Quick Clip: Defrost Cycle and how to Test on a Goodman Heatpump. EP 58

  Рет қаралды 16,649

Nighthawk HVAC

Nighthawk HVAC

Күн бұрын

Quick Clip. How the defrost cycle works, how to test the defrost cycle on a Goodman Heat Pump.
Follow me on Facebook and Instagram
nighthawkhvac
nighthawk_hvac
Intro and Outro Music
"Alive" by CHOIX
#nighthawkhvac #hvac, #hvaclife, #airconditioning #maintenance, #heating, #cooling #refrigerator, #refrigeration #refrigerationcycle #airflow #refrigerant #techlife #installation, #hvachacks, #tools, #furnace, #tech, #electric, #residential, #commercial, #heat, #comfort, #ac, #hvacservice, #hvactools, #repair#toolreviews #fieldpiece #aircon #packageunit #howto #VAV #exhaustfan #Ignitor #trane #TXV #expansionvalve #defrostcycle #goodman #testdefrost

Пікірлер: 58
@Lopez.4602
@Lopez.4602 8 ай бұрын
So how would i be able to bypass my goodman unit to not go on defrost anymore. I live in phx arizona
@Rayfanz1
@Rayfanz1 3 жыл бұрын
Heat strips are not allowed in CA? Whoa. I live in central Texas, right in the middle of the ice apocalypse a few months ago. My heat pump condenser fan blade froze up with ice at one point. Without the heat strips I would have been doa. Defrost cycle ran normally, but it was so cold it couldn’t melt the ice fast enough. Even in 20-30-ish degrees, like a normal Texas cold snap, it still needs to defrost about once an hour. No heat strips seems insane for freak weather events. Also during a normal cold day in December my capacitor went out, compressor would not start. Heat strips saved the day until my new cap arrived a few days later. No heat strips as emergency heat on a heat pump seems flippin criminal.
@NighthawkHVAC
@NighthawkHVAC 3 жыл бұрын
They are not energy efficient. That’s why that outlawed them. Plus it doesn’t get that cold in SoCal. Coldest it ever got in SoCal was 37 degrees in the late night.
@heatingairservices8708
@heatingairservices8708 8 ай бұрын
Hi Thanks for the tutorial but is it necessary to Jump out defrost pins on board 1 st ? or can one just move the defrost pin to test ? or short out speed up & force defrost , - thereby cking defrost senser @ same time ? just wondering Thanks for any all help
@NighthawkHVAC
@NighthawkHVAC 8 ай бұрын
You want to jump the defrost thermostat first then short test.
@s.kammerer1206
@s.kammerer1206 3 жыл бұрын
nice job! wow for a goodman it was quite! it must be a fluke!
@sknight0391
@sknight0391 3 жыл бұрын
No, it was a Fieldpiece 😄👌
@kaptaintrips
@kaptaintrips 2 жыл бұрын
No. It was 'quite'.
@rexford9019
@rexford9019 Ай бұрын
I Have a Goodman heat pump, less than 4 yrs old. Installed with my new home. Unit failed after 2 years. Installer said coolant was overcharged (600+ psi). Replaced compressor $1200 under warranty (part and labor). Unit failed again after that, blower motor was burned out. I paid $300+ to replace that. This past June unit failed again. $456 to replace capacitor. Unit failed again today blows warm air as usual, compressor and fan are running. No problem whatsoever during heating season only during cooling season. Needless to say I am not impressed with this Goodman heat pump which has cost thousands to repair and less than 4 years old. LEMON!!! Any suggestions?
@NighthawkHVAC
@NighthawkHVAC Ай бұрын
I'm sorry to see you're having so many issues with your AC unit. High pressure will kill a compressor. Especially if it's running for a long time. I'm surprised the high pressure switch didn't cut off your unit. Usually when this occurs the outdoor unit will cycle on and off and will not cool. The fact that your unit was overcharged is definitely a mistake by the installer or tech. The failed blower motor can be caused by dirty filters, under sized return grill/ducts, some type of airflow restriction, or an out of specification capacitor. If the replacement compressor was not installed properly you might have another compressor failure in the future. Unfortunately sometimes you can get a lemon. That goes for all brands. It might be a good idea to try to find another company to take a look at the unit to get another set of eyes on it. I wish you luck and hopefully no more issues.
@rexford9019
@rexford9019 Ай бұрын
