How to Wire Discrete DC Sensors to PLC - Part 2

  Рет қаралды 316,803

RealPars

RealPars

Күн бұрын

Пікірлер: 231
@caffeinatedinsanity2324
@caffeinatedinsanity2324 4 жыл бұрын
To those who might struggle with sinking vs sourcing input plc cards: Sinking means that the input needs to be connected to +24 V to cause it to be detected as "activated". Sourcing cards mean that you need to connect the inputs on the negative of the 24 V. And now for PNP vs NPN: PNP: when the sensor detects something, it's signal (or load. Black wire) gets connected to +24 V, so it "pushes" or "sources" 24 V. NPN: when detecting something, the signal wire gets connected to the negative, so it will "pull" or "sink" current. Same logic applies if you want to use 2 wire sensors in both types of cards.
@enverismail6864
@enverismail6864 3 жыл бұрын
So on the npn card you need -24 power supply. That must be connected to the bottom of the IO card (the very last slot) and the common must be connected to the very first slot; where the +24 would normally be supplied. It's the only way this is making sense to me
@remingtonnathaniel6730
@remingtonnathaniel6730 3 жыл бұрын
sorry to be so offtopic but does anyone know a tool to log back into an instagram account? I was stupid lost the login password. I appreciate any tips you can give me!
@bentondarren9521
@bentondarren9521 3 жыл бұрын
@Remington Nathaniel instablaster =)
@remingtonnathaniel6730
@remingtonnathaniel6730 3 жыл бұрын
@Benton Darren thanks for your reply. I found the site through google and I'm waiting for the hacking stuff now. Looks like it's gonna take quite some time so I will reply here later with my results.
@remingtonnathaniel6730
@remingtonnathaniel6730 3 жыл бұрын
@Benton Darren it worked and I finally got access to my account again. Im so happy:D Thanks so much, you saved my account :D
@mikeduman358
@mikeduman358 2 жыл бұрын
I have been an electrician for 20 yrs I understood the concept but the kiddies on the job always took the PLC wiring and us older guys did the heavy lifting, motors,conduit this helped me greatly thank you
@eugenepohjola258
@eugenepohjola258 3 жыл бұрын
Howdy. Nice presentation. A couple of comments. 1. Using 2 -wire sensors (= Namur) the leaking current may be large enough to be detected as ON by the PLC DI card. To remedy this an external resistor of, say 10 k, may be connected over the input channel to deliver proper "sinking". 2. Separate 24 VDC power supplies should be used for input circuits and outout circuits. This prevents inductive load backspikes from generating "ghost" ON detections in input circuits. Alternatively the +24 rail may be splitted into two secondary + rails using two diodes in a back-flow blocking configuration. P600J is a 6 A diode. One secondary + rail powers the inputs and the other powers the outputs. The output secondary + rail should be fitted with a large electrolytic capacitor after the diode, say 2200 uF, between the + and the - to provide a place to go for possible backfire spikes. Electrolytic capacitors are not necessarily fast enough to kill spikes effectivery so a plastic capacitor of, say 1 uF, may be connected in parallel with the electrolytic capacitor. Regards.
@realpars
@realpars 3 жыл бұрын
Thank you, Eugene! We appreciate your insightful comments!
@isaacadokwah2739
@isaacadokwah2739 5 жыл бұрын
One of the best PLC videos ever. Very elaborate for easy understanding. Thanks for these great videos.
@realpars
@realpars 5 жыл бұрын
What a great compliment, Isaac! Thanks a lot! We are always extremely happy to hear such positive feedback! If you ever have any questions, feel free to reach out to us. Happy learning!
@lukaskohout419
@lukaskohout419 5 жыл бұрын
8:00 i think there is error in diagram--- if we talk about Voltage which is difference in potential between two poles then if you are showing +24VDC as positive pole and -24VDC as negative pole then you have potential of 48V! So it should be +24V and 0V or +12V and -12V etc...
@realpars
@realpars 5 жыл бұрын
The blue wire is common, or the negative side of the 24VDC power supply. The voltage difference between +24VDC and what is shown as -24VDC (common) is 24VDC. To be clearer, the common connection should have been shown as 0 VDC. Thank you for the observation and comment.
@bobbyyoung2831
@bobbyyoung2831 2 жыл бұрын
Great Free advice and videos. Much appreciated.
@realpars
@realpars 2 жыл бұрын
Glad you like them!
@TheGoodSon89
@TheGoodSon89 3 жыл бұрын
Massive respect for sharing knowledge. Keep going!
@realpars
@realpars 3 жыл бұрын
Much appreciated!
