Proper condensate drain piping for a condensing tankless heater.

  Рет қаралды 2,230

That Tankless Guy

That Tankless Guy

4 ай бұрын

This is probably one of the most important parts of an installation of a condensing tankless heater. Without proper condensate piping the condensate will back up into the lower heat exchanger and leak out of the seam between the lower and upper exchanger.
The example in this video needs to be followed to the letter. One of the first thing a tankless phone Teck will ask to see is the condensate piping and if it's not done correct, he may not continue with helping you.
The piping for a condensate A plastic female adaptor must be used because a transition adaptor will rot out. drain should only be run in CPVC, ABS or PVC piping and a vent tee needs to be installed rite at the unit under the female adaptor.
You should put the condensate neutralizer after the units near piping and you should have a bypass installed on the neutralizer incase the unit clogs up.
If you have any questions or are interested in my training, please e mail me at
economyplmbg@aol.com
Please follow me on,
Instagram, michaellatronico
TikTok, that tankless guy
I hope you enjoy the video,
Mike

Пікірлер: 13
@gwynhall5951
@gwynhall5951 2 күн бұрын
This technique solved my condensate drain problem. Thanks for this video. 👍🏽
@garysnider5885
@garysnider5885 23 күн бұрын
Thanks Mr Tankless Guy. My 6 year old Rinnai tankless installed with brass female transition fitting to 1/2 inch pex line corroded and fell off. With guidance of your video I installed new line including vent myself saving a lot of money. Great to have access to experienced pros on you tube.
@steveloux4709
@steveloux4709 4 ай бұрын
I followed this technique when you first introduced it for the Rinnai RU/RUR. So glad I did. Home Depot doesn't stock CPVC in the store, but you can order online with free shipping and it arrives in 1-2 days right to your home.
@brianfielden9320
@brianfielden9320 4 ай бұрын
Hi Tankless Guy, Would like to give you a big thanks for all your videos. They helped me install a Rinnai RSC 199in, Mucho appreciation for your recommendation to use spring loaded check valves on both the cold and the dedicated return line.
@alanbosma2159
@alanbosma2159 4 ай бұрын
Thanks, hadn't seen your yt lately. Very timely as installing a Noritz unit as yt came out. Learned a valuable condensate tip!Lunch break over
@timrowlett5451
@timrowlett5451 4 ай бұрын
Very true. Yes, thank you!
@rossspindler2728
@rossspindler2728 5 күн бұрын
Do you also need to put a condensate collector on the air intake? I'm installing a Rheem condensing tankless heater and there's a picture that shows the regular condensate drain AND the condensate collector on the air intake
@DukeJJZ
@DukeJJZ 3 ай бұрын
What about piping the condensate drain outside if you live in NYC? Any concern with the water freezing at the end of the pvc that is outside, I only have a a few inches (with an elbow) outside that is already draining my house furnace humidifier.
@MrParadigmRG
@MrParadigmRG 4 ай бұрын
Mike great videos. I have a question about my Rinnai. The built in circulation pump has a noisy vibration when circulating water in dedicated loop. any idea if this needs a new pump or is there a repIr or easy fix? Thanks again for your great posts.
@scottb3188
@scottb3188 3 ай бұрын
Mike, question about the specified CPVC female adapter (FPT/SS). I assume that the "transition adapter" your describing is a brass fitting (such as the one my plumbers put on mine). I'm replumbing the condensate drain and replacing the filter, removing the brass transition fitting, elbows, filter adapters, and pex, and installing straight PVC. What's immediately available from the local big box store (and what I have on order), is a 1/2" PVC FPT/SS adapter, without the rubber seal. I had intended to simply use pipe dope or tape to secure it to the Rinnai tank (RUR98iP) 1/2 drain stub (which I thought was MPT, or is it MIP?). If it's MIP, that might explain the difference, but the brass fitting the plumber used, was sealed with pipe dope. In any case, this is a non-pressurized gravity drain, so I expect the PVC adapter I purchased will work with teflon or dope. Thanks. (Update: Found one for $0.99 at a local Ace Hardware; It's 2 to 3 times that at the box store, special order/shipped. FYI: Apollo Schedule 40 1/2 in. Slip in to X 1/2 in. D FNPT CPVC Female Adapter 1 pk)
@Chefmarcel30
@Chefmarcel30 4 ай бұрын
As a home owner with a bad install and code 25 “condensate trap full” I don’t have the T shape, the installer just put a straight PVC pipe leading through the wall to outside. Could I cut the pipe myself and install the T at the top with those PVC cutters. Should I turn my tankless heater off to do it or is it ok to leave on?
@AJXOXO-vz1pn
@AJXOXO-vz1pn Ай бұрын
Hey. What happened? I thought it was Mike the Rinnai guy. Now, it’s Mike the Navian guy? What happened to Rinnai? I noticed all the Mike videos are Navian now.
@lurvenh1
@lurvenh1 4 ай бұрын
You should really talk more about a neutralizer, they go hand and hand. There are still a lot of techs that don't put them in, and a home owner watching this would miss the part you said about a neutralizer, or not know what you are talking about.
Proper condensate drain piping on a Navien tankless.
18:31
That Tankless Guy
Рет қаралды 7 М.
Proper condensate drain piping for a Rinnai condensing unit.
26:31
That Tankless Guy
Рет қаралды 51 М.
Задержи дыхание дольше всех!
00:42
Аришнев
Рет қаралды 3,6 МЛН
БАБУШКИН КОМПОТ В СОЛО
00:23
⚡️КАН АНДРЕЙ⚡️
Рет қаралды 17 МЛН
50 YouTubers Fight For $1,000,000
41:27
MrBeast
Рет қаралды 208 МЛН
Самый Молодой Актёр Без Оскара 😂
00:13
Глеб Рандалайнен
Рет қаралды 12 МЛН
Power Vent Water Heater Replacement
40:50
On the Mark with Mark
Рет қаралды 8 М.
A BEGINNERS GUIDE TO PRESS-FIT | My first go with my Novopress Press Tool
21:29
How to install a Rinnai tankless heater.
23:42
That Tankless Guy
Рет қаралды 282 М.
How to drain condensate on a Rinnai tankless heater
24:11
That Tankless Guy
Рет қаралды 25 М.
What venting to use for a Rinnai condensing tankless
15:06
That Tankless Guy
Рет қаралды 44 М.
Remove Air from your Boiler and Heating System | How To
16:25
Fix It With Zim
Рет қаралды 866 М.
Remove and Reinstall Pentair Big Blue Filter
7:37
Learn Plumbing
Рет қаралды 826
4 MISTAKES Everyone Makes When Using COMPRESSION FITTINGS
10:49
plumberparts
Рет қаралды 694 М.
3 Things They Don’t Tell You About Tankless
5:56
Matt Risinger
Рет қаралды 2,6 МЛН
王子居然在家这样 #艾莎
0:38
落魄的王子
Рет қаралды 5 МЛН
САМОЕ СЛОЖНОЕ СОРЕВНОВАНИЕ
0:41
MakkClips
Рет қаралды 2,3 МЛН
A woman comes a plan to teach her indifferent husband a lesson #shorts
0:44
Fabiosa Best Lifehacks
Рет қаралды 3,5 МЛН
A teacher captured the cutest moment at the nursery #shorts
0:33
Fabiosa Stories
Рет қаралды 49 МЛН
Forming of goal foam || A2Z SKLLS
1:00
A2Z SKILLS
Рет қаралды 24 МЛН
😳 Это ПРЕВРАЩАЕТ всё в ПИЦЦУ !
0:28
Настя, это где?
Рет қаралды 4,3 МЛН