Sir ganda po ng xplaination nyo sobrang smoth, salute po sayo... may kunting idadagdag lang po ako, dapat dun palang sa f1 & f2 meron ka ng motor contribution po.
@emmanuellimjoco47095 ай бұрын
The best detailed computation ever watch. Galing mo Sir God bless and thanks for sharing.
@RandyAmorchannel5 ай бұрын
Salamat sir
@justinlanielbaniqued250011 ай бұрын
Thank you Sir! Dami ko na pong napanuod abt short ciruit analysis diko ma gets yung iba pero yung inyo na gets ko agad hehe. Na lilito po kasi ako nung una paano kunin KAIC rating ng mga CB, salamat Sir sa learnings po! God Bless po.
@RandyAmorchannel11 ай бұрын
Salamat sir for watching my video
@justinlanielbaniqued250010 ай бұрын
Sir may question po ako, yung 500kva 3phase transformer po ba single phase pole mounted transformer na naka banking lang po ba na consist of 167kva each rating ganon po? Parang sinum up lang Sir? Thank you po. @@RandyAmorchannel
@banjomirandilla39179 ай бұрын
Thank you sir clear and concise
@RandyAmorchannel9 ай бұрын
Thank you sir. God bless
@raphaelcacanog73 Жыл бұрын
nakakatulong po ito maraming salamat po
@RandyAmorchannel Жыл бұрын
You're welcome sir
@CharlieDelaCruz-ki7cx2 ай бұрын
Sir Saan nyo nakuha ang Table 4. C for Conductor?
@ravenvillanueva7816 Жыл бұрын
sir pano po pag from center meter ang pag babasehan? pwede ba mag based sa 80percent ng kaic kung saan naka tap yung fault?
@RandyAmorchannel Жыл бұрын
Pag point-to-point method ang gamit mo kailangan mong mag simula sa source papunta sa point of fault kasi may factors na magdedepende sa fault current upstream ng fault point na gusto mong kunin.
@minzenbae6899Ай бұрын
boss saan po naggaling yung 100 sa formula mo and saang book or page yung basis mo na Table 4.C? thankyou po
@RaelSeanLinda2 ай бұрын
Constant PO ba Ang 100 sa pag calculate Ng multiplier?
@eduardodangoy9730 Жыл бұрын
sir pwuede maka hingi ng smath solver "worksheet short-circuit calculation" for reference, thanks
@RandyAmorchannel Жыл бұрын
You may download the file from my Facebook Group facebook.com/groups/usapangelektrikalph/files/files
@kamotipstv69805 ай бұрын
sir anung program yang gamit mo?
@DemetrioBautista-r9k5 ай бұрын
Saan po Eng’r. Nanggaling yung Table 4 “C”?
@sherwinguevarra-b5z3 күн бұрын
pag gnamit po ba ung per unit analysis same lng din b mkukuha n short ciruit curret po sa fault 1,2, and 3
@RandyAmorchannel3 күн бұрын
kundi man sakto, malapit ang sagot. Ang problema lang sa pinas hindi pa yata acceptable ng OBO ang ibang pethod bukod sa per unit
@anniehofer41516 ай бұрын
Sir, yung 500KVA sa simula san po sya kinukuha? Gumagawa kasi kami project sa residential house and di ko sure if sa schedule of loads ko ba kukunin yang KVA
@RandyAmorchannel6 ай бұрын
Sa utility po yun sir, kVA rating ng utility transformer
@ouevv Жыл бұрын
Sa value ng n, paano naging 2 sa pt 1? 3phase po diba so bale 3 wires? Medyo nakakalito lang.
@RandyAmorchannel Жыл бұрын
Yung n dun sir is number of parallel runs, in that case, n=2
@jeffreymanalomanalo2682 Жыл бұрын
@@RandyAmorchannelKunwari po 3 na acb galing sa hvsg to lvsg. So times 3? Tama po ba
@RandyAmorchannel Жыл бұрын
@@jeffreymanalomanalo2682 hindi po ganun sir. Yung number of parallel runs of cable po is kung ilang set ng three-phase cables and ginamit, for example kapag nakalagy sa single-line diagram na 2 - 3Cx100mm2 ibig sabihin 2 sets ng three-phase feeder so ang n=2
@emmanuellimjoco47095 ай бұрын
Kung 1 set lang n value is 1. Kung 3 sets ang n value is 3 di po ba?
@gbgb88782 жыл бұрын
It was nice video. Kindly give english subtitles.