@mernilodeleon4081
@mernilodeleon4081 6 жыл бұрын
Yes sir...thanks a lot everyday i am watching your shared videos ...coz directly related to my work now...i wish i ciuld able to join your training....one of these day. Thanks and more power....
@realpars
@realpars 6 жыл бұрын
Thank you Mernilo! Glad to hear that you're enjoying the videos.
@suchayanmondal9858
@suchayanmondal9858 6 жыл бұрын
Very Informative videos. Thanks for providing us for the knowledge. Please produce more nice videos on several PLC related topics like this in future. Awaiting for the next.
@rodrigocardenassill4700
@rodrigocardenassill4700 5 жыл бұрын
The best channel to learn, thank you for your valious content
@realpars
@realpars 5 жыл бұрын
Thanks for your comment! Happy to hear that!
@suheladesilva2933
@suheladesilva2933 5 ай бұрын
Great video, cleared a lot of my doubts, thanks.
@realpars
@realpars 5 ай бұрын
Glad it helped! Happy learning
@D0m1n4t0r33
@D0m1n4t0r33 4 жыл бұрын
Thanks alot for your videos, they surely are helpful if you're setting up stuff for the first time!
@realpars
@realpars 4 жыл бұрын
Great to hear that, Bas! Thanks for sharing.
@BW-xz6ol
@BW-xz6ol 4 жыл бұрын
14:30 if connecting to plc input 3 shouldn’t black wire Goto B? I think you meant to say if it connects to plc input 2 then it goes to terminal A. I’m new to all this... so thank you very much for all your videos
@juliuscontrolsandautomatio6861
@juliuscontrolsandautomatio6861 2 жыл бұрын
So great! So good! 👏👏👏👏 I'd like to learn about how to Wire Discrete DC Sensors to Variable Frequency Drive.
@realpars
@realpars 2 жыл бұрын
Great suggestion! Thanks for sharing and happy learning, Julius!
@eng.mohamedfandod1937
@eng.mohamedfandod1937 5 жыл бұрын
excellent Go ahead i will support your channel in every where .
@realpars
@realpars 5 жыл бұрын
Thanks a lot for your support, Mohamed!
@michaelcostello6991
@michaelcostello6991 5 жыл бұрын
well explained with appropriate diagrams. Only guys like you should have a license to teach !!!
@realpars
@realpars 5 жыл бұрын
That's a great compliment, Michael! Thanks a lot!
@yosefali7729
@yosefali7729 Жыл бұрын
is it safe to power the Sensors and field devices through the PLC input card, most cards have really low limit on current so connecting like 10 - 12 devices might be risky, how about powering it through a Power supply instead from the PLC input card ? wouldn't that be better ? appreciate your efforts in simplifying this great effort
@realpars
@realpars Жыл бұрын
Thank you for your question. In our videos, we focus on sensors specifically designed to interface with a PLC. The input cards are responsible for receiving signals from these sensors, while the output cards supply power to your device according to your engineering specifications and current requirements. If necessary, the output cards can also power relays for handling larger currents. Every industrial PLC manufacturer typically provides a manual detailing how to use and program their PLCs. Additionally, it's important to ensure you have a suitable power supply to energize your system. Happy learning!
@mernilodeleon4081
@mernilodeleon4081 6 жыл бұрын
Great job...more technician like could benefits this learning....please continue...
@realpars
@realpars 6 жыл бұрын
Thanks for watching Mernilo!
@longhungtruong7980
@longhungtruong7980 5 жыл бұрын
I have one question for RealPars: What exact function difference between 2-wire and 3-wire DC sensor? Use the 2-wire one is more easier than 3 wire when we connect with PLC. So, Why we don't have 2-wire DC sensor for Level switch and pressure switch? The information of this video is excellence. Please help me answer previous question. Thank RealPars.
@realpars
@realpars 5 жыл бұрын
The difference is fairly simple to explain. Sensors that are simple contact closures, such as limit switches, flow switches, hall-effect proximity switches, and vibratory level switches are all two-wire devices. One wire is 24VDC+ and the other is common, or 0VDC. These sensors are either mechanically or magnetically actuated or can use the 24VDC+ wire to power the device. Sensors based on solid-state technology require 3 wires. Solid-state devices are based on transitor circuits which require 3 wires: 24VDC+ applied to the base, a signal wire that goes back to the PLC as the input from the collector, and a ground wire for the emitter. Solid state devices are smaller and many times configurable as to setpoint, trip point, etc., but they also require 3 wire connections. That is why it is important to understand how to properly connect these to the PLC.
@longhungtruong7980
@longhungtruong7980 5 жыл бұрын
@@realpars So, Thanks for your explanation. I'm clear about function of both sensors types. Please release more videos like this. I keep following and learning with you.
