I learned a lot with your video, Thank you so much!!
@hdhosseini3 жыл бұрын
Thanks , please stay connected.
@DDMMAGALHAES3 жыл бұрын
Is it possible use a s7 1200 to check it ?
@SpottedEagleOwlsАй бұрын
how can i prevent the cpu from stopping when ob86 is called
@hdhosseini16 күн бұрын
Please watch this video for answers: kzbin.info/www/bejne/n3_FYqajrMxojrM
@prashantpitroda23852 жыл бұрын
hello sir, this is the case of profibus, but if profinet slaves are there then where to write slave address or what slave address should be write?
@osmarlima20123 жыл бұрын
Hi Hamid!! Good job!! Thank you for sharing with us, could you explain what is %LB11?
@hdhosseini3 жыл бұрын
Thanks for your message , LB11 is the local memory related to OB86 that keeps the slave address.
@sinanartemis6176Ай бұрын
dear sir, do you have an online course i want to take. especially on simatic manager stl
@hdhosseiniАй бұрын
Thanks for your message, Please visit: hdhosseini.com If you are interested, please contact info@hdhosseini.com for creation of an account.
@vorapobautomation97604 жыл бұрын
How to show where is slave fault or which module fault in HMI ?
@hdhosseini4 жыл бұрын
when you have the slave number (e.g 3) , it is up to your creativity to select an alarm or a nice automation system structure then marking the failed slave.
@kgauravb4 жыл бұрын
Hi, What is B#16#39 and 38 command..??
@hdhosseini4 жыл бұрын
Thanks for your message: B#16#39 when the error occurs B#16#38 when the error clears
@derina.maleek94084 жыл бұрын
Please more video on obs we want that subject thank you
@hdhosseini4 жыл бұрын
Thanks for your message , please stay connected for new related OB-related topics
@juanluisgtz82064 жыл бұрын
Nice vídeo! Could you explain how to call when a slot (digital card, analog) is going to fail? With profibus please
@hdhosseini4 жыл бұрын
Thanks for your message, First you need to have the module with diagnostic capabilities.Then , You can use OB82 for checking internal failures and OB83 for removing /inserting modules. Check the online help of STEP 7 or TIA Portal for more information.
@kgauravb3 жыл бұрын
Hello very informative and thank you for sharing could you please tell how to store the last error state if error occurred only for few seconds and restore itself. How to know which station had a problem if it comes only for a second or two in a month or a week? I'm having an issue of plc going into stop mode..!! How to stop plc for going into stop mode my PLC model is s7-300