bulb Temp Sensor amzn.to/2RRI7Tw Fieldpiece TC24 Temp Clamp amzn.to/2qHLyjZ Flaring Tools: Yellow Jacket Flaring Tool - amzn.to/2OBxGlM Spin Flaring Bits 1/4", 3/8", 1/2", 5/8", 3/4"- amzn.to/31BCs8Z Yellow Jacket Flaring Tool with Set Depth - amzn.to/2QIKsQH Yellow Jacket Torque Wrench - amzn.to/2NRR68Q Uniweld Swage and Flare Kit- amzn.to/2T55jyn Nylog - amzn.to/2MLJcch Ridgid Tubing Cutter - amzn.to/2DnjjR1 Wolverine Tube Reamer - amzn.to/2QGLyMV Swaging Tools: Manual Copper Tube Swage/Expander- amzn.to/2WRPa1M Spin Swaging Bits 1/4" to 7/8" for the Drill- amzn.to/2YQwwqS Uniweld Hydraulic Swaging Tool- amzn.to/2MlrI8m Uniweld Swage and Flare Kit- amzn.to/2T55jyn Uniweld Hammer Swage kit- amzn.to/2CzWMMU Uniweld 3/4" Hammer Swage- amzn.to/2CzXsSs Uniweld 7/8" Hammer Swage- amzn.to/2Mja5WE Uniweld Multi-Size Hammer Swage- amzn.to/2T3Cx1b Brazing Tools: Air Acetylene Torch setup - amzn.to/2aQalsb 15% Silver Brazing Rods - amzn.to/2gVLyLc Uniweld Cap-N-Hook and #2 Tip Oxy Acetylene Torch Setup - amzn.to/2STp3Fe Ameriflame Oxy Acetylene Torch Setup #1 &#2 Tip - amzn.to/2SRm3JF #2 Tip for Oxy Acetylene Torch - amzn.to/2SPDaeD Cap-N-Hook Tip for Oxy Acetylene Setup - amzn.to/2MbhpUk 40cu B Tank to 10cu MC Tank Acetylene Tank Fitting - amzn.to/2GxZZPi Nitrogen Regulator - amzn.to/2bXdR5f Uniweld NitroVue Flow Regulator - amzn.to/2GnsaAo Uniweld Nitrogen Flow Meter - amzn.to/2brvoBg Bernzomatic Trigger Start Lighter Propane/Mapp Gas - amzn.to/2vit0cv Uniweld Soft Flame Sweating Torch Setup for Acetylene - amzn.to/2DyzRD8 Flint Spark Ignitor - amzn.to/2L3P2u9 Stay Brite #8 Silver Bearing Solder and Flux - amzn.to/2XIDJsY Aluminum Braze Rods - amzn.to/2IGNMu Nitrogen: Uniweld NitroVue Flow Regulator- amzn.to/2GnsaAo Uniweld Nitrogen Flow Meter amzn.to/2brvoBg Nitrogen Regulator amzn.to/2bXdR5f Service Valve & Port Access: RectorSeal Bubble Gas Leak Detector - amzn.to/2ckWACn 25 Valve Cores - amzn.to/2L37UJU 25 ¼” Brass Port Caps with rubber O-rings - amzn.to/2GIOdD2 Brass Valve Core Tool which holds 3 valve cores - amzn.to/2GFEbm2 Valve Core Torque Wrench - amzn.to/2GHiLoD Locking Cap Universal Lock/Unlock Tool - amzn.to/2GGAoVp Locking caps - amzn.to/2GFXZ8A Ratcheting Service Wrench amzn.to/2dGV4Nh Yellow Jacket Sealright 90 Coupler- amzn.to/2LsU1V7 Yellow Jacket 1pk Compact Ball Valve- amzn.to/2uXdF18 Yellow Jacket 3pk Compact Ball Valve- amzn.to/2AiKfQe Thumb Screw Valve Core Depressor with Backseat- amzn.to/2mR0sCL Leak Detection: Accutrak VPE Ultrasonic Leak Detector amzn.to/2nFYKVe Accutrak VPE-GN Ultrasonic Leak Detector amzn.to/2Zy4IZP RectorSeal Bubble Gas Leak Detector - amzn.to/2ckWACn Other tool links can be found in the video description section. Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech
@mike-yp1uk
@mike-yp1uk Жыл бұрын
I don't work on this stuff but I actually enjoy watching you teach because of the in depth knowledge. Great video
@propanetechllc5675
@propanetechllc5675 5 жыл бұрын
Solid video, sir. I trust you to run gas in my house. Very impressed that you know not all gas valves are rated for high pressure.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thank you Propane Tech LLC!