@eliehajj3777
@eliehajj3777 2 жыл бұрын
A "Sinking" PLC input card has (0 VDC) commonly connected to all its Inputs. Therefore it needs PNP Sensors to be connected to it. A "Sourcing" PLC input card has (+24 VDC) commonly connected to all its inputs. Therefore it needs NPN Sensors to be connected to it. So for the example in the video above the inputs (from I0.0 to I1.7 ) should be commonly connected to ( - ), therefore terminals 10 and 11 should be connected to ( - ), not to (+24 VDC) because it is a "Sinking" input card and only accept PNP sensors. I hope that I'm wrong.😀
@Rexbo12
@Rexbo12 3 жыл бұрын
Really well explained. Thank you
@realpars
@realpars 3 жыл бұрын
Glad you liked it!
@Rexbo12
@Rexbo12 3 жыл бұрын
I'm just starting to learn about plc as its going to be needed for my new position thanks a lot even dumb ass like me can understand
@spatikmedia
@spatikmedia Жыл бұрын
Awesome..thank you Realpars
@realpars
@realpars Жыл бұрын
You're very welcome!
@user-ro6ou5vb8y
@user-ro6ou5vb8y 3 жыл бұрын
Thanks God for sharing this matter i indeed very interested and i wish i could learn more about plc such as how to program.
@realpars
@realpars 3 жыл бұрын
You are welcome!
@adriandeluna8906
@adriandeluna8906 3 жыл бұрын
Perfect video congrats to your channel..
@realpars
@realpars 3 жыл бұрын
Thank you very much, Adrian!
@ahmedadebakin8189
@ahmedadebakin8189 6 жыл бұрын
Really nice video but I have one question concerning NPN sensors. If I give positive to the brown wire from the PLC will I still connect same to common of the Input card?
@P.J16
@P.J16 4 жыл бұрын
7:49 Blue wire should be -24 Vdc or just O V?
@realpars
@realpars 4 жыл бұрын
It is best to consider the blue wire as common, or 0V.
@darbarisid
@darbarisid 5 жыл бұрын
Very good explanation
@jimbass924
@jimbass924 3 жыл бұрын
Very informative, great graphics!!
@realpars
@realpars 3 жыл бұрын
Much appreciated!
@andyhandyman2118
@andyhandyman2118 3 жыл бұрын
Always like and subscribed!
@realpars
@realpars 3 жыл бұрын
Thank you, Andy!
@bitebonumbere1426
@bitebonumbere1426 3 жыл бұрын
Awesome videos. Please can you upload the subtitles? The auto-generated one is difficult to follow. Thanks.
@realpars
@realpars 3 жыл бұрын
Hi Bitebo, Thanks for your comment! We have English subtitles for almost all our KZbin video courses. Unfortunately, some of our older video courses do not have this, and only have the auto-generated option. Sorry about that, hopefully you are still able to enjoy them!
@bitebonumbere1426
@bitebonumbere1426 3 жыл бұрын
@@realpars meaning is it impossible to add subtitles?
@dilantharuwan7373
@dilantharuwan7373 3 жыл бұрын
Nice explane and great work.keep it up
@realpars
@realpars 3 жыл бұрын
Glad you liked it, Dilantha!
@toddmaggio2032
@toddmaggio2032 3 жыл бұрын
Thank you for your educational videos. I have a two question that you might have already answered elsewhere. If so I'd be grateful for the links. Can a proximity sensor be used as a SPDT switch? Say I want a conveyor belt go back and fort. Can the wiring be tweaked in such way that sensor reverses the direction of the electrical circuit and make the conveyor belt reverse its direction?
@realpars
@realpars 3 жыл бұрын
A proximity sensor be used as a SPDT switch only if it is designed as a SPDT switch. Many (if not most) proximity switches used today are solid state, so there is only one output available, and it is transistor output, not a Form C contact. For your second question, you can use the proximity switch input as a trigger for PLC logic to act to reverse the belt. You likely will also need some timers in this logic as well. If you were to do this in a hardwired system, it can be done with a series of relays, sensors, and timers, but the proximity sensors would still be wired as shown in this video.
@tomcasarella6061
@tomcasarella6061 2 жыл бұрын
A PNP device is wired to a PNP card the common on the card is Negative input to the card is Positive
@mateorenai
@mateorenai 6 жыл бұрын
Hello.. Thankyou for your clear explanation about this. I am just learning about this PLC thing. but i have more question. how do you connect multiple let say 4 Proximity sensor. Thanks again
@photog1529
@photog1529 4 жыл бұрын
New to this, but a question. at about 14:34, you state if the proximity switch is connected to terminal 3, the load wire would be connected to "A"...shouldn't the load be connected to "B"?
