HVACR: Follow up call on Walk In Cooler Wired Incorrectly.

  Рет қаралды 9,791

Rookie Refrigeration

Rookie Refrigeration

Күн бұрын

Пікірлер: 65
@jjjames5089
@jjjames5089 4 жыл бұрын
Not enough va what a great teaching moment, it just proves what i teach constantly... As a refrigeration tech, you must be an electrician as well great job dude.
@ralphgiampietro85
@ralphgiampietro85 4 жыл бұрын
Your vids are all so good👍 In a case like that I would have told them to have an electrician give me the wires I needed I will terminate them later also those fuses are the wrong fuses for 208 system On the defrost contact And correct me if I'm wrong you have the load of the defrost heater going through the heater safety Least I think that I understand that's a warranty job but you're the last guy there no one will remember the good you attemped to do when something goes wrong ....am 40 yrs in pal know this by heart like i said excellent vid
@brandonprice3927
@brandonprice3927 4 жыл бұрын
Learn something new every day... Can’t help but laugh at some people’s mistakes.
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
Lol. Thanks bud.
@OcRefrig
@OcRefrig 5 жыл бұрын
That's a Dangerous unit to Work on ! When u Shut Off the service Disconnect and You Still Have 208 High current inside the Panel ! Illegal as Hell too ! at a Minimum the unit Needs a Seperate Service disconnect For the 208 volt circuit. and Labeled accordingly ! To Make it Legal The Unit Panel Must Be seperated into 2 Voltages. a 480 panel & a 208 supplied Panel From That 208 circuit. someones Gonna Get Killed or injured with that setup. Bad news there.
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
Yup. Exactly. We labeled the disconnect warning the next technician.
@OcRefrig
@OcRefrig 5 жыл бұрын
is there a service disconnect to shut down the 208 coming in for fans and heaters ?
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
@@OcRefrig not at the condensing unit. Which is stupid.
@OcRefrig
@OcRefrig 5 жыл бұрын
time to put one in. one of those cheapo residential disconnects would work. it might save your butt. u need to be able to service it.
@OcRefrig
@OcRefrig 5 жыл бұрын
it would also tell everybody - whats going on when they see the second disconnect. everybody would say to themselves - Hmmm whats going on here.
@Georges3DPrinters
@Georges3DPrinters 3 жыл бұрын
8:49 First issue I see those are 40 amp fuses and those wires not going to be rated 40 amps, second thing I see is you could have eliminated that 440 Transformer and use the control voltage from downstairs but you would have had to change the heater wires to correct gauge as well as correct the rest of the circuit to match schematics. However the path you took was much cheaper the more cost-effective for the customer. Cost of copper at that length, plus the conduit is too small. I am wondering what full current load is on heaters.
@Georges3DPrinters
@Georges3DPrinters 3 жыл бұрын
Good video
@andrewedis9907
@andrewedis9907 3 жыл бұрын
Control circuit in a control circuit controlled by a different control circuit. Genius 😉
@davidharmon8745
@davidharmon8745 4 жыл бұрын
Good job .you are no Rookie. You know what your doing.lol keep videos coming.
@colingilland3454
@colingilland3454 4 жыл бұрын
The jobs that keep you on your toes! I guess if it was easy it would be boring👍
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
Lol. Very true. Thanks for watching bud
@mdwightj
@mdwightj 4 жыл бұрын
In this case I would find the source of the secondary power source and disconnect it. your lucky you didn't get lit up on that late night call, it's dangerous. I would set it up for time off defrost 30-45 mins and fans on constantly. Not sure why they needed a 480 v service to begin with...
@patrickjholguin4447
@patrickjholguin4447 4 жыл бұрын
mdwightj ...I concur!
@Kilroy238_
@Kilroy238_ 4 жыл бұрын
