Good day sir, I need your expertise in solving my problem. Im using CP 1542-5 with 1500 cpu 6ES7 511-1CK01-0AB0 and want to connect with Emerson DCS system SE4022. In this situation, I dont need emerson gsd inside my TIA since it was confirmed by Emerson people. How to configure my hardware since I cannot assigned my master?
@iqbalmehedi34234 жыл бұрын
very nice
@hdhosseini4 жыл бұрын
Thanks , stay connected for new topics
@onurs160810 ай бұрын
Dear Hamid, thank you for explanation. Do you think that i can use same configuration to communicate with 410-5H CPU as master. But in my project there is CPU 313-2DP and I try to communicate over CP 342-5(as slave)
@hdhosseini9 ай бұрын
update: kzbin.info/www/bejne/jZm3cq1sgN6mrc0
@haristarique19514 жыл бұрын
Sir there two type of slave station one is packed and other is unpacked please tell me packed station thankyou
@hdhosseini4 жыл бұрын
Thanks for your message. DP Slaves are 3 types: 1- Compact slaves , the IO are fixed and you can not change. 2-Modular Slave , you can select the IO config. 3-Intelligent Slave like CPUs