@realpars
@realpars 4 жыл бұрын
At that point in the video, the schematic correctly shows a PNP sensor connected to the first channel of the PLC card, which is at terminal 2 of the input card, or terminal A on the marshalingpanel. The narration says "PLC input channel 3", the black wire should be connected to C, which is connected to screw terminal 4 on the PLC card.
@KevinNguyen-tw5ml
@KevinNguyen-tw5ml 9 ай бұрын
Thank you very much !
@realpars
@realpars 9 ай бұрын
You are welcome!
@tipko1863
@tipko1863 3 жыл бұрын
Am I missing something or is the wiring diagram for the PNP type switch around 9:09 (where - is the common wire on the input cards) different than than the one shown around 13:57 where the +24V is the common for the 2 groups of inputs?
@realpars
@realpars 3 жыл бұрын
No. in both cases, the (-) is attached to terminal 20 on the I/O card, which is common (blue wire).
@tipko1863
@tipko1863 3 жыл бұрын
@@realpars Alright, so then the wires connecting pins 10 and 11 to 24 V are used to power those groups of inputs or something else?
@wasuts.444
@wasuts.444 6 жыл бұрын
Your videos very helpful, Thanks very much. and I saw the subtitles start at 15:35 explain about PNP but your are talking about NPN first, I think the subtitles was wrong place, just let you know.
@realpars
@realpars 6 жыл бұрын
You're right! Thank you for letting us know.
@wasuts.444
@wasuts.444 6 жыл бұрын
RealPars You’re welcome.
@deku4497
@deku4497 4 жыл бұрын
I am confused with the explanation in time stamp 14:00. I thought if we will be using a PNP sensor, we need to use a Sinking Input Card. From what i know the input card he uses to demonstrate it is a Sourcing Input Card. Because the +24V is the one that is shared to the terminals 10 and 11. Please help I'm a beginner and I'm confused.
@deku4497
@deku4497 4 жыл бұрын
Or maybe I'm wrong for thinking that it is a Sourcing Input Card based on it's internal connection. Please correct me if im wrong
@realpars
@realpars 4 жыл бұрын
The card shown is one of several Siemens SM321 digital input cards that can support 2, 3, and 4-wire sensors in any configuration. [support.industry.siemens.com/cs/mdm/8859629?c=97343653771&lc=en-MY]. The PNP sensor is sourcing, so the +24VDC is applied to the sensor (brown wire) and when switched, the current is sunk to ground through the DI input terminal to ground. In the above link, follow the signal through the circuit to "M", which is connected to terminal 20 (ground).
@franciscojorge6568
@franciscojorge6568 2 жыл бұрын
That's so cool plc exemple.
@yem.t.3930
@yem.t.3930 6 жыл бұрын
Very comprehensive ! Thanks
@realpars
@realpars 6 жыл бұрын
You're very welcome!
@marcbiss5953
@marcbiss5953 5 жыл бұрын
Very clear and informative! Thanks
@realpars
@realpars 5 жыл бұрын
Great to hear that, thank you!
@ardentdfender4116
@ardentdfender4116 5 жыл бұрын
Along with this very well explained video, can you please add a video for “loop Checking” or how to properly Loop Check of devices to Terminal Block or Input Card/ Output Card module for the RealPars video team to do.
@realpars
@realpars 5 жыл бұрын
Thank you, Ardent! I have gone ahead and forwarded your topic suggestion to our creator team. Hopefully, they can add it to the list. Thanks again!
@MrPromerican
@MrPromerican 4 жыл бұрын
Thank you real pars
@realpars
@realpars 4 жыл бұрын
You are very welcome!
@hayel2015
@hayel2015 6 жыл бұрын
You are the best to explain the PLC💝💝💝👍👍👍
@thairaltimemy7287
@thairaltimemy7287 5 жыл бұрын
Thanks a lot for your good ,brief , explanation....keep going
@realpars
@realpars 5 жыл бұрын
You are very welcome, Thair! Happy learning.
@night_grinder1378
@night_grinder1378 5 жыл бұрын
Greatvideo. Real pars. Can you make video how to troubleshoot devices.? Thanks it will help a lot.
@realpars
@realpars 5 жыл бұрын
Thanks for your support, Christian! And thanks for the topic suggestion, I will definitely go ahead and forward this to our creator team. Happy learning!
@boothhits6144
@boothhits6144 4 жыл бұрын
great channel thank you so much
@realpars
@realpars 4 жыл бұрын
Thanks for your support!
