What is Intrinsically Safe?

  Рет қаралды 99,677

RealPars

RealPars

Күн бұрын

Пікірлер: 64
@Roberval.Bulgarelli
@Roberval.Bulgarelli 2 жыл бұрын
Clear, simple and straightforward basic explanation of the main aspects and concepts of intrinsic safety. Congratulations! Just a small conceptual comment: Both "classified" and "unclassified" areas need to be considered and deemed as "SAFE". Electrical, automation and instrumentation installations, in both cases, need to use equipment with appropriate "Ex" protection types (in classified areas) or associated equipment (in non-classified areas), in addition to performing the applicable installation, inspection and maintenance "Ex" service procedures, according to IEC 60079-14 and IEC 60079-17. 👍 Thus, it is suggested to use the term "UNCLASSIFIED AREA" or "NON HAZARDOUS AREA" instead of "SAFE AREA".
@MrDinger24
@MrDinger24 2 жыл бұрын
Absolute brilliance! Teaching this to new apprentices and time and time again I find exactly what I am teaching right here at RealPars - Thank you
@realpars
@realpars 2 жыл бұрын
You're very welcome!
@Sumit-Instrumentation-p6h
@Sumit-Instrumentation-p6h 13 күн бұрын
Absolutely perfect way of explaining. !
@realpars
@realpars 12 күн бұрын
Glad it was helpful!
@tonyj8949
@tonyj8949 3 жыл бұрын
For your example division two actually refers to the presence of a hazardous atmosphere under abnormal operating conditions such as maintenance
@mervbohrer3537
@mervbohrer3537 3 жыл бұрын
Did they flip flop Div 1 and 2 (normal vs abnormal) in this video?
@rsmakishi
@rsmakishi 3 жыл бұрын
I can’t remember where I read it but it said that Div.2 is presence of a hazardous atmosphere less that 6 hours per year which means emergencies only and Div.1 is over 6 hours per year.
@leojrbarcenas8813
@leojrbarcenas8813 3 жыл бұрын
I agree; I also think that they got it switched with Division 1.
@87113037
@87113037 2 жыл бұрын
4:29 Division 2 means particles present during ABNORMAL operations.
@zakirsayed111
@zakirsayed111 2 жыл бұрын
Hello, the video was really helpful in understanding intrinsic safety in a context of plc control system. But, I have something to clarify. It was said in the video that Div 1 is for environment where combustible dust is present during abnormal conditions. I think abnormal is for Div 2. Would like if you can give clarification on this. Thank you
@realpars
@realpars 2 жыл бұрын
Correct. Div 1 conditions exist where the hazard is normally present. Div 2 is when the hazard exists under abnormal conditions.
@emmanuelsanusi1389
@emmanuelsanusi1389 3 жыл бұрын
Thank you Realpars. You are doing great!
@realpars
@realpars 3 жыл бұрын
Glad you like them!
@abdelrahmanabdelgadier5537
@abdelrahmanabdelgadier5537 10 ай бұрын
Very useful as usual from RealPars
@realpars
@realpars 10 ай бұрын
Glad it was helpful!
@anusyirvan
@anusyirvan 2 жыл бұрын
On minutes 5:00 when photo-eye ON it will turn on a diode. Where is the power from? Is there any battery inside photo-eye?
@realpars
@realpars 2 жыл бұрын
The power (usually 12VDC or 24VDC) comes from the PLC card it is attached to, or in some cases, an external power supply. Photo eyes do need a power source.
@anusyirvan
@anusyirvan 2 жыл бұрын
@@realpars But on the video 05:00 the circuit only connected with light diode to PLC. Is there any other wire to photoe eye to carry 24VDC?
@Solder_it
@Solder_it 7 ай бұрын
I think the power will not come from PLC card, the power is from external source, then the feedback (alarm reading or normal reading from the photo eye) ia connected to the barrier, the barrier then converts that small signal to a higher voltage signal to reach to the PLC AI card (i think the signal is Analog), if there is an alarm signal the ESD system will shutdown the power or act to prevent any explosion etc.. i think its done that why but i am not sure.
@asadiqbal87
@asadiqbal87 3 жыл бұрын
another interesting video thanks real pars
@realpars
@realpars 3 жыл бұрын
Glad you enjoyed it! Happy learning
@fitz83
@fitz83 3 жыл бұрын