Okay I am moving just past the rookie stage but still way below you so I love your video very informative. Electrical is one of my weaknesses so I love videos like this so I've got one question that has me a bit confused. When you were looking at the wiring diagrams I noticed that you were using the one that stated it was for no evaporator contactor nor heating contactor in the condensing but on the the diagram listed on the far left is one for a unit with heating and fan contactors in the condensing unit. They still wired up things wrong bypassing the safeties but it looks like that's what the installers first started to go by because on that diagram you can see that h1 and H2 and F1 and F2 are wired up directly. Why wouldn't you go by that one or am I missing something?
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
To be honest, I could have used the one for the contactors. You are correct with that. But I honestly just went from the top of my head and wired it the best way I knew how with how it was already wired. Half of the stuff you do out in the field are fixing other people’s stuff and rigging stuff up.
@Kilroy238_
@Kilroy238_ 4 жыл бұрын
@@rookierefrigeration4357 yeah you're right about fixing up other people's patchwork. I work in the tourist Mecca of pigeon forge and Gatlinburg and a lot of the refrigeration equipment has been rigged, rigged and patched then re-rigged and patched again. so I completely understand just go in the way you felt best with it I just wanted to make sure I wasn't missing and skipped it purposely for a reason. That being said if the evaporator unit had been wired up using the contractors in the condensing coil method would you have been had to go back and rewire the controls for those two contactors or was that part already set up to function correctly?
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
Bill Benson the fans were already wired right, except for the fan delay. The heaters needed to be wired into the safety. What was really “rewired” was the defrost termination so it could terminate off of temperature.
@John-xg2vj
@John-xg2vj 4 жыл бұрын
This is the kind garbage that hurts people. Without that contactor being labeled as live when condenser disconnect off how many techs would have believed it was off? Ridiculous!
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
Yup. Luckily we didn’t get hit. I always check for power.
@jjjames5089
@jjjames5089 4 жыл бұрын
where is the disconnect for the 208volts for the heaters... This is a very dangerous electrical box.
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
JJ James exactly
@swill1530
@swill1530 4 жыл бұрын
That condensing unit switch board may kill someone someday in the very least it should have a warning sign.
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
S will we did. Warned everyone
@swill1530
@swill1530 4 жыл бұрын
@@rookierefrigeration4357 Great job
@jjjames5089
@jjjames5089 4 жыл бұрын
Certainly should showing there are two separate power sources geez.
@steve19841117
@steve19841117 5 жыл бұрын
i just get confusing as fuck . but still a good job thank you man
@OcRefrig
@OcRefrig 5 жыл бұрын
Wasn't that a Walk in Freezer ? not a cooler.
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
Cooler.
@OcRefrig
@OcRefrig 5 жыл бұрын
alot of crap for a simple cooler. 35 degree cooler or colder than 35 degree ?
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
Exactly. It's just a simple 35° cooler, doesn't need electric defrost, etc. But this is the way the store wants it, so we have to do it as best we can. I'd settle for air defrost and no heaters 🤣🤣
@OcRefrig
@OcRefrig 5 жыл бұрын
Exactly. me too. use a digital a421. stick sensor in the evap. set digital at 15 degrees with a 25 degree diff and be done with it. Power fans directly off that 208 volt breaker other circuit and be done with it. Air defrost every time it cycles on the stat. easy peasy.
@ralphhalili8511
@ralphhalili8511 5 жыл бұрын