@mnada72
@mnada72 4 жыл бұрын
Sinking switch (NPN) needs sourcing module hence the common of the module is positive Sourcing switch (PNP) needs sinking module hence the common of the module is negative
@xhuljan11
@xhuljan11 3 жыл бұрын
Thanks a lot ❤️
@psi23k
@psi23k 4 жыл бұрын
@8:23 you show the brown wire from the npn sensor connected to the negative of the I/O card. Is that correct? Shouldn't it be connected to 10 or 11?
@realpars
@realpars 4 жыл бұрын
For a sinking sensor, the brown wire is connected to the most positive terminal on the PLC card. In this configuration, 24VDC is applied to the common terminal of the PLC card, as shown. This is true for the Siemens DI card chosen, but it is always good to check the specific wiring diagram for the card you are using before connecting a sensor. Some manufacturers have different models of DI card depending on the sensor type (sinking or sourcing).
@sntgjmb6195
@sntgjmb6195 6 жыл бұрын
Thanks for the information, from Ecuador
@realpars
@realpars 6 жыл бұрын
You're very welcome! Happy to have viewers from all over the world! Happy learning ;).
@maruthiprasad8184
@maruthiprasad8184 4 жыл бұрын
Team,Thank you so much for valuable information. I have a doubt on control valve resolution concept from long time. Is it possible to make a video on this concept. It will be great help to everybody.
@realpars
@realpars 4 жыл бұрын
Hi Maruthi! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@DannyJaves
@DannyJaves 4 жыл бұрын
The best information excellent
@davidpalmer963
@davidpalmer963 3 жыл бұрын
Image result for what can a inductive proximity switch detect? Inductive proximity sensors can only detect metal targets. They do not detect non-metal targets such as plastic, wood, paper, and ceramic
@kittylayyon2789
@kittylayyon2789 4 жыл бұрын
Thanks real pars
@realpars
@realpars 4 жыл бұрын
You are very welcome!
@vishnukr8010
@vishnukr8010 2 жыл бұрын
Hi, Can we ever connect a PNP sensor to PNP I/O card? I got a qsn like that in an assesment, any possiblity please help.
@realpars
@realpars 2 жыл бұрын
Yes, it is possible, but you will need to modify the circuit with a resistor and non-standard wiring connections. I do not recommend doing this because it will confuse other techs who may need to maintain the system.
@vishnukr8010
@vishnukr8010 2 жыл бұрын
@@realpars I got this as a qsn on one assesment..? Is there a proper answer for that ..is that just a pull down resistor
@realpars
@realpars 2 жыл бұрын
@@vishnukr8010 I believe the 24VDC connection at the I/O card is removed, and a 10k resistor is placed between the (-) terminal and ground for the digital input. Again, this is not standard and would require specific detailed documentation to avoid future issues. I would say the proper answer to an assessment question would be "no" if the question was looking for a binary choice. If you were to able to provide an explanation in the answer, I would respond, "yes, but the solution is non-standard and should not be implemented unless absolutely necessary".
@vishnukr8010
@vishnukr8010 2 жыл бұрын
@@realpars thank you mate.. Its not a boolean type I have to draw the electrical circuit and submit. Anyway, thank for your reply it was very helpful.
@mprv3755
@mprv3755 6 жыл бұрын
Great video. Possibly a video on how to use “scale/ scaling ” PID instruction on Analog instrumentation on Siemens or Allen Bradley?
@realpars
@realpars 5 жыл бұрын
This topic is covered in a 9-part course on using the PID instruction in an S7-1500 on the Realpars.com learning site. Come subscribe and give it a try!
@zukhriddinmirzaumarov1758
@zukhriddinmirzaumarov1758 6 жыл бұрын
Thanks, really good job!
@realpars
@realpars 6 жыл бұрын
Great to hear! You are very welcome.
@erturkmemmedli1790
@erturkmemmedli1790 6 жыл бұрын
In 13:43, you show connection for pnp. So I guess for npn, unlike pnp, red wire must connect to 20 (negative terminal) and blue wire must connect to 10 (positive terminal). However, for npn, in 8:43, you showed red wire is connected to positive terminal of power source and blue one is connected to negative terminal of power source. I didn't get it. With that way, we connect positive terminal of power source to 20 in PLC (negative side), how is it possible?
@realpars
@realpars 6 жыл бұрын
You make a good observation. But remember what was indicated in the video: a sinking discrete input card (for use with pnp sensors) and a sourcing discrete input card (for use with npn sensors) operate differently and are also wired differently. The function of Terminal 20 in each type of card is also different. Most plants will use pnp sensors with sinking input cards, simply because they are most common and are easier to wire. The npn and sourcing input cards sensors are mentioned because there are some industries where these type sensors are more common, and most manufacturers offer products with both types of configurations. It is therefore important to know the differences and specify the right type of sensor, and the right type of PLC card.
