Wow. Nice tutorial sir. Thank you for the knowledge that you share ❤️
@saimkhanafridi Жыл бұрын
Thanks for the very valuable video . I came here after my compressor got heated and burned out. This safety device was untouched ,dnt known how this device ddnt worked.
@whatwoulddennisdo7243 Жыл бұрын
Your comment on the saftety device being untouched is the exact reason I did the video. Indirect safety controls, which do not form part of the main power bus in can get ignored. Hopefully, everyone can appreciate the quality design of the protection symmetry within the stator that is offered.
@hvacknowledgechannel16214 жыл бұрын
Nicely defined by practical big thumbs up
@HolidayroadOz5 жыл бұрын
Great video mate, very clear and simple explanation.
@user-qf2bw4eh9v11 ай бұрын
Thanks for explaining sir 🙏
@sohilpatel375015 күн бұрын
Sir hamari company me ye compressor me protection relay he jisme comman se no me power nahi aata he to kya problem hoga, ek bar relay bhi change Kiya he
@kamranpenahov4027 Жыл бұрын
hi, compressor se e1 gives an alarm in my system, could you help me?
@oscarmendez1372 Жыл бұрын
Thanks for your video. I"m in la PAz B C S Mex . And I been working in a 27 hp bitzer compresor, I repair the compresor but I cant reset the int69. I replace the int69 and still show me a fail. You think is yhe resistence that is failing ?
@shajidkm98885 жыл бұрын
It's very clear thank you
@fridgydownunder67346 жыл бұрын
Nice video ken👍
@balbahadur182711 ай бұрын
Hi friend i need semi hermitic compressor full wiring diagram plz make other one video
@EpifanioBedro-ep9mm Жыл бұрын
Hi.. may I know if the connection or the diagram of SE-E1 and SE-B1 are the same?
@wllayacom7 жыл бұрын
Hi. I have problem with my 8FC-70.2Y comp. Oil pump is changed 1,5year ago. When it was changing, they found small piece of metal in case. Now, compressor have to be restarted (oil pressure protection) several times (at starting).
@whatwoulddennisdo72437 жыл бұрын
Its not good to have the oil pressure switch tripping out constantly. If this is a loss of pump dynamic oil pressure causing it to fail then it would need to be checked over to see why. The dynamic pressure also needs to be verified that it meets the manufacturer requirements. Many oil failure switches are non adjustable now as manufacturers like to make sure their equipment is protected within their specifications. If oil level is not the issue , suggest the pump and/or control be tested further.
@wllayacom7 жыл бұрын
Dennis Kenworthy thank you. Oil level is ok. Probably it is something wrong with pump.
@esmeraldinofranca90869 ай бұрын
Hello, greetings! We replaced the compressor module and when it starts, it shows a pulse at start-up, turns on, turns off and then turns on again. We tested it outside the compressor and it has the same behavior, it could be a factory defect in the module?
@whatwoulddennisdo72439 ай бұрын
Hi, thanks for your comment. I suggest you take that up with the manufacturer with the behaviour of the module. Would be a good idea to check the total resistance of the internal sensor loop to ensure its not close to the trigger resistance.
@wladimirrincon26633 жыл бұрын
Que posibilidad esta instalación pero en español..
@jubara1956 жыл бұрын
Where is the wire it supposed exist from relay to control compressor contactor
@whatwoulddennisdo72436 жыл бұрын
On this type between points 11 & 14 on the protection module
@jollyscaria1922 Жыл бұрын
Potshion relay semey tupe comrssar using potshion rely power hev euqpend winding portacting
@muhammadpikri84542 жыл бұрын
Very important video for me Dennis.. Thank you. May I have your contact? I have big problem about bitzer comp, coil engine tripped even comp just started.
@rbrtsncmpsn20346 жыл бұрын
whwt compressor bitzer semi hermetic capacity 8 tns 220 volt 3 phase with model then how much
@wladimirrincon26633 жыл бұрын
Esta concepción concepción pero en español. .el video
@shuaib8908 Жыл бұрын
IV been told that it's no big deal if you bypass them cause they are fitted with a overload on the contactor
@saimkhanafridi Жыл бұрын
Don't know these compressors come with supply contactors or not ,but mine does not have one. I had to install the contactor separately. I think not many contactors have thermal overload relays with them. Thermal overload relays need input from temperature sensors anyway. It's not a good idea to bypass this safety device ,in the first place.