Actually I’ve had 4 companies work on this unit. Most recent was a routine maintenance 3 days ago and they said everything checked out fine. I’m living in a desert climate for 35 years and in recent years the 100+ degree heat waves have been brutal, lasting 6 to 8 weeks during the summer months.
@NighthawkHVAC
@NighthawkHVAC Ай бұрын
You might try one of those condenser misters. Especially on the hotter days. It will reduce your head pressure lowering the load on the compressor. It looks like a joke when you see it, but in extreme heat it can be effective.
@rexford9019
@rexford9019 Ай бұрын
Technician came back today and diagnosed the problem as stuck reversing valve. Said replacing that should fix the issue.
@NighthawkHVAC
@NighthawkHVAC Ай бұрын
Fingers crossed 🤞
@roqueherrera8471
@roqueherrera8471 10 ай бұрын
Where u located at? In CA ?
@NighthawkHVAC
@NighthawkHVAC 10 ай бұрын
In Oregon.
@kaptaintrips
@kaptaintrips 2 жыл бұрын
Gotta love the Cali terminology for a closed switch. TRIPPED!
@BC-nn8hs
@BC-nn8hs Жыл бұрын
I have the a Goodman that is blowing the 3amp fuse. I traced it to the defrost board (red wire). I replaced the board, it ran for a few days but blew the fuse again. Any suggestions. FYI. I didnt see a short in the wiring but may switch to another wire for troubleshooting purposed. Thank for the great video!!!
@ictviamfortruthgoogleisspa5886
@ictviamfortruthgoogleisspa5886 8 ай бұрын
to watch your video WHY? i have to watch bullSHIT goggle comercial for 2-3 minutes??? this is fkg Insane
@losaguilar2640
@losaguilar2640 8 ай бұрын
Hi! This is very helpful; thank you for sharing! My unit every winter season freezes and I have to turn it off to allow melt but I guess is not in defrost cycle. Can I do it by myself or definitely need to hire a professional?
@cutum
@cutum 2 жыл бұрын
I tried the same process on my unit and when I remove the test pin jumper, it goes right back into heat mode. It does not stay in defrost mode. Maybe my board is bad?
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
You could try leaving the pin on test or try it without jumping the defrost thermostat. It’s weird. Some you have to leave the pin on some you have to remove it.
@cutum
@cutum 2 жыл бұрын
@@NighthawkHVAC Thanks for your response.
@marcoalvarez1276
@marcoalvarez1276 3 жыл бұрын
That’s such a bizarre thing in CA. I would imagine the power consumption of a 5kw or even a 10kw in defrost mode would be far lower than having to cool down the space and having to reheat it again after defrost. Not to mention the comfort issue
@NighthawkHVAC
@NighthawkHVAC 3 жыл бұрын
They figured gas fired furnaces were more efficient. Oh wait now they’re banning gas fired furnaces by 2028. Heat pumps with no aux heat are cleaner and more efficient. Lol.
@97Napkins
@97Napkins 3 жыл бұрын
Correct. Probably banned because California politics went all global warming crazy and thought that was a good idea. Now they gotta stop them damn cows from farting.
@kaptaintrips
@kaptaintrips 2 жыл бұрын
@@97Napkins Cow fartz < 410a release.
@soloch69
@soloch69 Жыл бұрын
Great video love it thank you can’t wait for the next one 👍🏻🍺🍺🍺
@cattoking
@cattoking 2 жыл бұрын
Thanks a lot! Maybe next time I’ll watch the entire video before trying to continue. Spent 10 minutes trying to get it to start by pulling fan power and putting flathead in between test. Looked you up, saw that you actually moved the time selector, tried that for 10 minutes. Finally coming back to actually watch the whole thing trying to figure out why I can’t get it to switch, figuring out a sensor was stopping me 🤦‍♂️
@TomLawson05
@TomLawson05 Жыл бұрын
Great video very. Informative keep up the good work
@hkhsm359
@hkhsm359 3 жыл бұрын
Nice job. Thanks for sharing your knowledge
@sknight0391
@sknight0391 3 жыл бұрын
Horrible! 😁😁😁 Nah man, you did a good job. That version of the defrost board is much better than some of the older designs where the defrost setting pins were on the top right hand side, and much harder to get to. And the two fan wires were located on the left side of the board, right there for the door panel to fall into them and short to ground when you're taking it off.
@cornbreadsfishing1036
@cornbreadsfishing1036 2 жыл бұрын
Good video buddy. California doesn’t allow electric heat strips??? That’s crazy. Are there a lot of dual fuel systems?
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
