Hi bro I'm from Bangladesh working HVAC VRF System Troubleshooting and maintenance nice your video
@allanperez80553 ай бұрын
Sir you should show on video how to charge refrigerant and manifold connection not show clear
@fanielabuschagne89882 ай бұрын
Not checking the cause of compressor failure ? Acid test , oil return ? Cleaning or flushing condensers ? I never used existing gas when have burnouts. Don't think those two new compressors is going to last very long.
@somerandomhuman12347 ай бұрын
I am from INDIA, just curious to know how these systems work. Good work. Kudos
@craigladewig31585 ай бұрын
Old compressor needs to be weighed and referenced to new compressor and difference in weight = amount of oil to be added to system as per Samsung technical guide on replacing compressor. I would have checked inverter board with inverter checker + checked oil for acid level . Did you top up system from R410 cylinder after recharging system with recovered refrigerant ?
@Infowarrior-17767 ай бұрын
Thanks for the video! I’m in HVAC school and it’s hard to imagine that’ll I’ll be as sharp as you are but that’s my goal lol I’m in crossville, TN. Your content is very helpful!
@dcrickerson76117 ай бұрын
Really nice video! You're a great technician and teacher. Retired industrial electrician here, Tampa Florida area.
@TaddyDigest7 ай бұрын
Thank you, brother. I'm glad you enjoyed the video I'll be in Sarasota, Florida next month. I am ready
@bmillwood66667 ай бұрын
Oh the life of a Samsung compressor replacement and then you have the awful discharge temp sensor failure. I also, saw the distain in your face when you found two bad compressors. FYI I learned you must check for oil in the old compressors and also weigh old compressors versus new compressors. Oh the Samsung Fun never ends. Great video!!
@TaddyDigest7 ай бұрын
You saw that I was pretty upset Glad to get it fixed though
@taqmeemalam88526 ай бұрын
@@TaddyDigest inverter PCB
@taqmeemalam88526 ай бұрын
@@TaddyDigestSumsung DVM 12 hp
@yesidperez20297 ай бұрын
Hi Taddy. If the issue was caused by the compressors bieng shorted to ground why did you replace the inverted boards too?. Thank you.
@TaddyDigest7 ай бұрын
I replaced the inverter board to make sure that I don't have any callbacks.
@monisyaseenmughal9714Ай бұрын
Wonderful vidio and very usefull. One question please, Is it any setting to do before to recover of refrigerent??
@TaddyDigestАй бұрын
thanks for watching and to your question I am not sure
@KrisMoreno-uk9to7 ай бұрын
This was a good video nightmare job but good info one been changing capacitors and adding hard starts but the compressor wasn’t grounded yet but bad windings checked with ohmeter
@TonyRodriguez-ok2ix7 ай бұрын
when replacing an inverter compressor , its a wise idea to replace the inverter board.
@ahmaddarwiche74537 ай бұрын
Hello good work But i have a question what is the S NET I'm from London uk thanks
@TaddyDigest7 ай бұрын
The s net converter box is a tool that is utilized to convert the transmission signal into a readable signal by the s. Net software
@hituw2x47 ай бұрын
The resistance readings were in megahohms, see the uppercase "M" displayed on the screen. So if it says 24.1, that's 24,100,000 ohms. Those compressors were fine.
@tonydelgrego29067 ай бұрын
Do you always replace the inverter boards when the compressor is grounded. I’m from Connecticut
@JoseAcosta-qi2gpАй бұрын
I'm just curious both compressors were grounded, but you didn't replace the refrigerant or install any driers. Is that OK
@pcsof337 ай бұрын
Taddy good work but i didn't see you doing a flushing process for the system because it's very important before installing new compressor.
@USA-GreedyMenOfNoIntegrity7 ай бұрын
Take a guess how many of my systems got flushed in 27 years. Zero. I’ve had one compressor fail again 5 yrs later. Suction drier if it can fit, liquid drier, new refrigerant if needed, acid neutralizer if needed, new contactor and capacitor if needed.
@musakavalci94705 ай бұрын
Nicely done and beautifully explained. 👌🏼
@TaddyDigest5 ай бұрын
Thanks a lot 😊
@Eric-ot6sn7 ай бұрын
Had that same issue thought it was the inverter boards, but it turned out to be the compressors, and also what tool do you have to have to hook up to the Samsung units?
@TaddyDigest7 ай бұрын
snet converter box
@ronchambers97627 ай бұрын
Rocket 1 to earth. Could you check the output serial port 3. It is really warm in here. Command center to rocket 1. It appears we have lost both boostets and the computer control boards are toast. We are ordering those now. Stand by Rocket 1. Its air conditioning for goodness sakes.
@joshuasmith9737 ай бұрын
I just replaced two compressors on my first vrf's. LG
@jixia6767 ай бұрын
Hi, Teddy. Do you think 14Volt DC when compressor started to was abnormal? You measured 14vDC on inverter board
@TaddyDigest7 ай бұрын
yes
@AllTattedUp137 ай бұрын
Did u have to go to training thru samsung on them units. Our trade is sure getting complicated lol. Feel bad for all the new guys coming into it. Im glad im at my peak 😂
@TaddyDigest7 ай бұрын
I did do a 2 day training to learn 💪 before ever installing a dvm unit
@TonyRodriguez-ok2ix7 ай бұрын
why do u have to use thermal paste?