Great video dude
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
Thanks bud. Thank you for watching...
@davidharmon8745
@davidharmon8745 4 жыл бұрын
Looks like Baker Electric has been there.always leaving covers off
@pincheburro956
@pincheburro956 5 жыл бұрын
Nice find.
@johnsmithjr5498
@johnsmithjr5498 4 жыл бұрын
If it is only a cooler why do you even need Electric defrost? Air defrost would work fine.
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
I know. But that’s the way it was. We aint about to go ripping stuff out. 🤷‍♂️
@Aden5742
@Aden5742 5 жыл бұрын
Wow dangerous.. Installed by super tech hahahaha
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
A plus ac, Refrigeration yup. Sometimes I get surprised by installers.
@seanbeach5488
@seanbeach5488 3 жыл бұрын
Almost seems like this equipment was a good match together
@MariosACandRefrigeration
@MariosACandRefrigeration 3 жыл бұрын
the timer and 208 cirquit should be down stairs.at condenser only 460.
@syedbasheer8210
@syedbasheer8210 5 жыл бұрын
🤩
@donnierobertson3088
@donnierobertson3088 4 жыл бұрын
Good
@MRICE-qe4sv
@MRICE-qe4sv 5 жыл бұрын
If you have a 208v circuit why not abandon the transformer for control and just run your control off the 208v. Already have the fan wires and heater wires up to condenser so there’s your 4 wires. Utilize those and rewire. Maybe I’m missing something. None the less good find and made the best of the shit storm u found.
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
That's exactly what we thought about doing. But since it's a new unit under warranty, we didn't want to mess with it too much. So we just did what we did to get it working right. But you are correct. We could have done that easily..
@MRICE-qe4sv
@MRICE-qe4sv 5 жыл бұрын
Rookie Refrigeration you based out of Houston? Believe u said u were. I’m in Houston as well.
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
I'm up in DFW.
@HVACRDR
@HVACRDR 4 жыл бұрын
@@rookierefrigeration4357 Hows hvac in Dallas? Im thinking about moving to either Dallas or Houston from phx az. Im also looking to get into refrigeration. Im currently doing residential and light commercial.
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
There’s too much work and not enough techs. Get on up here
@mrnoodle43
@mrnoodle43 3 жыл бұрын
Take it all out and put back to factory
@christophergonzales1321
@christophergonzales1321 4 жыл бұрын
X terminal
@SombraLocs
@SombraLocs 5 жыл бұрын
How long have you been doing Refrigeration?
@rookierefrigeration4357
@rookierefrigeration4357 5 жыл бұрын
Familia Sanchez HVAC 1 year, 2weeks. Lol
@Jim89240
@Jim89240 4 жыл бұрын
Why do people do this shit. Then youre the one who has to clean it up at 8 o clock at night.
HVAC Refrigeration:  Walk In Cooler down and wired incorrectly.
19:14
Rookie Refrigeration
Рет қаралды 31 М.
Refrigeration Unit down, multiple offender!
15:25
Rookie Refrigeration
Рет қаралды 9 М.
兔子姐姐最终逃走了吗?#小丑#兔子警官#家庭
00:58
小蚂蚁和小宇宙
Рет қаралды 12 МЛН
🕊️Valera🕊️
00:34
DO$HIK
Рет қаралды 15 МЛН
Ouch.. 🤕⚽️
00:25
Celine Dept
Рет қаралды 27 МЛН
Когда отец одевает ребёнка @JaySharon
00:16
История одного вокалиста
Рет қаралды 16 МЛН
Basic walk in box control wiring
12:30
Nor-Cal Refrigeration & H.V.A.C
Рет қаралды 59 М.
HVAC REFRIGERATION:  Scroll compressor will not start!  Walk in Cooler Warm WIC
15:05
HVAC Refrigeration: Walk In Cooler Running Warm,  Erratic Temperatures
19:41
Rookie Refrigeration
Рет қаралды 14 М.
Defrost circuit in a commercial application
11:24
Curious HVAC Guy
Рет қаралды 28 М.
WALK IN FREEZER WITH TOO MUCH FROST
14:52
HVACR VIDEOS
Рет қаралды 465 М.
Walk in Freezer service call  (electric defrost explained)
27:37
HVACR VIDEOS
Рет қаралды 246 М.
Walk in cooler not cooling
13:23
Curious HVAC Guy
Рет қаралды 23 М.
HVAC REFRIGERATION LIFE:  On call Service Calls Part 2
17:47
Rookie Refrigeration
Рет қаралды 17 М.
兔子姐姐最终逃走了吗?#小丑#兔子警官#家庭
00:58
小蚂蚁和小宇宙
Рет қаралды 12 МЛН