@erturkmemmedli1790
@erturkmemmedli1790 6 жыл бұрын
Thank you very much. I haven't noticed that the connections for sinking and sourcing discrete input cards are different. Now, everything is totally okay :)
@almir2673
@almir2673 6 жыл бұрын
RealPars in the video npn is sinking type and pnp is sourcing, very useful video by the way, thanks for sharing your knowledge.
@javierferrer4634
@javierferrer4634 6 жыл бұрын
Very nice video!
@jcerranom
@jcerranom 3 жыл бұрын
Simply Awesome!!
@realpars
@realpars 3 жыл бұрын
Glad you like it, Julio!
@isidrovaldez2391
@isidrovaldez2391 4 жыл бұрын
I don’t think that an inductive proximity switch could detect a box. I was under the impression that an inductive prox only detected ferrous metals, and a capacitive proximity switch would be used to detect things like plastics, wood, liquids, and boxes.
@imamulkabirhimel7477
@imamulkabirhimel7477 4 жыл бұрын
What if i want to connect npn switch. Should the brown be connected to 20 and blue to 10?
@abrahamgreenidge8924
@abrahamgreenidge8924 5 жыл бұрын
Hello, do you have any basic basic basic instructional video on the wiring of PLC? I’m neww to this & has 0 experience.
@realpars
@realpars 5 жыл бұрын
This video and the companion Part 1 video provides good instruction on wiring discrete devices to the PLC. Other RealPars videos give instruction wiring other modules, power supplies, etc.
@richatpurba9047
@richatpurba9047 4 жыл бұрын
so if we accidentally buy a PNP switch when it should be an NPN switch, we can't just switch the wiring termination to make it works?
@realpars
@realpars 4 жыл бұрын
This can be done only if the PLC card supports sourcing and sinking type switches. An NPN sensor requires a sourcing PLC input and a PNP sensor requires a sinking PLC input.
@Levon9404
@Levon9404 6 жыл бұрын
Tank you very much for very informative vedios
@realpars
@realpars 6 жыл бұрын
You're very welcome Levon!
@SinhPV
@SinhPV 6 жыл бұрын
Useful a video ! Thank for sharing...
@realpars
@realpars 6 жыл бұрын
You're very welcome!
@hiwaabdulrazaq7920
@hiwaabdulrazaq7920 3 жыл бұрын
Thanks
@venkatvijayakumar6176
@venkatvijayakumar6176 4 жыл бұрын
Hi, I have two Level Sensors which is 4-20mA type. But, I have only one 24 VDC supply adapter. Is it possible share the DC supply to two sensors to get the 4-20mA output?
@realpars
@realpars 4 жыл бұрын
Yes, as long as your power supply can output at least 50ma (20ma for each sensor). This is normally how analog circuits are set up: common power supply with individual milliamp signals back to an analog input card. The sensor is the device that regulates the milliamp signal.
@venkatvijayakumar6176
@venkatvijayakumar6176 4 жыл бұрын
@@realpars Thanks a lot, I'll check on that.
@priceless55
@priceless55 6 жыл бұрын
Simplicity is the key. :)
@realpars
@realpars 6 жыл бұрын
Definitely! ;)
@eliosgreek8028
@eliosgreek8028 5 жыл бұрын
Great video
@realpars
@realpars 5 жыл бұрын
Thank you, Elios!
@glaucioferreira13
@glaucioferreira13 6 жыл бұрын
Thanks for this usefull video!
@realpars
@realpars 6 жыл бұрын
You are welcome, Glaucio!
@Logical_Controls
@Logical_Controls 6 жыл бұрын
Informative video. Thanks. FYI slight text error @ 7:53
@realpars
@realpars 6 жыл бұрын
Thank you! Happy to hear! I just double checked to video. However, I couldn't spot any error.
@Logical_Controls
@Logical_Controls 6 жыл бұрын
Thanks for the reply Realpars. Nothing major, it's just says +24VCD instead of +24VDC. Also shouldn't it be 0VDC for the blue wire as opposed to -24VDC which is a negative voltage instead of a ground?
@chuchuokeke
@chuchuokeke 5 жыл бұрын
Also, plc terminal 2 is point A on the marshaling terminal block..i think you said point 3 is A..great work, very informative. Keep it up for more likes!
@hoangzxc2467
@hoangzxc2467 5 жыл бұрын
oh hi, It makes me confused and wondered when the actual PLC I/O cards in this video that's not shown the actual power supply used to power the card(I mean it's just shown that the card requires +24VDC power and there's only +24VDC (shown by number) to the terminals(at 12:20). it's quite different to the PLC module's common terminal shown at (8:28) ), please help me to understand that correctly
@realpars
@realpars 5 жыл бұрын
In order to highlight the important wiring connections, we often just represent the power connection as +24VDC and common connection as COM. If we had shown the actual power supply in the diagram, +24VDC and COM would be connected to the power supply at terminals of the same name.
