Excellent Job...need more sessions on CEA guidelines, Power System protection, power system modelling , testing and commissioning of substation and Power System stability’s
@PowerProjects_etap4 жыл бұрын
Will plan shortly
@anandmpmurthi4 жыл бұрын
As usual, Broad way of teaching, Seeing everyone electrical nerves by teaching. Rocks!! Pls use Tags in title such as #Powersystem #shortcircuitstudies #Powerprojects #Electrical that can find this video easily who are searching related topics.
@PowerProjects_etap4 жыл бұрын
Thanks Anand.. Its the first online session.... Long way to go....
@anandmpmurthi4 жыл бұрын
100% Sure
@jawadamjad934 жыл бұрын
Excellent Session and very knowledgeable content. Great to refresh our knowledge.
@PowerProjects_etap4 жыл бұрын
Glad you liked it
@Om.Dandale4 жыл бұрын
Sir Hats off to you!!!! What a informative webinar it is!
@PowerProjects_etap4 жыл бұрын
Thanks a ton
@shaikato4 жыл бұрын
Excellent content and would like get more topics on power system studies. It's really appreciated.
@PowerProjects_etap4 жыл бұрын
More to come!
@singhvikas4994 Жыл бұрын
Very Informative & Awesome Explanation.i have Been following on every platform.Kindly upload latest webinars on the channels.
@tamizhmurugesan81524 жыл бұрын
Very Informative & Awesome Explanation, Thanks for the video session sir.
@PowerProjects_etap4 жыл бұрын
Most welcome
@priyaarun74024 жыл бұрын
Thank you for this very informative session sir👏
@PowerProjects_etap4 жыл бұрын
Always welcome
@ganpathji4 жыл бұрын
Congratulations. Long awaited for this session. Keep rocking.
@PowerProjects_etap4 жыл бұрын
Thanks a lot
@nithinpinto18024 жыл бұрын
Thank you. Very informative.
@sanjeevrana83174 жыл бұрын
Impeccably Excellent, similarly make video on DC fault calculations.
@PowerProjects_etap4 жыл бұрын
Thanks, will do!
@ManojIllangasooriya2 ай бұрын
Love it
@gomathimadeswari88623 ай бұрын
Very Good session
@gopinathsundaramoorthy81184 жыл бұрын
Very informative and intuitive towards the short circuit studiesof power system....
@PowerProjects_etap4 жыл бұрын
Thanks a lot Gopinath
@varunrisbud2483 жыл бұрын
Amazing session, please upload more! or can you send recorded session by email?
@PowerProjects_etap3 жыл бұрын
We are starting AskSelva Session from 22nd November 2020 again. You can stay tuned in the channel.
@sanjeevrana83174 жыл бұрын
Impeccably Excellent, also series fault, relay co-ordination charts
@PowerProjects_etap4 жыл бұрын
Thanks for listening
@RajnishKumar-hr5ow4 жыл бұрын
Excellent Session
@PowerProjects_etap4 жыл бұрын
Thanks for listening
@srikanth028225 күн бұрын
How to decide short circuit current 31.5 kA or 40 kA for 132kv substation. What inputs are needed for calculation.
@mizanalaqaid17764 жыл бұрын
Thank you sir, great content
@PowerProjects_etap4 жыл бұрын
Welcome!
@musaibshaikh50754 жыл бұрын
Wonderful explained
@PowerProjects_etap4 жыл бұрын
Glad it was helpful!
@mprathik48854 жыл бұрын
Congratulations sir good effort 👌. BE completed year typed wrongly 20006 instead 2006.
@PowerProjects_etap4 жыл бұрын
Thanks a for correction. Updated for upcoming sessions
@tanzeemkhan852 ай бұрын
❤
@charinath54453 жыл бұрын
Can you please confirm my understanding that faults "Close to Generator" & " Far from Generator" would be decided by the ETAP software as an inbuilt function of ETAP?
@PowerProjects_etap3 жыл бұрын
All equipments in Power system offers constant impedance during the fault except generator which has time varying impedance (Xd", Xd' & Xd). If you provide correct values of these parameters along with their time constant Td0" & Td0' you will get the proper results in all simulation softwares
@charinath54453 жыл бұрын
In my short circuit report from ETAP, Making capacity of device > ip (calculated) Ib sym of device > Ib sym (calculated) Ib asym of device > Ib asym (calculated) Idc < Idc (calculated) -- shows alert I think since the calculated "Ib asym" includes the decaying dc component, I can ignore the device Idc being less than Idc(calculated) or Should I replace the breaker with higher rating or ask the manufacturer to provide higher time constant breakers
@PowerProjects_etap3 жыл бұрын
You need to look at the DC Breaking capacity of the breaker at the instant of breaker opening (Not at t=0) Still if DC current is more either you have to replace the breaker or intentionally delay the breaker for one or two cycles.
@pelango36584 жыл бұрын
use full information, nice explanation...
@PowerProjects_etap4 жыл бұрын
Thanks a lot
@charinath54453 жыл бұрын
Which method of calculating R/X ratio is typically used for short circuit calculations as per IEC 60909? Method A /Method B/ Method C?
@PowerProjects_etap3 жыл бұрын
Refer IEC 60909. Will discuss more in Upcomg #AskSelva
@kevinpatel60274 жыл бұрын
Where i can get a participation cetificate of this online session ?
@PowerProjects_etap4 жыл бұрын
There will not be any participant certificate for KZbin sessions
@ezhilaniruthan4 жыл бұрын
Great content...
@PowerProjects_etap4 жыл бұрын
Thanks a lot Ezhil
@sudhirsharma34352 жыл бұрын
Is there any paper or journal which clearly differentiate between IEEE and IEC standard for Short Circuit Study of Power system? So, someone who is working with ANSI system, these lectures will be more helpful to them as well.
@PowerProjects_etap2 жыл бұрын
ieeexplore.ieee.org/document/222435
@manojkumarmahto98054 жыл бұрын
In 33 kV or some other voltage level.. Main bus is quad moose acsr and transfer bus is twin moose acsr.. Why.. How we decide which one is quad or twin....
@PowerProjects_etap4 жыл бұрын
Can you share the details to skumar@powerprojectsindia.com. We will check and revert
@muthuvelganesh65544 жыл бұрын
System study deals with internal arc withstand current of switchgear or how to design internal arc withstand current of switchgear?
@PowerProjects_etap4 жыл бұрын
We will schedule a session on Arc flash shortly
@muthuvelganesh65544 жыл бұрын
@@PowerProjects_etap I am not asking about arc flash study. I am asking about internal arc compliance requirement it is stated something in IEC 62271-200
@sudampatra5608 Жыл бұрын
How to choose IDC for 220 kv
@PowerProjects_etap Жыл бұрын
While performing Short circuit studies, you will get Ibsym Idc Ibasym ip Choose the breaker capacity in such a way that the breaker is capable of interrupting Idc
@swarupnayak77373 жыл бұрын
Sir, If there is a Star-Star Transformer with both side NGR connected. Will an earth fault at say LV side be affected by HV side NGR.
@PowerProjects_etap3 жыл бұрын
Depends on the NGR Value. If the NGR on HV side limits the fault current less than the current limited by LV NGR then it may have an impact. In general we may not have such scenario in real time.