@boby115
@boby115 4 жыл бұрын
Good video but I'd like to add some helpfully suggestions and insight that may help some of your viewers .My experience comes from 35 years as a first responder/ service fitter for the natural gas utility in St Louis, Mo. #1 you may want to add an appropriate pressure rated cock ( shut off) between your gauge and fuel runs you are pressure testing ( this way you can isolate your gauge to ensure it is leak free and use it for isolating; you can shut it off during the pressure test and turn it right back on to verify no gauge drop.).#2 best method for use of approved liquid leak detector is a spray bottle or a round parts cleaning brush. Use of dobber just can't get to every area efficiently. #3 active leaks should be located with a tick rate electronic leak detector and pinpointed with approved liquid leak detector ( never an open flame, let me repeat never).#4 after all the appliances are connected to the fuel runs one more pressure test should be completed ( this is the low pressure test completed with a manometer ,7 to 13 inches water column). This will ensure you have no leaks on the appliance connections & no appliance gas controls or valves are passing gas. Hope this helps and stay safe out there.
@scottmichael7178
@scottmichael7178 Ай бұрын
can you pressure test with a 2psi to 1/2 psi regulator or do those have to be installed after ? I have a few appliances that come off each regulator and would be inline in the attic with the gas lines but cant find if the regulators are ok to be pressure tested
@dcagle91
@dcagle91 5 ай бұрын
How much does pressure testing the gas line cost?
@phillipjoy8191
@phillipjoy8191 5 жыл бұрын
Where I live the gas company makes us test at 20 psi here in Easley s.c.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
If that is for low pressure, it sounds like it is just the inspector there because that is much higher than IFGC states, thanks!
@ChrisMasto
@ChrisMasto 3 жыл бұрын
This is very interesting. I just had a line added to my existing system for a generator and the installer told me that the pressure test failed because of a leak somewhere in my existing pipes. Specifically they said they tested at 4.5 psi and it dropped to 4. They're charging me a lot of money to come tomorrow and find the leak. If I understand correctly, they shouldn't have pressure tested the whole thing, just the new line.
@nsudatta-roy8154
@nsudatta-roy8154 3 жыл бұрын
How did you make out?
@38snubnose
@38snubnose 5 жыл бұрын
What Size Air Compressor Do I Need Please?
@acrepairnearme
@acrepairnearme 5 жыл бұрын
Great video! Thank you!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Tapch MC!
@MrChipBryant
@MrChipBryant 5 жыл бұрын
Good video.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Chip!
@JoseGuerrero-sj5ie
@JoseGuerrero-sj5ie 5 жыл бұрын
Good video it’s a great information
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Jose!
@bshoff3
@bshoff3 4 жыл бұрын
If you think you have a leak, can you test with the blue spray stuff with gas in the line?
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
yes but only with non-corrosive bubble leak detector, thanks!
@mathman0101
@mathman0101 Жыл бұрын
@@acservicetechchannel even better than the dobber a spray end with the non corrosive bubble leak detector fluid would help even more as it more effectively gets into tight and small spaces. I would also pre-test and post-test with an active electronic gas leak detector after the bubble leak test. Call it a belt and braces approach but with something as dangerous as gas it really is something I would recommend.