@hoangzxc2467
@hoangzxc2467 5 жыл бұрын
oh hi, in this video, is proximity switch the same proximity sensor ? (at 6:01)
@realpars
@realpars 5 жыл бұрын
Yes. A proximity sensor is typically a solid state switch that is tripped when the sensor is moved near a target.
@shuhaibvk2456
@shuhaibvk2456 5 жыл бұрын
Very informative👌🏼
@realpars
@realpars 5 жыл бұрын
Happy to hear that! Thank you, Shuhaib!
@phillyo51
@phillyo51 4 жыл бұрын
How can you find out which cards are compatible with PNP or NPN?? I've checked the siemens support website but have found no information. Cheers.
@realpars
@realpars 4 жыл бұрын
Check out this article: support.industry.siemens.com/cs/document/23451499/what-is-the-meaning-of-the-terms-sinking-(german%3A-p-lesend-)-and-sourcing-(german%3A-m-lesend-)-in-digital-modules-of-simatic-?dti=0&lc=en-WW The cards compatible with NPN and PNP wiring are listed toward the bottom of the article referenced above.
@MegaRyad
@MegaRyad 3 жыл бұрын
if you put electrons going in and out in the animation it would have been better to understand this pnp and npn sensors , thank you
@realpars
@realpars 3 жыл бұрын
Thanks for the feedback! I will happily go ahead and pass this on to our course creators. Thanks again for sharing and happy learning
@andersonsardinha1504
@andersonsardinha1504 3 жыл бұрын
Perfect 😃
@AgentK-111
@AgentK-111 4 жыл бұрын
i cannot understand why the black wire of the sensor is conected to the terminal A when, the plc input channel 3 corresponds to terminal D
@realpars
@realpars 4 жыл бұрын
Kostadin, thank you for your comment. You are correct. The video narration indicates Channel 3 on the PLC card, which corresponds to marshaling terminal D, if you consider the channels on the PLC card to be 0 - 7. To be honest, to avoid confusion, the narration should have indicated "connected to the first channel..." which would be marshaling terminal A.
@AgentK-111
@AgentK-111 4 жыл бұрын
@@realpars thanks for answering
@anwarmuzamil6972
@anwarmuzamil6972 4 жыл бұрын
Which type of PLC is used for connecting dc sensors??
@realpars
@realpars 4 жыл бұрын
Most any PLC can interface to DC sensors. You just need to have I/O, either connected to the PLC or in remote I/O racks that support DC sensor signals. It is the type of I/O card that determines the signal interface allowed at that card, not the type of PLC itself.
@mikemwabilwa572
@mikemwabilwa572 5 жыл бұрын
Many thanks
@realpars
@realpars 5 жыл бұрын
You are very welcome, Mike!
@rongulamhusain981
@rongulamhusain981 3 жыл бұрын
I want to learn plc course, kindly let me know how should I connect to u
@realpars
@realpars 3 жыл бұрын
Hi Ron! Thanks for your comment! Great to hear your motivation in regard to learning PLC Programming. 

Our course library is specifically designed in a way where it provides all the tools needed for beginners to evolve into an advanced level through our hands-on courses. Feel free to browse through our course library to see all the different topics we are covering. bit.ly/30AVJaR Just to let you know, that we also have a free course on PLC Hardware bit.ly/2XnnUrF
 If you are interested, you will obtain full access to our complete course library (400+ video courses) by subscribing to either our monthly package for €22.12 a month or our yearly package for €159.28,-. 

Additionally, you will have access to our Technical Team - consisting of high ranking engineers with a lifetime of experience - who are here to help you out with any questions you might have along the way! 
 Hope this helps! If I can be of any further assistance, please let me know - I’m more than happy to help!
@oyekanmibamidele6196
@oyekanmibamidele6196 3 жыл бұрын
@@realpars Sir, I'm seen different prices on your website?
@oyekanmibamidele6196
@oyekanmibamidele6196 3 жыл бұрын
@@realpars l would have sub for a year package
@frankietrenado9327
@frankietrenado9327 5 жыл бұрын
I believe if wiring into IO channel 0.3 the black input wire should go to terminal D
@realpars
@realpars 5 жыл бұрын
It does. In video, terminal 1 is 24VDC, terminal 2 is I0.0, terminal 3 is I0.1, terminal 4 is I0.2, and terminal 5 is I0.3, connected to "D".