@RandyAmorchannel2 жыл бұрын
Thanks for the comment. I will try to put english subtitles to it.
@jonasfuertes5895 Жыл бұрын
Assuming na running yung ckt at nagkaroon ng Fault sa Point 3, hind po ba magkakaroon ng contribution sa Fault yung motor loads? Thanks
@RandyAmorchannel Жыл бұрын
Yung point-to-point method, sabi ay kapag hindi significant yung motor contribution at pwede nang hindi isama. Sa dulo ng video pinakita ko yung fault currents at different points of the system with and without motor contribution. Salamat sir. God bless
@Jepz_ Жыл бұрын
Engr Ano gamit mo na software sa presentation 😁.. galing..
@RandyAmorchannel Жыл бұрын
Smath Solver sir, may video ako kung paano mag download at gamitin kzbin.info/aero/PLfGtZkfoxIwyw55mf2kqRSNfz86rOLRuK
@Jepz_ Жыл бұрын
Nakita ko Engr sa suggestion.. salamaat ng marami.
@erickmanangan4803 Жыл бұрын
Hello Engr. Nice video. Saan yan nilalagay A3 or A4 pag iaatached na at ipapasa for electrical permit? Thank you
@RandyAmorchannel Жыл бұрын
Kasama po yan sa analysis na ginagawa at pinipirmahan ng PEE. Normally separate sheet sa A4
@alvinnobitski2159 Жыл бұрын
Sir tanong ko lang po, kapag po ang fault point po ay nasa Main distribution Panel, ang Length (L) po ba na gagamitin sa formula ay from MDP to service point lang o from MDP to transformer?
@RandyAmorchannel Жыл бұрын
Consider mo yung length hanggang transformer kasi may contribution yung transformer sa fault current
@marclestercarlos661911 ай бұрын
Kelangan ba iconvert to "feet" yung length ng cable?
@RandyAmorchannel11 ай бұрын
Yes po sir kailangan i-convert sa feet kasi yun po ang nasa formula
@eap0226 Жыл бұрын
Paano po kunin yong n, number of parallel rods?
@RandyAmorchannel Жыл бұрын
Sir sa design po yun makikita normally naka indicate sa single-line diagram
@jonasfuertes5895 Жыл бұрын
2nd is, di ba natin gagamitin yung actual voltage doon sa computation assuming na may voltage drop na pagdating doon sa Location ng Fault? Thanks
@RandyAmorchannel Жыл бұрын
Sir with regards to voltage used, ang voltage drop sa buong system ay limited to 3% from source to last point as per standards, so negligible na yung voltage drop. Kung gusto talaga nating gamitin yung actual voltage sa point of fault, pwede din naman pero mag calculate ka pa ng voltage at every point. Salamat sir and God bless.
@rommelbondoc11217 ай бұрын
Engr anong program/app yun gamit mo na auto nagcompute after mo magtype?
@RandyAmorchannel7 ай бұрын
Smath Studio sir. May tutorials din ako tungkol jan kzbin.info/aero/PLfGtZkfoxIwyw55mf2kqRSNfz86rOLRuK
@rommelbondoc11217 ай бұрын
@@RandyAmorchannel salamat
@christophermillan6310 Жыл бұрын
good day po, constant po ba ang percentage ng impedance, or naka depende pomsa size ng transformer?at kung oo po,san po pwede macheck ang mga impedances na to?
@RandyAmorchannel Жыл бұрын
Yung impedance ng transformer varies depende sa capacity at sa manufacturer din. Makikita naten ang % impedance ng transformer sa nameplate. Salamat sir question mo sir. God bless
@marvin08250010 ай бұрын
@@RandyAmorchannel Sir kung walang nakaindicate na impedance sa nameplate, ano ang gagamitin na impedance?
@RandyAmorchannel10 ай бұрын
@@marvin082500 standard nameplate ng transformer shall always include impedance. Pero kung di available for example eh nabura na or nawala yung nameplate, etc at wala kang sources ng information tungkol sa impedance, pwede kang mag refer sa IEEE std 142 or yung Gray Book. May table dun na Approximate Impedance Values.
@marvin08250010 ай бұрын
Thank you Sir @@RandyAmorchannel
@pochitaiitft10 ай бұрын
Sir anong software ginagamit nyo
@RandyAmorchannel10 ай бұрын
Gamit ko Smath Studio
@Dragon26-Tiger31 Жыл бұрын
sa calculation ng M1, 100 divide by Z times 0.9, san nangaling yung 100?