Yeah. Not even for auxiliary heat. Yet they want to get rid of gas fired furnaces all together. I haven’t seen any dual fuel in California personally. I’m sure they’re out there.
@cornbreadsfishing1036
@cornbreadsfishing1036 2 жыл бұрын
@@NighthawkHVAC a small are is controlling your state and ruining it for sure!
@dannymatthews855
@dannymatthews855 2 жыл бұрын
Excellent video. thanks..
@benjamintimmins1656
@benjamintimmins1656 3 жыл бұрын
Thanks where are you located in cali? It was 37 degrees?
@NighthawkHVAC
@NighthawkHVAC 3 жыл бұрын
I’m currently in Central Oregon I don’t know longer live in California.
@zwagoner3
@zwagoner3 2 жыл бұрын
My thermistor is tripped and kicks the defrost on but only lasts for a minute. If I jump the board it will run about 10 minutes. Why is this? Bad thermistor?
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
It could be the defrost thermistor or the defrost board. I’d start with the thermistor.
@zwagoner3
@zwagoner3 2 жыл бұрын
Thanks for the fast reply. The lower third of my heat pump has about 4” of ice on the outside and inside. I don’t think the defrost has been running for the whole duration causing this buildup here in Northern Idaho. Would it be a bad idea to leave the board jumped until I get a new thermistor? It will be under 40 degrees for a while.
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
If you do that It may just go into defrost constantly. I’d just run your heat in emergency mode till you can make your repair. Or set the timer as long as possible. Good luck!
@zwagoner3
@zwagoner3 2 жыл бұрын
Thanks for the help!
@nelsonsantos770
@nelsonsantos770 Жыл бұрын
How long does it take for heat pump to start pumping heat out of the register?
@Killerbuckets23
@Killerbuckets23 7 ай бұрын
It take a few minutes for the refrigerant to increase in temperature in the evaporator,
@brandonprice3927
@brandonprice3927 3 жыл бұрын
Can you possibly find a package unit to show the same thing?
@NighthawkHVAC
@NighthawkHVAC 3 жыл бұрын
If I come across a heat pump package unit.
@dombelardo4909
@dombelardo4909 2 жыл бұрын
Horible😄
@97Napkins
@97Napkins 3 жыл бұрын
Putting a goodman into defrost damages the operation. So does taking the door off. Touching one can cause issues. I once looked at one and it broke down. Legend has it that leaving them alone and never changing the filter makes a goodman last longer😆🤣
@NighthawkHVAC
@NighthawkHVAC 3 жыл бұрын
Lol
@kaptaintrips
@kaptaintrips 2 жыл бұрын
I bet you're a fan of Carrier, Pat. Don't poo poo on a decent brand.
@SuperSeanXXX
@SuperSeanXXX Жыл бұрын
Hey man I have a Goodman like in this video....and it's doing a defrost step every time the compressor runs.....like the thermostat is always closed.....how do I bypass it
@NighthawkHVAC
@NighthawkHVAC Жыл бұрын
Just unplug the coil thermostat.
@SuperSeanXXX
@SuperSeanXXX Жыл бұрын
@@NighthawkHVAC would one being low of freon cause this?
@NighthawkHVAC
@NighthawkHVAC Жыл бұрын
It is possible.
Water Source Heat Pump Not Cooling.  How to Diagnose. EP67
13:17
Nighthawk HVAC
Рет қаралды 15 М.
Troubleshooting the Goodman Defrost Board
14:52
John Jennings
Рет қаралды 84 М.
Inside Out 2: BABY JOY VS SHIN SONIC 3
00:19
AnythingAlexia
Рет қаралды 9 МЛН
А ВЫ ЛЮБИТЕ ШКОЛУ?? #shorts
00:20
Паша Осадчий
Рет қаралды 9 МЛН
when you have plan B 😂
00:11
Andrey Grechka
Рет қаралды 67 МЛН
Learn Everything About Heat Pump Defrost
26:00
HVAC School
Рет қаралды 69 М.
The Sequence of Operation for a Defrost Heat Pump Board
9:30
SuperCool Slide Rule
Рет қаралды 224 М.
HEAT PUMP FROZEN UP LIKE A ICE MACHINE I MISSED  UP & TOASTED THE FUSE
24:43
How a Variable Air Volume VAV System Works
16:54
MEP Academy
Рет қаралды 113 М.
Heat Pump Defrost Board Troubleshooting Tips
9:26
Fox Family Heating and Air Conditioning
Рет қаралды 41 М.
How an Air Handler & Heat Pump Work & are Controlled by 24v Thermostat Wires!
19:29
Testing heat pump defrost controls. #hvac #heatpump #hvactraining
18:01
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Jersey Mike HVAC
Рет қаралды 33 М.
How to diagnose a bad defrost board on a Goodman heat pump
15:34
Iron Shield Heating & Air
Рет қаралды 5 М.
HVAC Heat Pump Basics
11:11
HVAC School
Рет қаралды 355 М.
Inside Out 2: BABY JOY VS SHIN SONIC 3
00:19
AnythingAlexia
Рет қаралды 9 МЛН