@TaddyDigest7 ай бұрын
I use it so that the board does not overheat
@joshuasmith9737 ай бұрын
VRF Baby!!!!!! Let's go!!!!!!
@Johnny2000k7 ай бұрын
I have a unit that’s 41 years old and it’s still running. Should I buy a new one cause every one in my family is saying all the new stuff is garbage, is that true?
@USA-GreedyMenOfNoIntegrity7 ай бұрын
Run it until it breaks. Buy the simplest unit you can from the best contractor.
@JesseDoesHVAC7 ай бұрын
Or consider the fact that 40 years of innovation means waaayyy better efficiency and better refrigerants, you could be pleasantly surprised at the power savings
@AllTattedUp137 ай бұрын
Been doing hvac going on almost 30yrs. ABSOLUTELY the new stuff is garbage. And it's going to get worse now that the government is sticking their nose in the hvac trades.
@craigladewig31585 ай бұрын
@@JesseDoesHVAC For domestic , what would the run time on an inverter system be to recover the cost of replacing an inverter PCB ? And if a inverter system is running full load most of the time, its not much more efficient than a non inverter system.
@فيصلالطويرقي-ت7ج7 ай бұрын
Why you change the card if issue is compressor
@TaddyDigest7 ай бұрын
I ordered the inverter boards first. The compressors did not check short to ground. So I already had the boards Might as well replace them
@andyreyes64647 ай бұрын
Great video, vrf rocks
@universalservicetechust35787 ай бұрын
Sooo much funner when you understand what you’re doing 😂
@TaddyDigest7 ай бұрын
Yes sir I agree brother
@hurcklynbrown26307 ай бұрын
Great job, i learn a lot
@sleepdoctor34337 ай бұрын
Wow, I have soooo much to learn
@AbdulSattar-bw1lf6 ай бұрын
Thanks sir 🎉very helpful ❤
@เกิดทรัพย์เพ็ชรตะกั่ว2 ай бұрын
I from Thailand I want snet pro2 You sell?
@TaddyDigest2 ай бұрын
I do not sell go to waveshare and order similar box
@danpresson7 ай бұрын
Awesome video your so smart
@فيصلالطويرقي-ت7ج7 ай бұрын
We need video know how PCB is not work properly
@theanh4373Ай бұрын
thank you
@TaddyDigestАй бұрын
You're welcome.Thank you so much for watching
@theanh4373Ай бұрын
@ present I have a case, U201,E464 and i changed inv pcb of sub1 for inv pcb of Main after that display U200,E364, so is inv pcb of sub1 fault?
@MrEzhilarasan7 ай бұрын
nice
@TonyRodriguez-ok2ix7 ай бұрын
good show
@TaddyDigest7 ай бұрын
Thanks!
@jjbsrefairconservices31003 ай бұрын
Very good video thank you for sharing I request for next video to clean evaporator and condenser @@TaddyDigest
@isaelcortes39536 ай бұрын
Awesome video!
@TaddyDigest6 ай бұрын
Thanks!
@djkingpersia7 ай бұрын
Repair is different than installation. These units looks like you can get to the boards easily versus the residential units which are absolute nightmare. On the other hand I think you have worked on these units several times to include several major repairs now you have two compressors down I'm pretty sure the owner is like WTF is going on this thing isn't worth a shit. Nothing beats conventional. On the other hand nothing beats the flexibility of mini split that's if it lasts
@icidro17 ай бұрын
Great video Your Tadness
@TaddyDigest7 ай бұрын
Glad you enjoyed it
@samsungdvm81265 ай бұрын
❤❤❤❤great
@TaddyDigest5 ай бұрын
thanks
@abdullah_q81717 ай бұрын
Most of these vrv vrf break down frequently, and working on them is not easy
@GreyRockOne7 ай бұрын
@giveaway - Thanks Taddy!
@bmillwood66667 ай бұрын
I hate seeing any 400 codes.
@JesseDoesHVAC7 ай бұрын
Samsung? More like Sam-suck! But good for us in the feild, just like our “wonderful” daikin units we get here in Australia 🇦🇺- garbage units of late but great for business Also why does the new compressor look like it came off the back of a truck 😅
@ebfsystem7 ай бұрын
Those units are pure junk
@USA-GreedyMenOfNoIntegrity7 ай бұрын
Pure junk! I had an American standard compressor fail after two months last summer. Puts a dent in your profits, doesn’t it.
@ebfsystem7 ай бұрын
Warranty supposed cover for that?
@USA-GreedyMenOfNoIntegrity7 ай бұрын
@@ebfsystem they give you the part after 1-3 weeks and may cover shipping. That’s it. Add $750 for each 1 ton portable cooling unit, refrigerant, vacuum pump oil, torch supplies, two trips out, 8 hrs labor, disappointed customer.