@RandyAmorchannel Жыл бұрын
constant po yun sa formula sir.
@Dragon26-Tiger31 Жыл бұрын
ano ang formula?@@RandyAmorchannel
@RandyAmorchannel Жыл бұрын
@@Dragon26-Tiger31 sir nasa video po ang formula M=100/(%z x 0.9)
@Botchukoy2 жыл бұрын
sir, anung gamit mong app sa presentation?
@RandyAmorchannel2 жыл бұрын
Smath Solver (formerly known as Smath Studio) sir gamit ko jan. Free alrernative to Mathcad
@arielgallego88036 ай бұрын
Sir, may video ka ba kung genset naman ang power source?
@RandyAmorchannel6 ай бұрын
wala pa sir, try ko gawan next time. Thanks
@arielgallego88036 ай бұрын
@@RandyAmorchannel Salamat sir!
@cas49713 Жыл бұрын
Good day sir, accepted na ba ang poin-to-point method ng Bussman sa PEE exam or sa detail engineering? Thank you in advance.
@RandyAmorchannel Жыл бұрын
Ang alam ko PU method ang accepted ng OBO for permit. Dapat na siguro mag update ng OBO sa acceptable method of calculation ng SC to include other methods. Pero magagamit mo tong methid na to for quick calculation para sa KAIC rating ng equipment
@jeffreymanalomanalo2682 Жыл бұрын
Hello sir. Saan po nakuha Yun 100
@RandyAmorchannel Жыл бұрын
Yung 100 sir ay kasama sa formula yun
@leovincalubag479 Жыл бұрын
anong C value and dapat gamitin pag Single Phase.
@ImmortalShiro Жыл бұрын
Same lang din. Naka dipende naman po kasi yung C values mainly sa wire size, then kung magnetic or nonmagnetic yung conduit, tsaka yung voltage.
@RandyAmorchannel Жыл бұрын
Walang separate value for single phase. Magkaiba lang ng value for single conductors and multi-conductor cables or kung busway
@OP-OP999 Жыл бұрын
Hello Sir. Blurry po ang given. Kindly provide clearer video. 🙏🙏🙏
@RandyAmorchannel Жыл бұрын
Malinaw naman po yung video.
@OP-OP999 Жыл бұрын
@@RandyAmorchannel Hello po Sir Randy. Blurry sa cellphone ko sir. But clear sa laptop. Maraming salamat po sir.
@OP-OP999 Жыл бұрын
@@RandyAmorchannel Hello Sir Randy, tanong ko lng po kasi nalilitu po ako. yung impedance po ng transformer is 5%. Yung tanong ko is M1=100/(5)(0.9), since 5% po yan sir hindi po ba dapat 0.05 ang gagamitin natin Sir? magiging M1=100/(0.05)(0.9)?
@RandyAmorchannel Жыл бұрын
@@OP-OP999 kung ano po yung naka indicate na %Z ayun po yung gagamitin hindi na po gagawing decimal
@OP-OP999 Жыл бұрын
@@RandyAmorchannel got it po sir. Maraming salamat po at binigyan niyo po ako nang kalinawagan.
@dhardstv9818 Жыл бұрын
boss panu mo ginawa sa diagram?panu ininsert
@RandyAmorchannel Жыл бұрын
Ginawa ko muna boss sa powerpoint then copy & paste
@jeffreymanalomanalo2682 Жыл бұрын
Sir sana po naituro mo din yun breaker na gagamitin para sa na compute na fault
@RandyAmorchannel Жыл бұрын
sir pagdating sa breaker na gagamitin base sa na calculate ng fault current, ang rule lang naman dun ay kunin mo yung breaker na may kAIC rating na equal or mas mataas sa calculated fault current.
@jeffreymanalomanalo2682 Жыл бұрын
@@RandyAmorchannel thanks
@incoyjoshuagabriell.418410 ай бұрын
san po nangaling yung %z=5 thanks po
@RandyAmorchannel10 ай бұрын
Sir yung 5% impedance po ay given sa problem, pero sa actual na calculation kukunin nyo po ang impedance sa nameplate ng transformer. Salamat po sa panonood sa video. God Bless.
@bloomberg48656 ай бұрын
Bkt s pag compute mo ng isc3 hindi mo naconsider ung current contribution ng motor during fault condition. Meron dn yan contribution.