Supplementary Protective Bonding and Touch Voltage

  Рет қаралды 6,476

JPElectric

JPElectric

Күн бұрын

An overview of the testing procedure for supplementary protective bonding.
I also talk about "My' take on touch voltage. Comments on this most welcome, as I find it a complex issue.

Пікірлер: 28
@RaxTubeYou
@RaxTubeYou 5 ай бұрын
Wow and wowsers, the BEST detailed explanation and I've seen 10's of tutorials. Thank you so much and please keep up this good work!
@JPElectric
@JPElectric 4 ай бұрын
Thanks RaxTubeYou, really appreciate your kind comment. Yes plan to keep on doing videos, as long as people find them useful
@cfgman1
@cfgman1 4 ай бұрын
This is the only video which clearly makes the distinction between the purpose of CPC and PBC respectively - one limits the duration of the fault and the other limits the level of the fault. This is a very important concept which is quite difficult to grasp but once understood makes sense. I must admit these videos are impressive - I suspect you have taught this subject ...if not you should !
@JPElectric
@JPElectric 3 ай бұрын
Thank you cfgman1, No not a teacher, just an electrician, trying to pass stuff on.
@2002yeunglau
@2002yeunglau 23 күн бұрын
Bro thank you so much the video is very detailed and I really appreciate your work please make more videos
@euanwylie8046
@euanwylie8046 2 ай бұрын
great explanation and great work, gives me better understanding now it about main bond calc i will see in ur next vid
@RatBikerNotts
@RatBikerNotts 6 ай бұрын
Thanks, finally a clear explanation.
@JPElectric
@JPElectric 5 ай бұрын
Thank you RatBikerNotts
@Weaselspleen75
@Weaselspleen75 5 ай бұрын
Well explained and it’s finally became clear 👍
@JPElectric
@JPElectric 5 ай бұрын
Thanks Weaselspleen75, glad you found it helpful.
@cestemshow
@cestemshow Жыл бұрын
Underrated video, deserves more views. Top job ❤️
@JPElectric
@JPElectric Жыл бұрын
Thanks very much, really appreciate your comment. I have been trying to put a video together for a while on transposing formula. Something I still struggle with. Looking at your channel, you have some great content on that.
@eddie_pegasus_electrical
@eddie_pegasus_electrical Жыл бұрын
Good explanation on Supplementary Protective Bonding and Touch Voltage. Good revision, especially as I don't work in bathrooms and the like. Back in about the late 80s we were involved in a refurbishment of some blocks of flats 12 storeys +, we had to bond the metal window frames throughout each flat. My governor at the time with technical teams argued against it, still had to be done 🤷‍♂🤦‍♂. Thank you. 👊😎👍💙
@alpaycelikel
@alpaycelikel 3 күн бұрын
really informative thanks. i usually check piping system (water and gas), lightning rod and metal building frame of the building, is there anything more can be checked? I usually first do continuity test to see if there is a connection as sometimes there is no bonding. Also I never done that but planning to use one pole voltage reading next time to see existence of voltage and to see if its more than 50V or not.
@peterbradley4916
@peterbradley4916 10 ай бұрын
Surprisingly good!
@JPElectric
@JPElectric 10 ай бұрын
Thank you 🙂
@no_short_circuit
@no_short_circuit 2 жыл бұрын
Thanks for the video. I've always struggled with this topic but the graphics using hypothetical resistances helped. Confused when you said at 17.39 you say you can "calculate the Volt Drop on the R1 leg", then realised you'd included the external element of 0.175 ohms. Certainly helps and I'll bookmark this video for future reference. Just a quick question, why 240 volts and not 230 volts as used in most other calculations?
@JPElectric
@JPElectric 2 жыл бұрын
Thanks for the comment. I used 240, because I was using the touch voltage scenario from Paul Cooks Comment on the wiring regulations book, and he used 240V.
@ja_adam_
@ja_adam_ Жыл бұрын
Hi, are you supposed to test between extraneous and exposed conductive parts on an EICR and EIC? I’ve never been taught to ever test if this is needed
@ja_adam_
@ja_adam_ Жыл бұрын
Can you explain how you would know if you need supplementary bonding? Are you supposed to test between exposed and extraneous part in a bathroom
@ja_adam_
@ja_adam_ Жыл бұрын
I’ve never been tought to test between tap and exposed conductive part for example? Is this always supposed to be done ?
@heron9524
@heron9524 9 ай бұрын
Best to test with a megger as in insulation resistance test.. Put one lead of the megger onto a known earth in the bathroom i.e the earth in the light fitting and test it to the extraneous conductive part i.e the Tap in the bath. If the resistance is less that 1667 ohm there is no need to supplementary bond. If the resistance is between 1667 and 22000 ohms then it needs to be supplemtary bonded. Take a 2.5mm earth from light fitting and bond to tap. 50 volts is minimum touch voltage and resistance of human body is 1667 ohm approx. Divide 1667 into 50 volts result is .02 miliamps which is 20 miliamps. All bathrooms should be 30ma rcd protected. So that means rcd will trip as resistance has a low enough value for fault current to flow.
@ningis21
@ningis21 2 жыл бұрын
Hi...Thanks for the video. I was under the impression that 230 volts multiplied by the Cmin, was to be used in this type of callculation. ... Also, that the 50 volts was for use on a TT system, and you should use 230 volts on TN systems which if used along with an RCD would give 1667Ohms with 59 volts but 7667 ohms with 230 volts?
@JPElectric
@JPElectric 2 жыл бұрын
Thanks for the comment. You only need to use Cmin, to account for fluctuation in the supply voltage when finding Zs values. 50 volts in the maximum touch voltage allowed. The 1666 reading --- Supplementary bonding test is 50V not 59V ( 50/ 0.03 is 1666.66666...) Often rounded up to 1667. And the 230 V is for the extraneous CP test so for a 30mA RCD that would be 6.67kΩ, as you take 1000Ω off for the impedance of the human body
@heron9524
@heron9524 Жыл бұрын
@@JPElectric great video. So why is supplementary bonding test is at 50 volts? And extraneous bonding test is 230 volts? They both can indroduce a dangerous potential! I assume the supplemtary test is at 50 volts because water is more likely present! I.e water tap, radiator pipe etc.
@leroycfc
@leroycfc 2 жыл бұрын
Do you have an Instagram page ?
@JPElectric
@JPElectric 2 жыл бұрын
Hi Leroycfc, Not really, something I plan to get going.
@leroycfc
@leroycfc 2 жыл бұрын
@@JPElectric awesome mate ! Could you do a video to break down under floor heating systems?
Testing Zs - Why it is so important?
29:50
JPElectric
Рет қаралды 22 М.
Can This Bubble Save My Life? 😱
00:55
Topper Guild
Рет қаралды 84 МЛН
Using a TT earth where a TN earth already exists
23:49
John Ward
Рет қаралды 72 М.
Understanding your test results - Vital knowledge when testing.
13:27
Earthing and Bonding Part 1 - A SparkyNinja Webinar
1:18:51
SparkyNinja
Рет қаралды 23 М.
Maximum Earth fault loop impedance
27:21
JPElectric
Рет қаралды 10 М.
Diverted neutral Currents -  Is our electricity supply safe?
14:22
Essential Nikola Tesla Lecture from 1891
51:04
Master Ivo
Рет қаралды 39 М.
The Adiabatic Equation
7:36
JPElectric
Рет қаралды 4,4 М.
Earthing vs. Bonding: What's the Difference?
6:38
eFIXX
Рет қаралды 69 М.