@GRant16NCH
@GRant16NCH 6 жыл бұрын
Thanks for video
@adhavtejashri
@adhavtejashri 6 жыл бұрын
How we can connect 2 proximity switches at 24 vdc common terminals.
@realpars
@realpars 6 жыл бұрын
In the video, only one sensor is connected. If you have multiple sensors connected to the PLC card, external terminal blocks will be required. If you have a 16-point input card, there will ultimately be 16 connections to 24 COM. In this case, I would take 17 DIN-rail terminal blocks, jumper them together, connect the input common wires to the first 16 terminal blocks (one per block), and connect the 17th terminal block to 24 COM.
@jawadkhan6531
@jawadkhan6531 5 жыл бұрын
Connect two wire riela
@jay_rana
@jay_rana 6 жыл бұрын
What will be the connection for npn switch?
@realpars
@realpars 6 жыл бұрын
Watch this kzbin.info/www/bejne/aKHHp6mnoMyod5Y
@sattara6901
@sattara6901 6 жыл бұрын
RealPars this link dosn't work
@realpars
@realpars 6 жыл бұрын
Hey! I just checked the link kzbin.info/www/bejne/aKHHp6mnoMyod5Y and it works fine. Can you please try again? :)
@scottsommer6480
@scottsommer6480 6 жыл бұрын
In the video linked at kzbin.info/www/bejne/aKHHp6mnoMyod5Y, start watching at about 6:30 for the discussion of wiring of an NPN device.
@ieight8234
@ieight8234 5 жыл бұрын
blue wire is -24v? so potential difference between blue and brown (+24v) is 48v? 😉
@scottsommer6480
@scottsommer6480 5 жыл бұрын
The blue wire is common, or the negative side of the 24VDC power supply. The voltage difference between +24VDC and what is shown as -24VDC (common) is 24VDC.
@jeremyk2173
@jeremyk2173 5 жыл бұрын
@@scottsommer6480 the difference between +24 and -24 is 48v. The blue wire is 0v, not -24v
@scottsommer6480
@scottsommer6480 5 жыл бұрын
@@jeremyk2173 Technically, yes.
@suhail8086123757
@suhail8086123757 6 жыл бұрын
Wonderful videos
@pradippatole1328
@pradippatole1328 6 жыл бұрын
plz share video related to potential free contact and wetted contact
@realpars
@realpars 6 жыл бұрын
Glad to have you as a subscriber! :)
@alhassanalmusawy2056
@alhassanalmusawy2056 5 жыл бұрын
thanks,and please keep going
@realpars
@realpars 5 жыл бұрын
You are very welcome! Thanks for your support!
@charliechimples
@charliechimples 5 жыл бұрын
Great vid once again, well explained. 🐵
@realpars
@realpars 5 жыл бұрын
Thanks a lot!
@3498137
@3498137 2 жыл бұрын
Excellent¡
@realpars
@realpars 2 жыл бұрын
Thank you!
@runbou3485
@runbou3485 2 жыл бұрын
Thankអរគុណ👏
@samisrour3129
@samisrour3129 4 жыл бұрын
great videos.. hope to be fine
@grow8151
@grow8151 6 жыл бұрын
Very good
@amilabalasooriya8944
@amilabalasooriya8944 6 жыл бұрын
Thanks.keep going
@realpars
@realpars 6 жыл бұрын
Thanks for watching!
@suhelpatel2028
@suhelpatel2028 6 жыл бұрын
Beautiful 👌
@GRant16NCH
@GRant16NCH 6 жыл бұрын
Make vedio.. different connection AI, AO analog detection
How to Wire Discrete DC Sensors to PLC - Part 1
13:58
RealPars
Рет қаралды 347 М.
What is a Servo Motor and How it Works?
15:45
RealPars
Рет қаралды 2,1 МЛН
Une nouvelle voiture pour Noël 🥹
00:28
Nicocapone
Рет қаралды 9 МЛН
What Does an Orange Wire Do in an Electrical Control Panel?
8:01
What is HART Protocol?
17:01
RealPars
Рет қаралды 1 МЛН
How 3 Phase Power works: why 3 phases?
14:41
The Engineering Mindset
Рет қаралды 2,2 МЛН
What is PNP Sensor? Working, Wiring and Testing
8:01
Automatedo
Рет қаралды 57 М.
Proximity Sensor Interfacing to PLC made easy
18:14
Dorian McIntire
Рет қаралды 221 М.
Servo Motor Advantages And Disadvantages
15:10
RealPars
Рет қаралды 170 М.
Automotive Oscilloscopes: What you need to know
37:11
How a Car Works
Рет қаралды 336 М.
Une nouvelle voiture pour Noël 🥹
00:28
Nicocapone
Рет қаралды 9 МЛН