I HAVE a question about the choosen telegram 3 . as i read from siemens help the telegram 3 doesnt support the IRT it only support RT but why you choose the isonchrounous mode in the paramaeters ? i think you should select telegram 5 or 105
@mohammedrezk80722 жыл бұрын
So great videos tutorial,keep it up.
@adelcarrillo3552 Жыл бұрын
Hello, I appreciate a lot you rvideo. However I have a problem when I try to comissioning since tia portal: however the telegram is not being sent and the error on servodrive is: F8501: PROFIdrive: Time exceeded setpoint Reaction: OFF3 Confirmation: IMMEDIATELY Receiving PROFINET setpoints has been interrupted. • The PROFINET connection has been interrupted. • Controller disconnected. • Controller set to state STOP. • PROFINET defective. Restore the PROFINET connection and set the controller to R state. tHE COMM led is okay but RUN led is blinking red. The shyncronous is okay. Do you have Any idea to fix It? Thank you very much.