You mentioned at the start, that the video would show how to DESIGN a circuit which is intrinsically safe? Is this video demonstrating the LOOP concept (follow the manufacturer certification exactly) and ignores the ENTITY circuit calculations? What about the requirements for the circuit calculation, the entity parameters, cable capacitance and inductance? The number of times I’ve had near misses from sub contractors, mistakenly thinking, that when they pick a barrier which will power a device in the field also means it’s safe for the hazardous area is beyond frustrating (at times has lead to follow up action with their employer when competency is an issue). Also, would it not have been easier just to say the barrier must be installed in a safe area rather than give a specific example of a purged panel which achieves this?
@realpars
@realpars 3 жыл бұрын
@fitz83 Our short videos 9n KZbin are meant to introduce viewers to concepts used in the automation industry. Entity circuit calculations are quite a bit more involved than what our short videos can cover. And yes, in hindsight, placing the panel in a GP area would have simplified the discussion.
@bagsnwa6243
@bagsnwa6243 6 ай бұрын
Thanks for the information
@realpars
@realpars 6 ай бұрын
Our pleasure!
@adhamshorafa5338
@adhamshorafa5338 3 жыл бұрын
i always isolate the inputs and outputs between the panel and the field
@استادبرق-د8ب
@استادبرق-د8ب 3 жыл бұрын
Hello What beautiful animations! What software do you use to make these animations? Thank you @RealPars
@realpars
@realpars 3 жыл бұрын
Thank you! I am actually not sure, as the animations are created by our graphic and animation department.
@ohnanawhatsmyname3281
@ohnanawhatsmyname3281 3 жыл бұрын
Whats the difference between Ex d and Ex i? What are the applications? Also all barriers will need a photo eye?
@realpars
@realpars 3 жыл бұрын
A simplified answer is that Ex-ia sensors are classified as Category 1G/1D equipment, for installation in Zone 0, 1, or 2 and 20, 21, and 22 areas. Ex-d sensors are classified as Category 2G equipment, for installation in Zone 1 or 2 and 21 or 22 areas. Ex-ia sensors (such as a tuning fork level switch) can be installed in a tank with hazardous material , whereas an Ex-d sensor cannot be installed in that location.
@docteresamo703
@docteresamo703 3 жыл бұрын
Another interesting video on safety. Is Siemens ET 200iSP better to use in the field as DP compared with the inc. safety barriers?
@realpars
@realpars 3 жыл бұрын
The ET200iSP I/O cards have IS barriers built into the I/O card. It is a matter of convenience and cost to use the ET200iSP system versus a standard PLC I/O card with external IS barriers. Remember, that all systems placed into or interfacing with Zone 1, Zone 21, or Class 1 Div 2 or Class 2 Div 2 areas, must be designed for the appropriate level of protection from the field instrument through to the PLC or DCS. Just installing ah IS barrier or ET200iSP system is not alone sufficient to ensure safe operation.
@aminokamad1681
@aminokamad1681 3 жыл бұрын
Highly recommended videos 🔥
@realpars
@realpars 3 жыл бұрын
Thank you, Amino!
@nikolas8741
@nikolas8741 3 жыл бұрын
High quality content ❤️
@realpars
@realpars 3 жыл бұрын
Thank you, Nikolas!
@thesilentgamer4210
@thesilentgamer4210 5 ай бұрын
Hello, I am aware of IS CALCULATION concept. But for one loop only. Like BARRIER to JB to LT. But I am not sure how would be the process for IS like this case. BARRIER to JB to FIT to FE? How is The cable from FIT for FE considered in calculation?
@realpars
@realpars 5 ай бұрын
Thank you for your question! You’ve raised an interesting point. Here are two links that I hope will help clarify the calculations for the cable from JB to FIT or FE devices. www.extech.co.za/wp-content/uploads/How-to-calculate-an-IS-loop-approval-Extech.pdf www.icetoolkit.com/IntrinsicSafetyCalculator If you need further assistance or have any other questions, please don't hesitate to reach out.
@gamelover2594
@gamelover2594 Жыл бұрын
so for 4-20 mA we can use a zenner barier and for discrete signals we can use isolated barier? Thank you!
@realpars
@realpars Жыл бұрын