@randysavage1997
@randysavage1997 5 жыл бұрын
Hey Craig I got a question. Is it possible to start an apprenticeship in one state, then halfway through you move to another state and finish the apprenticeship there? Will the credentials carry over to the other state? I live in NJ and I want to start my apprenticeship now. But I know I am moving out of state in 1 to 2 years, and I dont want to have to start it all over again. Thanks.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
You should contact an apprenticeship director at the state where you are moving to in order to see if they are reciprocal. It depends on the state, thanks!
@حسين-ج9ط7ي
@حسين-ج9ط7ي 5 жыл бұрын
شكرا اخي عمل رائع
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
أنا سعيد جدا للمساعدة! I am very glad to help!
@Rinebo
@Rinebo 4 жыл бұрын
Good stuff!
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks a lot Ryan!
@jimbola77
@jimbola77 5 жыл бұрын
thank you, partner, for sharing!!!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Jimbola77!
@fathom73
@fathom73 5 жыл бұрын
Ball valve closed only rated at half a psi? Where are you getting this info? Nibco gas valves are max rated at 125 psi. Never had a problem testing a line using the ball valve in the closed position.
@fathom73
@fathom73 5 жыл бұрын
@Wizdomtrek you're definitely a nutty snowflake or doing a great impersonation. Did you miss a pill today crackpot?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
The non full port no WOG valves are typically stamped with the pressure rating with the valve closed. It certainly can handle more than that but thats the rating and IFGC states to that gas valve should not be stopping the gas during a pressure test. The Nibco WOG valves have high ratings since they are for water oil or gas, thanks!
@fathom73
@fathom73 5 жыл бұрын
@@acservicetechchannel you show the pressure gauge where the gas meter is going to end up so it's safe to assume no gas is in the line for testing right? FGC states not to pressure test with a valve separating the actual gas (boom boom)and another test medium (air or nitrogen). It also says a valve is fine to use if it can safely withstand the test pressure. Section 406 testing fgc2015. Now lets say the valve is approved for 1/2 psig for gas like you're saying, are we not allowed to pressure test it with Air at a higher rate if the valve shows a max pressure of 600 psi? My questions are directed at learning and understanding only, snowflake peanut gallery be warned. 🤣
@phillipjoy8191
@phillipjoy8191 5 жыл бұрын
The inspectors were I live there’s no consistency.It is very frustrating
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thats is unfortunate if they won't listen to you when showing them codes!
@rickybrown6585
@rickybrown6585 3 жыл бұрын
The kind of guys that test the gas leaks with a lighter are the kind that try to fight when you teach them something...KZbin is the only place where professionals are...out here...it's a mess
@boardwalkbw7130
@boardwalkbw7130 2 жыл бұрын
The dang gas company turned off our gas so how do we find leak now??
2 Hose Vacuum Pump Procedure VS 1 Hose Vacuum Pump Setup for HVAC!
19:24
AC Service Tech LLC
Рет қаралды 176 М.
How to Find and Fix a Gas Leak in Your Home!
10:11
Stud Pack
Рет қаралды 121 М.
Who is More Stupid? #tiktok #sigmagirl #funny
0:27
CRAZY GREAPA
Рет қаралды 10 МЛН
HVAC Silver Soldering vs Brazing vs Brazing While Flowing Nitrogen!
18:42
AC Service Tech LLC
Рет қаралды 123 М.
Steps to Vacuum and Charge Refrigerant on a Mini Split Unit!
15:08
AC Service Tech LLC
Рет қаралды 1,3 МЛН
How to Set a Low-Pressure Control for Refrigeration Systems
4:24
The Fridge Mechanic
Рет қаралды 94
How an Air Handler & Heat Pump Work & are Controlled by 24v Thermostat Wires!
19:29
Gas Company Locked Out The Meter - Said There Was Gas Leak
4:53
HVAC Know It All
Рет қаралды 21 М.
Liquid Line Restriction on AC Unit Explained! Found Bad TXV!
13:35
AC Service Tech LLC
Рет қаралды 404 М.
Pressure testing my gas line how to.
3:59
Grant Keys Properties
Рет қаралды 21 М.