Hello GameLover! Thank you for your question! Unfortunately, I can’t fully assist as it is not in the contents of our video, as we discuss in Intrinsic safe example 1. But it is a valid question. To help you with your question, here is a head start. Here are 2 links to manufacturers that might be able to help you with these devices you are asking about. 0-10v, 4-20ma intrinsic safety barrier Zener barrier explosion-proof safety www.alibaba.com/product-detail/0-10v-4-20ma-intrinsic-safety_62468731323.html www.pepperl-fuchs.com/usa/en/classid_14.htm Signal Converters - Intrinsic Safety Barriers Happy learning from RealPars!
@jesusmanuellevinsonrondon5107
@jesusmanuellevinsonrondon5107 3 жыл бұрын
What about intrinsic safety for wireless loops? Does the receiver has to comply with IS regulations too?
@realpars
@realpars 3 жыл бұрын
The short answer to your question is YES. Every part of the "circuit" must be analyzed to insure that the maximum radiated energy does not exceed the threshold for IS installations. A good summary can be found at: www.controlglobal.com/articles/2019/how-to-ensure-intrinsic-safety-for-wireless-systems/. Most wireless installations do not exceed the 2W limitation for the most stringent Group IIC environments, and when installed properly (in Ex d enclosures, for example), can be used in hazardous areas without modification.
@bitebonumbere1426
@bitebonumbere1426 3 жыл бұрын
Realpars, please what's the difference between this video vis-a-vis IS vs Non-IS cables?
@realpars
@realpars 3 жыл бұрын
Intrinsically safe cables are designed to be UV and weather-resistant and conform to certain ISI standards. Cables that are installed in IS service should have blue jacketing/insulating covering to distinguish the cables from those installed in non-IS circuits. In many cases, the type of connection made in the hazardous area is restricted to eliminate the possibility of arcing (as with quick-disconnect cables).
@bitebonumbere1426
@bitebonumbere1426 3 жыл бұрын
@@realpars Thank you RealPars.
@saltlight4220
@saltlight4220 3 жыл бұрын
Definitely for Electrical control engineering and technicians
@realpars
@realpars 3 жыл бұрын
Thank you!
@TuanNguyen-qi8iq
@TuanNguyen-qi8iq 3 жыл бұрын
Thank you!
@realpars
@realpars 3 жыл бұрын
You're welcome!
@abdessamedghettas7167
@abdessamedghettas7167 Жыл бұрын
Thanks
@realpars
@realpars Жыл бұрын
You're welcome!
@cleversomtoyoda8086
@cleversomtoyoda8086 3 жыл бұрын
Very Nice!
@realpars
@realpars 3 жыл бұрын
Thank you!
@nikhilpatil9231
@nikhilpatil9231 3 жыл бұрын
Sir please make videos on mitsubishi plc
@realpars
@realpars 3 жыл бұрын
Thanks for your topic suggestion, Nikhil!
@shaun1961hodge
@shaun1961hodge 2 жыл бұрын
What happens if the field instrument is not ATEX certified?
@realpars
@realpars 2 жыл бұрын
If an instrument is not ATEX certified, then there is no guarantee that the construction of the instrument and its circuitry will provide the level of protection against flammable hazards that may be required.
@shaun1961hodge
@shaun1961hodge 2 жыл бұрын
@@realpars even if it’s a simple device
@aminokamad1681
@aminokamad1681 3 жыл бұрын
🔥🔥🔥
@abulfazibrahimov1990
@abulfazibrahimov1990 3 жыл бұрын
👍
@jeremyreynolds5497
@jeremyreynolds5497 Жыл бұрын
I wish the video in Arabic would be much easier
@realpars
@realpars Жыл бұрын
Hi Jeremy, Thanks for your comment! We currently only provide our course videos in English, you are always able to turn on the English subtitles as that might make it a bit easier for you.
Circuit Breaker Explained | Working Principle
7:54
RealPars
Рет қаралды 121 М.
Intrinsic Safety
7:43
Thorne & Derrick
Рет қаралды 33 М.
99.9% IMPOSSIBLE
00:24
STORROR
Рет қаралды 31 МЛН
coco在求救? #小丑 #天使 #shorts
00:29
好人小丑
Рет қаралды 120 МЛН
What is a Safety Instrumented System?
15:46
RealPars
Рет қаралды 263 М.
Thermocouple Explained | Working Principles
7:51
RealPars
Рет қаралды 160 М.
What is HART Protocol?
17:01
RealPars
Рет қаралды 1 МЛН
Intrinsic Safety
7:43
Hazcon
Рет қаралды 16 М.
Idle Hands & A Tormek!
29:57
This Old Tony
Рет қаралды 286 М.
What is the Difference Between PLC and DCS?
11:23
RealPars
Рет қаралды 1,3 МЛН
99.9% IMPOSSIBLE
00:24
STORROR
Рет қаралды 31 МЛН